1 / 30

A Chilled Water System Analysis Tool for Industrial Assessments

A Chilled Water System Analysis Tool for Industrial Assessments. Chiller System Optimization & Energy Efficiency Workshop September 2003 Presented by Michael Socks UMass Industrial Assessment Center. The Industrial Assessment Center at UMass-Amherst.

Download Presentation

A Chilled Water System Analysis Tool for Industrial Assessments

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. A Chilled Water System Analysis Tool for Industrial Assessments Chiller System Optimization & Energy Efficiency Workshop September 2003 Presented by Michael Socks UMass Industrial Assessment Center

  2. The Industrial Assessment Center at UMass-Amherst • The IAC performs no-cost, on-site energy efficiency, waste reduction, and productivity improvement assessments for small and mid-size manufacturers • Client Characteristics: 1) SIC Code 2000-3999 2) Annual energy bills of $100,000 to $2,000,000 3) Gross annual sales less than $100 million 4) Fewer than 500 employees at the plant site 5) No in-house staff to complete a similar assessment

  3. Summary of Operating Cost Reduction Measures Equipment-based Opportunities • Replace the chiller • Install NG or absorption chillers (Hybrid) • Install HX to recover condenser heat • Store thermal energy for peak use

  4. Summary of Operating Cost Reduction Measures Control-based Opportunities • Optimize chiller sequence • Raise chilled water temperature setting • Lower condenser cooling water temperature • Use variable speed capacity control • Use 2-speed or VSD control of tower fans • Use VSD control of pump flow • Use free cooling

  5. Summary of Operating Cost Reduction Measures Load-based Opportunities • Use chilled water efficiently • Distribute chilled water efficiently • Use optimal coil or heat exchanger size/design

  6. Program Introduction Purpose: Reduce the energy consumption of installed chilled water systems Goal: Create a simple but useful software tool for analyzing potential energy savings in chilled water systems

  7. Chilled Water System (Water-Cooled)

  8. Chilled Water System (Air-Cooled)

  9. Program Description Visual Basic Executable Program • User is prompted for system information • Program analyzes the existing system • User is prompted for changes to system • Program analyzes the proposed system • Program presents savings results

  10. Program Overview: Input Basic System Data: • Number of chillers (up to 5) • Chilled water supply temperature • Geographic location • Condenser cooling method (water or air)

  11. Program Overview: Input If chiller condensers are water-cooled: • Condenser cooling water supply temperature (if constant) • WB to cooling water temperature differential (if variable) • Cooling Tower Data (# towers, # cells/tower, motor hp, # motor speeds)

  12. Program Overview: Input If chiller condensers are air-cooled: • Cooling air design temperature • Average annual ambient air temperature (if indoor air is used for cooling) • DB to condenser temperature differential (if outdoor air is used for cooling)

  13. Program Overview: Input Pump Data: • Fixed or variable flow pumping • Flow rate [gpm/ton] • Nominal pump efficiency [%] • Nominal motor efficiency [%]

  14. Program Overview: Input Chiller Data: • Chiller compressor type • Chiller capacity • Chiller full load efficiency (if known) • Chiller age

  15. Program Overview: Input Energy Cost Data: • Average electricity cost [$/kWh] • Average NG cost [$/MMBtu] System Control Data: • System operating schedule • System loading schedule

  16. Program Overview: Cost Reduction Cost Reduction Measures to Consider: • Increase chilled water supply temperature • Decrease chiller condenser temperature • Upgrade to 2-speed or variable speed tower fan motors • Upgrade to variable speed pump motor control • Replace chillers (use more efficient or NG units) • Replace refrigerant • Install VSD on chiller compressor motor (centrifugal only) • Use free cooling • Sequence chillers

  17. Program Overview: Output Output Information: • Annual chiller energy consumption (kWh and/or MMBtu) and cost • Annual cooling tower energy consumption (kWh) and cost • Annual pump energy consumption (kWh) and cost • Total annual energy consumption and cost

  18. Program Overview: Output Chiller energy may be viewed by: • Chiller • Load Cooling tower energy may be viewed by: • Wet-bulb temperature group Pump energy may be viewed by: • Chiller

  19. Example Let’s run an example . . . • (3) 200 ton water-cooled chillers (centrifugal) • 44 ºF chilled water temperature • Located in Boston, Massachusetts • Condenser cooling water is held constant at 85 ºF • (1) 2-cell tower with 15 hp 2-speed motors • Chilled water flow is constant [2.4 gpm/ton] • Condenser water flow is constant [3.0 gpm/ton] • Electricity is $0.06 per kWh • Operates 24/7 and serves an air-conditioning load • Install VSDs on each chiller compressor motor

  20. Example: Input Screen

  21. Output Summary: Chillers: 2,187,676 kWh (92%) Tower: 4,768 kWh (< 1%) Pumps: 193,934 kWh (8%) Total Energy: 2,386,378 kWh Total Cost: $143,183 Example: Output Screen

  22. Operating Cost Reduction Measure: Install a VSD on each Centrifugal Compressor Motor Example: Operating Cost Reduction Opportunities Screen

  23. Savings Summary: 598,797 kWh/yr $35,928/yr Example: Savings Screen

  24. Case Study: Application Manufacturer of laminated circuit boards uses chilled water for process cooling and space conditioning Process Cooling • Laminating oven cool-down cycle • Plating fluid temperature control Space Conditioning • ~ 50,000 ft2 clean rooms • Office and manufacturing floor air conditioning

  25. Case Study: System Specs Chilled Water System Summary • (2) 250-ton helical rotary chillers (1997) • (2) 350-ton helical rotary chillers (2001) • 45ºF chilled water; 2.4 gpm/ton • 75ºF condenser water; 3.0 gpm/ton • (4) cooling towers; (3) 15-hp fans each (2-speed) • Operates 24/7 year-round • Free cooling is used when possible

  26. Case Study: System Loading Typical Loading Schedule • 20% load for 25% of year • 30% load for 25% of year • 40% load for 25% of year • 50% load for 25% of year Note: These are average system loads. Individual chiller loading will differ.

  27. Case Study: Results

  28. Case Study: Prediction vs. Actual Without Using Free Cooling • 3,478,905 kWh actual • 3,436,931 kWh predicted • Difference: 41,974 kWh (-1.2%) With Free Cooling • 489,054 kWh and $41,570 actual savings • 608,720 kWh and $51,744 predicted savings • Difference: 119,666 kWh and $10,174 (+24%)

  29. Chiller and pumping energy decrease by approximately 22% Tower energy increases by approximately 63% Case Study: Other Observations

  30. Closing Comments • The Program IS NOT intended to determine system energy use down to the kWh or MMBtu • Program IS intended to direct analysis effort toward the most promising cost reduction opportunities • I need your help to make this program better: 1) Download the program from www.ceere.org 2) E-mail questions, suggestions, errors, etc. to me at msocks@ecs.umass.edu • Any questions?

More Related