210 likes | 324 Views
Objectives. Finish with Heat exchangers Learn about Specifics of VAV and DOAS systems. Heat exchanger performance (Book Section 11.3). NTU – absolute sizing (# of transfer units) ε – relative sizing (effectiveness). Summary. Calculate efficiency of extended surface
E N D
Objectives • Finish with Heat exchangers • Learn about Specifics of VAV and DOAS systems
Heat exchanger performance (Book Section 11.3) • NTU – absolute sizing (# of transfer units) • ε – relative sizing (effectiveness)
Summary • Calculate efficiency of extended surface • Add thermal resistances in series • If you know temperatures • Calculate R and P to get F, ε, NTU • Might be iterative • If you know ε, NTU • Calculate R,P and get F, temps
Reading Assignment • Chapter 11 - From 11.1-11.7
Analysis of Moist Coils • Redo fin theory • Energy balance on fin surface, water film, air Introduce Lewis Number • Digression – approximate enthalpy • Redo fin analysis for cooling/ dehumidification (t → h)
Energy and mass balances • Steady-state energy equation on air • Energy balance on water • Mass balance on water
4. Fin analysis for wet fins Heat conduction only occurs in y-direction through water film
Overall Heat Transfer Coefficients • Very parallel procedure to dry coil problem • U-values now influenced by condensation • See Example 11.6 for details
Wet Surface Heat Transfer • If you know dry surface heat transfer • Reynolds number changes – empirical relationships • Approximate wet-surface • Does a wet or a dry coil have higher or lower heat exchange? • Does a wet or a dry coil have higher or lower pressure drop?
HW4(posted on the website) Homework Assignment # 4 Pat A DUE: April 9, 2013 • Problem 11.1 (page 326) • Problem 11.7 (page 327) • Designs Problem For the problem #9 from the HW assignment 2 (design process in AHU) calculate the needed a) Effectiveness of the cooling coil b) UoAo value for the CC Assume Inlet water temperature into CC is coil is 45ºF Homework Assignment # 4 Pat B DUE: April 16, 2013 • Problem 18.13 • Problem 18.16 • Problem 18.19 • Problem 18.20 • Problem 18.27
VAV Example • One system • Multiple Spaces/Zones • - VAV box for each space/zone • http://www.trane.com/commercial/library/vol242/v24b6.asp
VAV System Terms & Equations(you can find them in ASHRAE Standard 62) • Fraction of minimum outdoor air in space/zone supply air Xi = VOAi / VSAi • Critical space Space with maximumXi , Z=max(Xi) • Fraction of outdoor air in system supply air X = sum(VOA ) / sum(VSA) • Required Fraction of outdoor air: Y=X/(1+X-Z)
Other Issues Related to VAV • Reheaters (sizing and control) • Fan control • Minimum supply air • Occupancy sensors
DOAS System • www.doas.psu.edu
DOAS with multi-split systems Fresh air?
Issues Related to DOAS • Split of sensible and latent load • Selection of hydronic system • Winter vs. summer operation • Winter operation with DX systems (heat pump)