1 / 20

Objectives

Objectives. Discuss Project Topics Learn to design VAV and DOAS System. 3D model – Biomedical Engineering (BME) Building. 3D model – Biomedical Engineering (BME) Building. 3D model – Biomedical Engineering (BME) Building. 3D model – Biomedical Engineering (BME) Building. VAV Example .

fai
Download Presentation

Objectives

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Objectives • Discuss Project Topics • Learn to design VAV and DOAS System

  2. 3D model – Biomedical Engineering (BME) Building

  3. 3D model – Biomedical Engineering (BME) Building

  4. 3D model – Biomedical Engineering (BME) Building

  5. 3D model – Biomedical Engineering (BME) Building

  6. VAV Example • One system • Multiple Spaces/Zones • - VAV box for each space/zone http://www.trane.com/commercial/library/vol242/v24b6.asp

  7. VAV System Terms & Equations(you can find them in ASHRAE Standard 62) • Fraction of minimum outdoor air in space/zone supply air Xi = VOAi / VSAi • Critical space Space with maximumXi , Z=max(Xi) • Fraction of outdoor air in system supply air X = sum(VOA ) / sum(VSA) • Required Fraction of outdoor air: Y=X/(1+X-Z)

  8. Example Solution

  9. Other Issues Related to VAV • Fan control • Minimum supply air • Occupancy sensors

  10. DOAS System • http://doas.psu.edu/

  11. Enthalpy wheel

  12. Figure 3 – A desiccant-based cooling system combined with regenerative heat exchanger, vapor compression cooling, and evaporative humidifier (hybrid system). Desiccant wheel

  13. HVAC Control Example 1: Economizer (fresh air volume flow rate control) Controlled device is damper - Damper for the air - Valve for the liquids fresh air damper mixing recirc. air T & RH sensors

  14. Economizer Fresh air volume flow rate control % fresh air 100% enthalpy Fresh (outdoor) air TOA (hOA) Minimum for ventilation damper mixing Recirc. air T & RH sensors

  15. Economizer – cooling regime How to control the fresh air volume flow rate? If TOA < Tset-point→ Supply more fresh air than the minimum required The question is how much? Open the damper for the fresh air and compare the Troom with the Tset-point . Open till you get the Troom = Tset-point If you have 100% fresh air and your still need cooling use cooling coil. What are the priorities: - Control the dampers and then the cooling coils or - Control the valves of cooling coil and then the dampers ? Defend by SEQUENCE OF OERATION the set of operation which HVAC designer provides to the automatic control engineer % fresh air 100% Minimum for ventilation

  16. Economizer – cooling regime Example of SEQUENCE OF OERATIONS: If TOA < Tset-point open the fresh air damper the maximum position Then, if Tindoor air < Tset-point start closing the cooling coil valve If cooling coil valve is closed and T indoor air < Tset-point start closing the damper till you get T indoor air = T set-point Other variations are possible

  17. HVAC Control Example 2: Dew point control (Relative Humidity control) fresh air damper filter cooling coil heating coil filter fan mixing T & RH sensors Heat gains Humidity generation We should supply air with lower humidity ratio (w) and lower temperature We either measure Dew Point directly or T & RH sensors substitute dew point sensor

  18. Relative humidity control by cooling coil Cooling Coil Mixture Room Supply TDP Heating coil

  19. Relative humidity control by cooling coil (CC) • Cooling coil is controlled by TDP set-point if TDP measured > TDP set-point → send the signal to open more the CC valve if TDP measured < TDP set-point → send the signal to close more the CC valve • Heating coil is controlled by Tair set-point • if Tair < Tair set-point → send the signal to open more the heating coil valve • if Tair > Tair set-point → send the signal to close more the heating coil valve Control valves Fresh air mixing cooling coil heating coil Tair & TDP sensors

  20. Mixture 3 DPTSP Set Point (SP) Mixture 2 Mixture 1 DBTSP Sequence of operation(ECJ research facility) Control logic: Mixture in zone 1: IF (( TM<TSP) & (DPTM<DPTSP) ) heating and humidifying Heater control: IF (TSP>TSA) increase heating or IF (TSP<TSA) decrease heating Humidifier: IF (DPTSP>DPTSA) increase humidifying or IF (DPTSP<DPTSA) decrease humid. Mixture in zone 2: IF ((TM>TSP) & (DPTM<DPTSP) ) cooling and humidifying Cool. coil cont.: IF (TSP<TSA) increase cooling or IF (TSP>TSA) decrease cooling Humidifier: IF (DPTSP>DPTSA) increase humidifying or IF (DPTSP<DPTSA) decrease hum. Mixture in zone 3: IF ((DPTM>DPTSP) ) cooling/dehumidifying and reheatin Cool. coil cont.: IF (DPTSP>DPTSA) increase cooling or IF (DPTSP<DPTSA) decrease cooling Heater control: IF (TSP>TSA) increase heating or IF (TSP<TSA) decrease heating

More Related