IEC 61850 enabled UniGear

0 1 0 0 1 1 0 0 1 0 0 1 1 0 1 0 1 0 1 0 0 1 0 1 0 1 1 1 1 0 0 0 1 0 1 0 1 0 1 0 0 1 1 0 0 0 1 1 1 0 0 1 0 1 0 1 0 1 0 1 1 0 1 0 1 0 1 1 1 1 0 0 0 1 1 0 1 0 1 0 0 1 0 1 0 1 0 1 0 1 0 0 0 0 1 0 1 0 1 0 1 0 1 0 1 0 1 1 1 1 1 1 1 0 1 0 1 0 1 0 . May 2013. IEC 61850 enabled UniGear. Tenders.

freira
Download Presentation

IEC 61850 enabled UniGear

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. 0 1 0 0 1 1 0 0 1 0 0 1 1 0 1 0 1 0 1 0 0 1 0 1 0 1 1 1 1 0 0 0 1 0 1 0 1 0 1 0 0 1 1 0 0 0 1 1 1 0 0 1 0 1 0 1 0 1 0 1 1 0 1 0 1 0 1 1 1 1 0 0 0 1 1 0 1 0 1 0 0 1 0 1 0 1 0 1 0 1 0 0 0 0 1 0 1 0 1 0 1 0 1 0 1 0 1 1 1 1 1 1 1 0 1 0 1 0 1 0 May 2013 IEC 61850 enabled UniGear Tenders

  2. IEC 61850 enabled MV Primary switchgear Main Accessories H01 H02 H03 H04 H05 • ABB’s Relion® IEDs with IEC 61850 native support • Managed Ethernet Switch/es • Communication Links

  3. IEC 61850 enabled MV Primary switchgear Main Accessories / IED with IEC 61850-8-1 interface • Converter is needed (communication gateway, card …) • Supported communication • Vertical

  4. IEC 61850 enabled MV Primary switchgear Main Accessories / IED with IEC 61850-8-1 interface • Relion® protection and control • True, native support for IEC 61850 • Supported communications • Vertical • Horizontal GOOSE • Dedicated web page • www.abb.com/relion

  5. IEC 61850 enabled MV Primary switchgear Main Accessories / Ethernet Switch • ABB AFS family • Managed Ethernet Switch • “Substation hardened” to the same level as IEDs • Recommended to use all switches from the same vendor, especially when building ring architecture

  6. IEC 61850 enabled MV Primary switchgear Main Accessories / Ethernet Switch • Managed Ethernet Switch • Type of switch • Compact – Fixed number of ports (connections) • Modular – Variable number of ports and their types • Type of Port • Copper / Fiber

  7. IEC 61850 enabled MV Primary switchgear Main Accessories / Communication Links • Patch cord (cable) • Electrical or optical cable used to connect one device to another for data routing • It is terminated by connectors on both ends • Electrical cable is susceptible to EMI, therefore should be only used inside cabinets • Optical: Duplex Patch cord with LC-LC connectors • Electrical : STP cable Cat.6 or better with RJ45-RJ45 connectors RJ45 LC

  8. IEC 61850 enabled MV Primary switchgear Single Network Architecture … … • Typical architecture • IEDs are connected directly to Managed Ethernet switch • Supported by all IEDs • Backbone Ring network

  9. IEC 61850 enabled MV Primary switchgear Ring (Self-healing) max. 30 IEDs • Data is sent into both directions on the ring • Essential part is Managed Ethernet switch • Supported by 611, 615 (except RED), 620 Series IEDs

  10. IEC 61850 enabled MV Primary switchgear Ring (HSR) - Redundant Network Architecture max. 30 IEDs • High-availability Seamless Redundancy (HSR) • Same data is sent into both directions on the ring • Eliminating communication downtime • Supported by 615 Series IEC (except RED) and 620 Series IEC

  11. IEC 61850 enabled MV Primary switchgear Double (PRP) - Redundant Network Architecture LAN B LAN A • Parallel Redundancy Protocol (PRP) • Same data is sent to both networks with identical topology • Eliminating communication downtime • Supported by 615 Series IEC (except RED) and 620 Series IEC

  12. IEC 61850 enabled MV Primary switchgear Ethernet Network Topology • Ring • Built-in redundancy • Centralized /Decentralized • Interconnection • Fiber optic • Ring Network Topology • Decentralized ring Architecture

  13. IEC 61850 enabled MV Primary switchgear Accessories Layout • Location • Inside Low Voltage Compartment of the switchgear panels • Typically in Bus riser, Metering panel • Main benefits • Cubicles are ready for connection • Saving space in substation building • Shorter communication links • Cheaper solution • Ethernet switch RSG2100 assembled in LVC of UniGear

  14. IEC 61850 enabled MV Primary switchgear UniGear Pro • Global Tendering Tool for Air-insulated UniGear panels

  15. IEC 61850 enabled MV Primary switchgear IED Communication Protocol and Media 2. Select tab Control • 3. Select IED Communication protocol • IEC61850 Single + GOOSE • IEC61850 Ring (Self-healing) + GOOSE • IEC61850 Ring (HSR) + GOOSE • IEC61850 Double (PRP) + GOOSE • IEC61850 Single • IEC61850 Ring (Self-healing) • IEC61850 Ring (HSR) • IEC61850 Double (PRP) • 4. Select Communication media • Galvanic (RJ45) • Optic Glass Fiber 1. Open Switchgear data window

  16. IEC 61850 enabled MV Primary switchgear Intelligent Electronic Device (Relay) 2. Select tab Functional unit 3. Select sub-tab Relays 1. Open Panel data window • 5. Select Relay • Applied filters • Communication protocol • Communication medium 4. Press Add button 6. Press OK button

  17. IEC 61850 enabled MV Primary switchgear Ethernet Switches 2. Select tab Additional articles 4. Select Make ABB … 3. Select Type Communications 5. Select Variant Ethernet Switches 6. Select Type of Ethernet Switch 7. Press Add button 1. Open Switchgear data or Panel data window

  18. IEC 61850 enabled MV Primary switchgear Communication cables (Patchcords) 3. Select sub-tab Additional articles 2. Select tab Functional unit 4. Select Type Communications 6. Select Variant Patchcords 5. Select Make Miscellaneous 7. Select Type of Patchcord 8. Press Add button 1. Open Switchgear data or Panel data window