An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. COLORADO SPRINGS FIRE DEPARTMENT "Protecting life and property today - creating a safer tomorrow" 2009 International Fire Code – Major Changes and Proposed Amendments Kris Cooper Deputy Fire Marshal September 22, 2010

  2. Introduction to ICC Code Cycle 2009 IFC – Major Changes 2009 IBC – Major Changes of Interest to CSFD CSFD Proposed Amendments THIS PRESENTATION IS NOT ALL EMCOMPASING, IT IS ONLY A SUMMARY OF HIGHLIGHTS OF THE IFC, IBC AND PROPOSED AMENDMENTS. Overview

  3. ICC Code Cycle – 3 Years • Call For Committees • Proposed Changes • Public Proposal Form • Code Development Hearings • Reports of Hearings • Final Action Hearings • Final Action Results

  4. Local Code Cycle • Regulatory Agencies Review Codes • PPRBD and CSFD Meet • Review Committees Established • CSFD Staff • Proposed Amendments • Proposal Forms • Public Process • City Council Adoption

  5. IFC Significant Changes

  6. Section 202, 903.2.2, 907.2.2 • Defines Ambulatory Health Care Facilities • Group B occupancies used for outpatient surgery and similar activities that render patients incapable of self preservation • Requires Sprinkler and Automatic Fire Detection Throughout

  7. Section 311.5 • Dangerous Building Placards • Information placards for fire fighters to identify hazards associated with vacant structures

  8. 311.5 continued Normal Structural Conditions Structural or Interior Hazards Exist Major Structural or Interior Hazards Exist, Exterior Operations Only Additional Markings: R/O Roof Opening, S/M Stairs Missing, F/E Fire Escapes, H/F Holes in Floor

  9. Section 403.3 • Requires crowd managers for assemblies or events where more than 1,000 people congregate. • 1 crowd manager to every 250 occupants • Assist with evacuation procedures • Not intended to require dedicated staff

  10. Section 404 • Code now includes provisions for occupants who need assistance with evacuation. • Previous CSFD amendment for “special needs occupants” • Applies to emergency plans

  11. Section 404.3.3 • Lockdown plans for schools • Required to be included in Fire and Life Safety Plans • Required to be approved by the fire code official • CSFD is not going to require approval of the fire and life safety plans (amendment).

  12. Section 508 • Fire Command Center • Room size increased from 96 square feet to 200 square feet with a minimum dimension of 10’ • Layout must be approved by CSFD • See 508.1.5 for required features

  13. Section 510 & Appendix J • Emergency responder radio coverage • ALL buildings shall have approved radio coverage for emergency responders. • May require bi-directional amplifiers • This item is still being discussed.

  14. Section 603.4.2 • Portable Outdoor Gas-Fire Heating Appliances • 5’ clearance to buildings and other combustibles • Also see Section 307 for clearances of outdoor burning (50’), recreational fires (25’) and portable outdoor fireplaces (15’).

  15. Outdoor Heating Appliances 5’ or manufacturer’s specifications 15’ or manufacturer’s specifications

  16. Section 607.3, 903.3.1.1.1 • Fire Service access elevators • Buildings greater than 120’ • Adjacent to exit enclosure (stairway) • Driven by 9/11

  17. Section 608 • Stationary battery systems • Expended battery types • Lithium – Ion • Lithium Metal Polymer • Nickel cadmium • Nonrecombinant • Recombinant

  18. Section 609.3.3.1 • Frequency for Inspection of Kitchen Hoods – Table 609.3.3.1 • High Volume Cooking – 3 months • 24 hour cooking operations • Low Volume Cooking – 12 months • Churches, seasonal businesses • Solid Fueled Cooking – 1 month • BBQ pits, smokers • All Other Cooking Operations – 6 months

  19. Section 903.2.3 • E (Educational) Occupancies • Reduces sprinkler threshold from 20,000 square feet to 12,000 square feet

  20. Section 903.2.7 • Requires sprinklers for the display and sale of upholstered furniture in M Occupancies, regardless of size of fire area • No Specified Threshold • Huge Implications for Plan Review • Driven by Charleston Fire

  21. Section 907 • Complete re-write of the section • No major changes • Side note: 2010 NFPA 72 now the National Fire Alarm and Signaling Code • Recognizes other alarm functions • Fire Alarm not necessarily priority signals • Mass Notification Systems

  22. Section 909 • Smoke Control Systems • CSFD had previously amended this section to be more restrictive. • Accepting code as written with this adoption.

