250 likes | 482 Views
Tracer ES. Trane Control and ASHRAE Gannett Fleming Engineering. Jack Gornik Trane Commercial Systems Harrisburg, PA. Controls and ASHRAE 90.1-2010. Existing controls requirements Fan pressure optimization (Today) Demand control ventilation (DCV) (Today) Changes to controls requirements
E N D
Tracer ES Trane Control and ASHRAE Gannett Fleming Engineering Jack Gornik Trane Commercial Systems Harrisburg, PA
Controls and ASHRAE 90.1-2010 • Existing controls requirements • Fan pressure optimization (Today) • Demand control ventilation (DCV) (Today) • Changes to controls requirements • Ventilation reset (Today) • Pump pressure optimization (Today) • Trane Controls Update
Fan Pressure Optimization • Required by ASHRAE 90.1 since 1999 *When system design is > 10,000 CFM • Goal: • Control system static pressure to the lowest level while maintaining zone airflow requirements; thereby minimizing fan energy consumption • What is required for implementation? • Communicating controls on the VAV boxes • Static pressure sensor • Building automation system
Fan-Pressure Optimization • The BAS determines the “most open” damper in the system • The system static pressure is controlled to keep the “most open” zone damper between 65% and 75% open • With this strategy, location of sensor is not critical • Take advantage of labor savings and mount the sensor at the fan discharge • Saves 20% to 45% of the system fan energy • Significant acoustical benefits
Defobj VAV[boxes], // array of vav box objects (array size = boxes) setpoint // object used to store the calculated setpt Defflt maxpos, // the maximum air valve position staticsp, // calculation of the static pressure setpoint increment = 0.1, // amount by which the the setpoint may be changed high_limit = 95.0, // adjust setpoint up if max greater than this value low_limit = 85.0, // adjust setpoint down if max less than this value initial_staticsp = 2.0, // initial static pressure setpoint min_staticsp = 0.5, // minimum static pressure setpoint allowed max_staticsp = 3.0 // maximum static pressure setpoint allowed // define the property (from the database) that confirms that the // AHU is running. // IMPORTANT! Use the Add Obj&Property selection under the Edit menu // to select the correct property. ahu_status = {RTU-3 Engineering}.{Supply Fan Status} // define the AOP object (from the database) for the vav boxes served // by a particular air handling unit. This AOP should be referenced // by the ahu as its static pressure setpoint // IMPORTANT! Use the Add Object selection under the Edit menu // to select the correct objects. setpoint = {RTU-3 Static Pressure Setpt} // load the object array with the VAV objects VAV[1] = {VAV 3-01 Engineering} VAV[2] = {VAV 3-02 South America Conf. Rm} VAV[3] = {VAV 3-03 Engineering} VAV[4] = {VAV 3-04 Engineering} VAV[5] = {VAV 3-05 Engineering} VAV[6] = {VAV 3-06 Engineering} VAV[7] = {VAV 3-07 Engineering} VAV[8] = {VAV 3-08 Engineering} VAV[9] = {VAV 3-09 Test Room} VAV[10] = {VAV 3-10 Hardware Lab} VAV[11] = {VAV 3-11 Order Fulfillment} VAV[12] = {VAV 3-12 Order Fulfillment} VAV[13] = {FP VAV 3-01 Engineering} VAV[14] = {FP VAV 3-02 Engineering} VAV[15] = {FP VAV 3-03 Asia Conf. Room} VAV[16] = {FP VAV 3-04 Order Fulfillment} VAV[17] = {FP VAV 3-05 Corridor} VAV[18] = {FP VAV 3-06 Corridor} PROGRAM VAV_Critical_Zone_Reset_RTU_3 // Written: // Modified: 03/98 // Properties Read: VAV[i].{Communication State} // VAV[i].{Diag: Flow Sensor Fail} // VAV[i].{Control Mode} // VAV[i].{Air Valve Position} // VAV[i].{Communication Address} // Properties Modified: setpoint.{Present Value} // Routine Summary: /// This routine calculates the static pressure setpoint for an air /// handling unit. It resets the AHU static pressure setpoint based on /// a "critical zone". VAV terminal units' maximum air valve position /// is determined, which is the basis for calculating an AHU static pressure /// setpoint. The AHU static pressure setpoint is adjusted to satisfy /// the critical zone, which inherently satisfies all other zones. // Fan horsepower is minimized and comfort in all spaces is maintained. // For background information about this routine, see SYS-EB-2. // This cpl object, the AHU object and all (or the majority