250 likes | 363 Views
Phare twinning project BG/2004/IB/EY/01. ENERGY AUDIT on New University of Plovdiv Building - Block A Case studies work by STE Expert team in collaboration with Bulgarian EEA. Institutional Building at the Energy Efficiency Agency. Phare twinning project BG/2004/IB/EY/01. A.
E N D
Phare twinning project BG/2004/IB/EY/01 ENERGY AUDIT on New University of Plovdiv Building - Block A Case studies work by STE Expert team in collaboration with Bulgarian EEA Institutional Building at the Energy Efficiency Agency
Phare twinning project BG/2004/IB/EY/01 A Blocco A entrata • Block A ( wing on left side ) : • Individual heating sub-station ( database ) • 2. Utilization ( representative ) Institutional Building at the Energy Efficiency Agency
Phare twinning project BG/2004/IB/EY/01 Institutional Building at the Energy Efficiency Agency
Phare twinning project BG/2004/IB/EY/01 2,42 1,60 Parete verticale 1. Intonaco 2. Pannello cemento 3. Pannello pietra Vetrate 1. vetro 2. camera 3. vetro Institutional Building at the Energy Efficiency Agency
Phare twinning project BG/2004/IB/EY/01 • Cornice verticale • ponte termico: • teoria delle alette • Keq. = 1,91 W/ mq*K Institutional Building at the Energy Efficiency Agency
Phare twinning project BG/2004/IB/EY/01 Solaio interrato • Solaio cemento • Camera d’aria • Basamento Solaio a cielo • Solaio cemento • Camera d’aria • Isolante in fibra • Solaio cemento Institutional Building at the Energy Efficiency Agency
Phare twinning project BG/2004/IB/EY/01 A2 A3 LT A4 A1 θe R2, A2 Rse2 Rse3 Rsi2 θsi2 δвс θu R3, A3 Rse1 θse1 Rsi3 Rsi1 R1, A1 θi Rse3 R3 Rsi3 R2 R4 Rsi4 Rsi2 R1 Applicazione del modello resistivo: 1. Analoghi risultati della EEA in Mladost 2. Risultati in linea con riferimenti generali Institutional Building at the Energy Efficiency Agency
Phare twinning project BG/2004/IB/EY/01 • Centrale termica: • Bassa temperatura entrata • ( 60 °C contro i 80 °C) • Cattive condizioni dello scambiatore Institutional Building at the Energy Efficiency Agency
Phare twinning project BG/2004/IB/EY/01 Radiatori: 1. Con copertura in legno si abbassa l’efficienza di emissione Institutional Building at the Energy Efficiency Agency
Phare twinning project BG/2004/IB/EY/01 • Sistema di condizionamento: • Tipologie differenti di potenza e vetustà • Presenti solo in alcuni ambienti • ( studi dei professori ) Institutional Building at the Energy Efficiency Agency
Phare twinning project BG/2004/IB/EY/01 • Sistema di illuminazione • Lampade a medio consumo • Utilizzo consistente degli apparati dato l’ombreggiamento degli edifici a corte Institutional Building at the Energy Efficiency Agency
Phare twinning project BG/2004/IB/EY/01 distribuzione dei consumi per tipologia Institutional Building at the Energy Efficiency Agency
Phare twinning project BG/2004/IB/EY/01 Consumi reali nel periodo 2003-2006 Institutional Building at the Energy Efficiency Agency
Phare twinning project BG/2004/IB/EY/01 Valori medi 2003-2006 gradigiorno 2500;energia elettrica 333 MWh; termica 376 MWh Institutional Building at the Energy Efficiency Agency
Phare twinning project BG/2004/IB/EY/01 Provincia autonoma di Bolzano • Software casaclima • Semplicità di confronto con altri software • Open source quindi confrontabile assieme a terzi ( EEA ) • Aggiornato su fabbisogni di raffrescamento ed energia primaria ( forma semplificata ) Institutional Building at the Energy Efficiency Agency
Phare twinning project BG/2004/IB/EY/01 Provincia autonoma di Bolzano • Software casaclima • Inserimento dati dimensionali 2. dati climatici a database Institutional Building at the Energy Efficiency Agency
Phare twinning project BG/2004/IB/EY/01 • Inserimento di • Tipologie costruttive 2. superfici di scambio termico Institutional Building at the Energy Efficiency Agency
Phare twinning project BG/2004/IB/EY/01 • Inserimento di • Dettagli caratteristiche tecniche ( spessori- trasmittanze termiche ) Institutional Building at the Energy Efficiency Agency
Phare twinning project BG/2004/IB/EY/01 Provincia autonoma di Bolzano • Output • Fabbisogni specifici • Potenze specifiche • Classificazione su protocollo casaclima • ( Bolzano e località riferita )
Phare twinning project BG/2004/IB/EY/01 Provincia autonoma di Bolzano • Input • Caratteristiche impianti elettrici • raffrescamento • Correzione • Su dati reali i calcoli sono stati integrati Institutional Building at the Energy Efficiency Agency
Phare twinning project BG/2004/IB/EY/01 Provincia autonoma di Bolzano • Output • Fabbisogni specifici • Potenze specifiche • Classificazione su protocollo casaclima • ( Bolzano e località riferita ) Institutional Building at the Energy Efficiency Agency
Phare twinning project BG/2004/IB/EY/01 Misure correttive di efficienza energetica proposte 1 2 Institutional Building at the Energy Efficiency Agency
Phare twinning project BG/2004/IB/EY/01 Misure correttive di efficienza energetica proposte 3 4 5 6 7 Institutional Building at the Energy Efficiency Agency
Phare twinning project BG/2004/IB/EY/01 Conclusioni e suggerimenti • Sul profilo tecnico la conoscenza e il potenziale utilizzo di più software aumentano la qualità del risultato finale riducendo la probabilità di errore umano che nel caso di raccolta ed elaborazione dati è significativo • Gli interventi di efficienza energetica, contestualizzati nell’ambito territoriale ( costi energetici della Bulgaria ) si evidenziano comunque come interessanti sul profilo economico finanziario oltre che ambientale ( isolamento a cappotto, valvole termostatiche,..) • La competenza in materia energetica dovrebbe essere vincolante in fase progettuale poiché ai casi come questo, concorrente alle aspettative architettoniche ( in cui la EEA è in grado di svolgere un ruolo di riferimento istituzionale ) Institutional Building at the Energy Efficiency Agency
Phare twinning project BG/2004/IB/EY/01 Si ringraziano tutti i membri della EEA per l’ospitalità e la disponibilità ricevuta Institutional Building at the Energy Efficiency Agency