ZE Ready Electric board

ZE Ready Electric board. Functionality of Electrical board. Safety and protections User protections Equipment protections Cluster and energy management Manage and control access right for RFID use

Download Presentation

ZE Ready Electric board

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. ZE Ready Electric board

  2. Functionality of Electrical board • Safety and protections • User protections • Equipment protections • Cluster and energy management • Manage and control access right for RFID use • Manage the power allocation between each charging spot (throught PWM functionality inside the charging point) • Energy management to interface with the building electrical distribution

  3. Example

  4. Safety and Protection Upstream main protection • Lighting protection • Main circuit breaker (depending of the number of charging spot) For each charging spot • Auxiliary line for control device inside charging spot: • Circuit Breaker D curve 4A to avoid nuisance triping due to power supply (Add reference Schneider 4A) • Differential 30 mA type A/SI (Add reference Schneider for 4 A power) • Auxiliary contact to report status to PLC • 1 or 2 Power Line 3 phase (up to 22KW) in function of the number of plugs • Circuit Breaker D curve 40A to avoid nuisance triping due to transient current (Add reference Schneider 40A) • Differential 30 mA type B (Add reference Schneider for 40 A power) According to Renault derogation differential 30mA type A/SI can be use • Auxiliary contact to report status to PLC • Under voltage actuator (MNX) (Add reference Schneider for 40 A power)

  5. Cluster and energy management PLC Modicom M340 (Example) • BMXXBP0X00 RACK X POSITIONS • BMXCPS2000 ALIM AC STANDARD • BMXP342020 CPU340-20 MODBUS ETHERNET • BMXDDI3202K DIG 32I 24 VDC SINK • BMXDRA1605 DIG 16Q RELAYS • BMXNOE0110 CPL. FACTORYCAST M340 • TCSESU053FN0 CONNEXIUM UNMANAGED SWITCH • ABL8RPS24100 ALIMENTATION • Energy meter for each plug • Energy sensor and meter for the building • Current transformer (depend on the building main circuit breaker) • Power monitoring device • RFID Cards