of) the VAV // objects should reside in the same BCU. (Do not put this cpl object in // one BCU if the VAV boxes and AHU reside in another BCU.) /// Routine Execution: This program is executed every 1 minute. // Note: this routine executes every minute but the reset calculation is // done only at a user defined interval (usually much less frequently). /// Routine Text File: VAV_CZR3.CPL // ***** Define Variables ***** // In this section, the programmer defines the variables used throughout // this routine. The only variables that require editing are in the "User // Edited Variables" section. No other changes are required. Defint On = 1, // define enumeration Up = 1, // define enumeration Normal = 0, // define enumeration Occupy = 0, // define enumeration for VAV control mode i, // index used in the For-Next loop ahu_status, // status feedback from AHU ahu_timer, // number of minutes since the ahu started // ***** begin User Edited Variables ***** startup_delay = 30, // number of minutes after the ahu starts before // allowing the reset to occur reset_interval = 15, // number of minutes between reset calculations // Reset Interval will depend on actual system dynamics. // Tuning the reset interval should be done with // the system operating. boxes = 18 // number of vav boxes included in the calculation 2.0 // ***** end User Edited Variables ***** // No changes are required beyond this point. // ***** ahu timer ***** // In this section a counter keeps the number of minutes the ahu // status shows the unit has been On. The counter is stored in // Local.{Saved Value}[16]. If the ahu status is Off the counter is // reset to 0 and the setpoint is reset to its user defined initial // value. The routine also stops if the ahu status is Off; there is // no reason to run the rest of the routine with the ahu Off. This // counter is used to verify the ahu has been On a user defined // number of minutes before allowing the static pressure to be // adjusted. ahu_timer = Local.{Saved Value}[16] If (ahu_status = On) Then ahu_timer = ahu_timer + 1 Else Local.{Saved Value}[16] = 0 If (setpoint.{Present Value} <> initial_staticsp) Then CONTROL(setpoint,{Present Value},initial_staticsp,16,Set) End If Stop End If Local.{Saved Value}[16] = ahu_timer // ***** vav box data ***** // In this section the air valve position is read from each vav box that // is communicating with the bcu and has a valid air flow reading. A // failed flow results in air valve position based control. This strategy // requires "pressure independent" flow control. The vav UCMs must be // in occupied mode and communicating with the bcu to properly read // values and perform calculations. This for-next loop finds the position // of the most open VAV box air valve. The routine will only find the // most open box after the ahu has gone through its user defined startup // delay. It only performs the rest of the routine every user interval, not // every minute. // No changes are required in this section. If (Local.{Saved Value}[1] >= reset_interval) and (ahu_timer > startup_delay) Then Local.{Saved Value}[1] = 0 Local.{Saved Value}[2] = 0 For i = 1 To boxes Step 1 If (VAV[i].{Communication State} = Up) and (VAV[i].{Diag: Flow Sensor Fail} = Normal) and (VAV[i].{Control Mode} = Occupy) Then If (VAV[i].{Air Valve Position} > maxpos) Then maxpos = VAV[i].{Air Valve Position} Local.{Saved Value}[2] = VAV[i].{Communication Address} End If End If Next Else 2.5 Local.{Saved Value}[1] = Local.{Saved Value}[1] + 1 Stop End If Local.{Saved Value}[3] = maxpos // ***** adjust setpoint ***** // If the maximum air valve position is greater than the high limit the static // pressure setpoint is increased. If it is less than the low limit the setpoint // is decreased. The setpoint is adjusted only if the air handling unit is On and // the maximum air valve position is nonzero. It will be zero if all boxes // are not communicating or if all the flow sensors have failed. It will also // be zero if all boxes are unoccupied, (with unocc min allowed to go to zero). // The setpoint will be set to the user defined initial setpoint if the adjustment // calculation is not done. After the setpoint is calculated, it is verified that // it does not exceed its minimum or maximum. // No changes are required in this section. staticsp = setpoint.