1 / 50

TTC110(C2), AEGIS Controller

TTC110(C2), AEGIS Controller. (In-depth). Ed Hill 7/09. AEGIS Configurable Control. ON/OFF & Variable Frequency controls. Built-in real time views. Less I/O than a MultiFlex but easier to use & configure Newest water-treatment controls; copying volumes, mirroring, contact set control

herringe
Download Presentation

TTC110(C2), AEGIS Controller

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. TTC110(C2), AEGIS Controller (In-depth) Ed Hill 7/09

  2. AEGIS Configurable Control • ON/OFF & Variable Frequency controls. • Built-in real time views. • Less I/O than a MultiFlex but easier to use & configure • Newest water-treatment controls; copying volumes, mirroring, contact set control • Trackster reporting & alarm polling. • Unique pumped volume tools & logging.

  3. The ‘View’

  4. Diagnostic ‘View:’ Tagging I/O

  5. Sensor, Meter, Pump, Valve, Solenoid IDs • Letter Function Typical • A Conductivity Boiler,Tower, CTF • B Temperature Tower, Feedwater.. • G 4-20mA Input Level, LBs/Hr. .. • C-D & E-F Sensor Card pH,ORP,uS, mpy, • G-N Phantom Sensor ppm,Tank level • O to V Meters-Contacts Floats, interlocks.. • W-Z Phantom Meter Vol. Sums, mirrors • Number Function • 1 to 5 ON/OFF 120VAC Relay Controls • 6 to 9 Variable Frequency Pump Controls

  6. Views: More than Towers & Boilers

  7. Views: User test & Sensor Values

  8. Views: Flag Off-View Faults

  9. Meter ‘P’

  10. Outputs ‘1’ to ‘9’

  11. Plug & Play

  12. LCD Auto-Sequence

  13. Log-in

  14. Sensor Diagnostic

  15. Sensor Compensation

  16. Sensors: Setting a test or verify value

  17. Meter Install

  18. Control Equation: ON/OFF

  19. Control Equation: Frequency

  20. Pumps: Variable Frequency Controls

  21. Pump Configuration

  22. Pumps: Selecting & Setting feed rates

  23. Controls: Using Alarms

  24. Diagnostic

  25. Controls: Using the Diagnostic

  26. Control Type

  27. Interlocking

  28. Blocking

  29. Sequencing on Volume

  30. Feed Verify & Inventory

  31. Rate-to-Volume

  32. Manual Inputs

  33. Sensors: Control on a user test level, 1 of 2

  34. Sensors: Control on a user test level, 2 of 2

  35. Pumps: Feeding on Make-up ppm

  36. Calculate ppm

  37. Pumps: Feeding on Tower ppm, 1 of 2

  38. Pumps: Feeding on Tower ppm, 2 of 2

  39. Copying Meter Volume

  40. Copying Pump Volume

  41. Mirroring Outputs

  42. Contact Set Controls

  43. Measuring Corrosion

  44. 4-20mA Outputs

  45. System: Passwords

  46. View-Configuration Management

  47. Modifying a View

  48. Sidebars: Manuals Sidebar: • Inverting Sense: • Contact sets interlock and control when they are ON. • For non-inverted contact sets, ON is when the contact set is closed. • If you wish to Interlock or control when the contact set is open, set Invert sense to YES. • If your contact sets are open when they are measuring the state you wish to alarm, control using or log, set Invert sense to YES.

  49. Sidebars: Manuals, continued RUN/STOP an ‘Invert sense’ Example: • Contact set ‘U’ is used for a RUN/STOP switch. • The switch contacts are OPEN when the switch is set to RUN. • Invert sense is set for ‘U’ so that RUN displays on the controller as ON and so that ‘U’ can be used as a flowswitch for pumps and solenoids. • 1 Contact Set, 2 Jobs Example: • I want to control a solenoid when the contact set is open & control a pump when the contact set is closed. • Wire the contact set to input ‘U’ and jumper the U+ terminal to the V+ terminal. • Use input ‘U’ for the pump. Invert the ‘V’ input & use it for the solenoid.

  50. Skipped: • Boiler blowdown controls & Fail-to-Sample. • Biocide Events. Prebleed & Lockout. Event Cycle. • Variable Cycles blowdown controls. • Contact set ON time & OFF time alarms. • Volume – Water Meter alarms. • Keypress-Alarm Log • Ethernet Configuration. • Modbus & using the Aegis_Modbus client • Enabling I/O. Set Units. Time & Date.

More Related