  23. Section 913.2.1 • Protection of Fire Pump Enclosures • Dedicate rooms • High Rise • 2 hour separation • Non-High Rise • 1 hour separation

  24. Section 1005.1 • Minimum Egress Width • No longer have different design width for sprinkled vs. non-sprinkled structures • 0.3 inches per occupant for stairs • 0.2 inches per occupant for all other means of egress • Loss of any one means of egress shall not reduce the available egress width to less than 50% of required capacity.

  25. Section 1007.3, 1007.4, 1007.6.3 & 1007.8 • Areas of Refuge • Not required in buildings protected throughout with sprinklers • Elevators now approved for occupant evacuation as a means of egress • Two-way communication required for areas of refuge and evacuation elevators

  26. Section 1008.1.9.8 • Electromagnetically locked egress doors • Clarifies the use of magnetic locks on egress doors

  27. Section 1011.4 • Exit Signs • Electrically Powered • Self-luminous • Photo-luminescent • Must comply with UL 924 – Emergency Lighting and Power Equipment.

  28. Section 1024 • Luminous Egress Path Markings • High Rise Structures • Required in exit enclosures of new and existing buildings • CSFD not adopting retroactive application • Required on hand rails, stair treads and landings

  29. Luminous Egress Path Markings

  30. Section 2206.8 • Provides requirements for dispensing Alcohol Blended Fuels • Specific listing of equipment • Signage requirements for facility identification • Alcohol Blended Fuels: Including those containing 85% ethanol and 15% unleaded gas (E-85). Flammable liquids consisting of ethanol or other alcohols blended greater than 15% by volume

  31. Chapter 24 • Now treats tents, canopies and membrane structure the same • Reasoning: Canopies can have walls added to become tents • 2,400 square foot permit threshold (amendment)

  32. Chapter 46 • Combines requirements for existing buildings into one chapter • Look at this closely as it contains significant retroactive requirements • CSFD has amended this section with lots of deletions.

  33. International Building Code • The following code sections are from the 2009 IBC • These are fire related items or CSFD has a specific interest in them.

  34. Section 419 • Guidance on live work units • Classified as R-2 • Non-residential use up to 50%

  35. Section 703.6 • Marking and identification of fire walls, fire barriers, fire partitions, smoke barriers and smoke partitions • Allows for easy identification of rated assemblies

  36. Marking and Identification

  37. Section 909.20 • Stairwells can be pressurized or built with a vestibule • Design will impact standpipe valve locations.

  38. Section 1018.4 • Dead End Corridors • Increase from 20’ to 50’ in B, E, F,I-1, M, R-1, R-2, R-4, S and U occupancies • Must have NFPA 13 sprinkler system

  39. Section 3002.4 • Elevator cars must be sixed to accommodate a 24” x 84” stretcher

  40. Local Amendments • Local changes made to the code during the adoption process as a means to clarify, comply with City Code and/or Charter, or modify code requirements. • Based upon local practices, polices, procedures or interpretations. • Less is more approach

  41. Chapter 1 - Administration • Changes made in order to be consistent with The Code of the City of Colorado Springs. • Administrative Powers • Penalties • Fire Board of Appeals

  42. Permits • Permits as listed in the code maintained as written • Modified some hazmat permit threshold amounts • Added permit amounts for electrolytes • Added Work at Risk Permits

  43. 105.7.15 – Fire Lanes • Added a new permit for the construction of Fire Lanes • Applies to alternative methods • Grass Pave • Gravel Pave

  44. Alternative Fire Lanes

  45. Fees • Reinspections Fees • Cleaned up language where fees may apply to routine fire inspections • Subsequent review fees • Added a provision for the collection of fees where plans are revised and or updated and require additional reviews beyond the initial approval

  46. Section 407.2 • Allows MSDS to be in electronic format • CSFD amendment to specify format and storage on thumb drive in Knox Box • Microsoft Word 2000 or newer • PDF

  47. Section 901.5 • Approved Contractors • Going with 3rd party testing • Will include fire alarm, fire alarm monitoring contractors, water based fire suppression, portable fire extinguishers, special hazard systems and fire hydrants • New state law for testing for all fire sprinkler installers • Unknown impact from state law

  48. 904.11.2 • Kitchen Fire Suppression Systems • Added requirement to cut off power to any appliances under the hood or any power source that could be used to supply power to an appliance under the hood.

  49. 904.11.6.4 • Kitchen Hood Ventilation • Added a new code section to require the exhaust to start and/or stay on upon activation of the fire suppression system. • Prevents heat roll out from the hood that might activate sprinklers.

  50. 905.4 • Standpipe Connections in Stairways • Provides guidance where the standpipe valve will be located when the stairway is built with a vestibule per the IBC.