{Present Value} If (maxpos <> 0.0) Then If (maxpos > high_limit) Then staticsp = (staticsp + increment) End If If (maxpos < low_limit) Then staticsp = (staticsp - increment) End If Else staticsp = initial_staticsp End If staticsp = Min (staticsp, max_staticsp) staticsp = Max (staticsp, min_staticsp) // ***** control AOP ***** // Control the analog output to the calculated static pressure // setpoint only if it has changed. // No changes are required in this section. If (setpoint.{Present Value} <> staticsp) Then CONTROL(setpoint,{Present Value},staticsp,16,Set) End If End // end of routine 1.0 0.1 75 65 15 Typical Way Tracer Summit Standard Applications The Trane Way Repeatable - performance from building to building and job to job
System Performance Summary Sustainable - performance over the life of the installation Provable - demonstrate we are providing the functions as promised
Demand Control Ventilation (DCV) • Required by ASHRAE 90.1 2007 • Background: • VAV systems are designed to bring in at least the minimum outdoor airflow at worst case conditions • At any other condition, design airflow results in over-ventilation • Goal: • Reduce over-ventilating a space by resetting the level of outdoor air introduced during times when occupancy is lower than design conditions
Demand Control Ventilation (DCV) • Methods – determine required ventilation rate • Occupancy sensors • Detect the presence of people in each monitored space • Occupancy schedules • Predict the current population based on the time of day • Carbon dioxide (CO2) sensors • Monitor the concentration of CO2 that the occupants continuously produce • Each are appropriate for different types of zone
Demand Control Ventilation (DCV) • Required at zone level if: • Larger than 500 ft2 • Design occupant density greater than 40 people per 1,000 ft2 • Served by system with one or more of the following: • An air-side economizer • Automatic modulating control of the outdoor air damper OR • A design outdoor airflow greater than 3,000 cfm
Ventilation Optimization : System Level Ventilation Reset • Required by ASHRAE 90.1 2010 • Multiple zone VAV systems with DDC shall: • Automatically reduce outdoor air intake flow below design rates in response to changes in system ventilation efficiency as defined by ASHRAE Standard 62.1, Appendix A. • Exceptions: • Systems required to have energy recovery in 6.5.6.1 • Some dual-path systems, such as dual-duct dual-fan or fan-powered VAV systems • Systems where the design exhaust airflow is more than 70% of the design outdoor air intake airflow
Outside Air Delivered Outside Air Required by ASHRAE62.1-2004 Stategy #3: Allowing reset Traq Damper Strategy #1: Damper Fixed at 67% Strategy #2: OA Flow Control at 933 cfm Design SA = 3000 = 1000 + 1000 + 1000 OA = 700 = 200 + 200 + 300 Vent Fraction = 0.20 0.20 0.30 25% or750 cfm 25% or750 cfm 2010 cfm 31% Critical Zone 1260 cfm excess 183 cfm excess 70% SA = 2100 = 650 + 550 + 900 OA = 700 = 200 + 200 + 300 Vent Fraction = 0.31 0.36 0.33 34% or714 cfm 34% or714 cfm 1474 cfm 42% 40% SA = 1400 = 500 + 500 + 400 OA = 700 = 200 + 200 + 300 Vent Fraction = 0.40 0.40 0.75 67% or933 cfm 67% or933 cfm 933 cfm 67% Worst case Note: Credit for unused air OA requirements for a Multiple-Space System –System Load–
Ventilation Optimization Application Defobj VAV[boxes], // array of vav box objects (array size = boxes) setpoint // object used to store the calculated setpt Defflt maxpos, // the maximum air valve position staticsp, // calculation of the static pressure setpoint increment = 0.1, // amount by which the the setpoint may be changed high_limit = 95.0, // adjust setpoint up if max greater than this value low_limit = 85.0, // adjust setpoint down if max less than this value initial_staticsp = 2.0, // initial static pressure setpoint min_staticsp = 0.5, // minimum static pressure setpoint allowed max_staticsp = 3.0 // maximum static pressure setpoint allowed // define the property (from the database) that confirms that the // AHU is running. // IMPORTANT! Use the Add Obj&Property selection under the Edit menu // to select the correct property. ahu_status = {RTU-3 Engineering}.{Supply Fan Status} // define the AOP object (from the database) for the vav boxes served // by a particular air handling unit. This AOP should be referenced // by the ahu as its static pressure setpoint // IMPORTANT! Use the Add Object selection under the Edit menu // to select the correct objects. setpoint = {RTU-3 Static Pressure Setpt} // load the object array with the VAV objects VAV[1] = {VAV 3-01 Engineering} VAV[2] = {VAV 3-02 South America Conf. Rm} VAV[3] = {VAV 3-03 Engineering} VAV[4] = {VAV 3-04 Engineering} VAV[5] = {VAV 3-05 Engineering} VAV[6] = {VAV 3-06 Engineering} VAV[7] = {VAV 3-07 Engineering} VAV[8] = {VAV 3-08 Engineering} VAV[9] = {VAV 3-09 Test Room} VAV[10] = {VAV 3-10 Hardware Lab} VAV[11] = {VAV 3-11 Order Fulfillment} VAV[12] = {VAV 3-12 Order Fulfillment} VAV[13] = {FP VAV 3-01 Engineering} VAV[14] = {FP VAV 3-02 Engineering} VAV[15] = {FP VAV 3-03 Asia Conf. Room} VAV[16] = {FP VAV 3-04 Order Fulfillment} VAV[17] = {FP VAV 3-05 Corridor} VAV[18] = {FP VAV 3-06 Corridor} PROGRAM VAV_Critical_Zone_Reset_RTU_3 // Written: // Modified: 03/98 // Properties Read: VAV[i].{Communication State} // VAV[i].{Diag: Flow Sensor Fail} // VAV[i].{Control Mode} // VAV[i].{Air Valve Position} // VAV[i].{Communication Address} // Properties Modified: setpoint.{Present Value} // Routine Summary: /// This routine calculates the static pressure setpoint for an air /// handling unit. It resets the AHU static pressure setpoint based on /// a "critical zone". VAV terminal units' maximum air valve position /// is determined, which is the basis for calculating an AHU static pressure /// setpoint. The AHU static pressure setpoint is adjusted to satisfy /// the critical zone, which inherently satisfies all other zones. // Fan horsepower is minimized and comfort in all spaces is maintained. // For background information about this routine, see SYS-EB-2. // This cpl object, the AHU object and all (or the majority of) the VAV // objects should reside in the same BCU. (Do not put this cpl object in // one BCU if the VAV boxes and AHU reside in another BCU.) /// Routine Execution: This program is executed every 1 minute. // Note: this routine executes every minute but the reset calculation is // done only at a user defined interval (usually much less frequently). /// Routine Text File: VAV_CZR3.CPL // ***** Define Variables ***** // In this section, the programmer defines the variables used throughout // this routine. The only variables that require editing are in the "User // Edited Variables" section. No other changes are required. Defint On = 1, // define enumeration Up = 1, // define enumeration Normal = 0, // define enumeration Occupy = 0, // define enumeration for VAV control mode i, // index used in the For-Next loop ahu_status, // status feedback from AHU ahu_timer, // number of minutes since the ahu started // ***** begin User Edited Variables ***** startup_delay = 30, // number of minutes after the ahu starts before // allowing the reset to occur reset_interval = 15, // number of minutes between reset calculations // Reset Interval will depend on actual system dynamics. // Tuning the reset interval should be done with // the system operating. boxes = 18 // number of vav boxes included in the calculation // ***** end User Edited Variables ***** // No changes are required beyond this point. // ***** ahu timer ***** // In this section a counter keeps the number of minutes the ahu // status shows the unit has been On. The counter is stored in // Local.{Saved Value}[16]. If the ahu status is Off the counter is // reset to 0 and the setpoint is reset to its user defined initial // value. The routine also stops if the ahu status is Off; there is // no reason to run the rest of the routine with the ahu Off. This // counter is used to verify the ahu has been On a user defined // number of minutes before allowing the static pressure to be // adjusted. ahu_timer = Local.{Saved Value}[16] If (ahu_status = On) Then ahu_timer = ahu_timer + 1 Else Local.{Saved Value}[16] = 0 If (setpoint.{Present Value} <> initial_staticsp) Then CONTROL(setpoint,{Present Value},initial_staticsp,16,Set) End If Stop End If Local.{Saved Value}[16] = ahu_timer // ***** vav box data ***** // In this section the air valve position is read from each vav box that // is communicating with the bcu and has a valid air flow reading. A // failed flow results in air valve position based control. This strategy // requires "pressure independent" flow control. The vav UCMs must be // in occupied mode and communicating with the bcu to properly read // values and perform calculations. This for-next loop finds the position // of the most open VAV box air valve. The routine will only find the // most open box after the ahu has gone through its user defined startup // delay. It only performs the rest of the routine every user interval, not // every minute. // No changes are required in this section. If (Local.{Saved Value}[1] >= reset_interval) and (ahu_timer > startup_delay) Then Local.{Saved Value}[1] = 0 Local.{Saved Value}[2] = 0 For i = 1 To boxes Step 1 If (VAV[i].{Communication State} = Up) and (VAV[i].{Diag: Flow Sensor Fail} = Normal) and (VAV[i].{Control Mode} = Occupy) Then If (VAV[i].{Air Valve Position} > maxpos) Then maxpos = VAV[i].{Air Valve Position} Local.{Saved Value}[2] = VAV[i].{Communication Address} End If End If Next Else Local.{Saved Value}[1] = Local.{Saved Value}[1] + 1 Stop End If Local.{Saved Value}[3] = maxpos // ***** adjust setpoint ***** // If the maximum air valve position is greater than the high limit the static // pressure setpoint is increased. If it is less than the low limit the setpoint // is decreased. The setpoint is adjusted only if the air handling unit is On and // the maximum air valve position is nonzero. It will be zero if all boxes // are not communicating or if all the flow sensors have failed. It will also // be zero if all boxes are unoccupied, (with unocc min allowed to go to zero). // The setpoint will be set to the user defined initial setpoint if the adjustment // calculation is not done. After the setpoint is calculated, it is verified that // it does not exceed its minimum or maximum. // No changes are required in this section. staticsp = setpoint.{Present Value} If (maxpos <> 0.0) Then If (maxpos > high_limit) Then staticsp = (staticsp + increment) End If If (maxpos < low_limit) Then staticsp = (staticsp - increment) End If Else staticsp = initial_staticsp End If staticsp = Min (staticsp, max_staticsp) staticsp = Max (staticsp, min_staticsp) // ***** control AOP ***** // Control the analog output to the calculated static pressure // setpoint only if it has changed. // No changes are required in this section. If (setpoint.{Present Value} <> staticsp) Then CONTROL(setpoint,{Present Value},staticsp,16,Set) End If End // end of routine The Trane Way Typical Way Repeatable - performance from building to building and job to job
Pump Pressure Optimization • When is it required? • When the system includes control valves designed to modulate open or closed as a function of load • Systems having a total pump system power exceeding 10 hp • Reduce pump flow rates to 50% or less of the design flow rate • Individual chiller water pumps exceeding 5 hp • Limit demand to less than 30% of design wattage at 50% design water flow • When more than 3 water control valves are used • What is needed to implement? • Communicating controls on terminal unit valves • Pressure differential controller • Building Automation System
pressure differential controller /transmitter Pump Pressure Optimization Air Handling Units control valves with communicating controllers communicating BAS
Tracer Controls Progression Tracer Summit Workstation and Enterprise Enterprise Tracer ES™ Tracer Summit Workstation and BCU Building Tracer SC Tracer Unit Controls (LonTalk) Tracer UC (LonTalk and BACnet) Equipment Spaces Wired Sensors Wireless Sensors Legacy - Current - Future
What is Tracer SC? + + =
Value to Customer System applications, pre-engineered Easy web-enabled access Improved user interface Key Features Web-based interface Scalability Smaller incremental steps to build up a system Open standard protocol support (and integration point) BACnetTM and LonTalkTM Delivery platform for engineered system applications Air systems and central plant control Building ControlTracer SC…Linking Trane systems to the Web
Data Logs • Automatic data logs • Graphical view • Data log viewer exportable tabular view (*.CSV) • Selectable triggered or continual logging