1 / 28

AquaSensor Systems Installation Guide

This guide provides step-by-step directions for installing AquaSensor Systems, including setting the station numbers and troubleshooting tips. It also includes layouts for MODBUS and PROFIBUS installations.

holland
Download Presentation

AquaSensor Systems Installation Guide

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Installation of AquaSensor Systems Andreas Pelz, March 2011

  2. Technical Advices • Directions for the installation of several DataStick’s to one AV38: • All DataSticks have a default setting for the station number of 1! • Please connect at the early beginning one DataStick to the AV38 for setting the Station Number (DS) to a different one than ( 1) • Please use for this the menu function “Find DataStick” under the main menu “DataStick Comms” • Please follow the the steps mentioned on the next page

  3. Technical Advices • Directions for the installation of several DataStick’s to one AV38: • Go to „DataStick Comms“  press „Enter“ • Go to „Find DataSticks“  press „Enter“ • When AV38 found a DataStick  press „Enter“ – you can see the actual station number “( 1)” • Change the Station number with the up and down arrows to a number different to one and different to the settings for other DataSticks • Please shut off and on the AV38 after each setting of the station number • Please do so with all DataStick you want to connect to one AV38

  4. Technical Advices • AV38 shows „DataStick Absent“ • check all connections/ wires etc. • disconnect all sensors except one • if AV38 detects this sensor please check station number and change it to a different one (see before) • follow the advices from the first page and make the settings for the station number • please shut off and on the AV38 after each setting!

  5. Technical Advices • if AV38 does not detect the sensor take him out of the sample (basin/ pipe etc.) • check the display; if AV38 detects the sensor you maybe have a grounding issue • switch off the power; disconnect the grounding wire from the termination block and connect a new wire to this with an open end; connect this open end to a pipe/ basin etc. which has direct contact to the sample • put the sensor back into the sample – if AV38 shows a value - issue solved; • you can now connect the other sensors (if necessary) and make the final installation

  6. Topography of a MODBUS DataStickInstallation

  7. Layout of a MODBUS Installation with AV38 Installation with max two DataSticks: • To Host via • RS232 ASCII • MODBUS RS232 • MODBUS RTU(RS485) • DeviceNet • CanOpen • Ethernet IP AV38 DataSticks with MODBUS Interface

  8. Layout of a MODBUS Installation with AV38 Offer to the customer:

  9. Layout of a MODBUS Installation with AV38 Installation with max two DataSticks (at one or more positions) on different places: Multi-Port termination resistors AV38 2 Port Device Tap, DIN Rail Host DataSticks with MODBUS Interface

  10. Layout of a MODBUS Installation with AV38 Installation with 4 DataSticks in the same place: Multi- Port Termination Resistors Host AV38 4 Port Device Tap, NEMA4X

  11. Layout of a MODBUS Installation with AV38 Offer to the customer:

  12. Layout of a MODBUS Installation with AV38 • Example: • Waste Water Plant with 1x influent (pH/ CD), 3x aeration basins (6x RDO) 1x Nitrification basin (1x RDO/ ORP) • 1x effluent (pH/ CD/ RDO) • Host connection via Ethernet IP • What should we offer?

  13. Layout of a MODBUS Installation with AV38 Example: Primary Treatment Influent Grit Channel Effluent Aeration basin Clarifier Nitrification Basin

  14. Layout of a MODBUS Installation with AV38 Example:

  15. Topography of a PROFIBUS DataStickInstallation

  16. Layout of a PROFIBUS DP Network Up to 30 MODBUS RTU DataSticks can be connected to one Profibus adapter! AS-D9S Profibus Tee Connector PLC PSECXX Profibus to DataStick Adapter Multi- Port Termination Resistors 4 Port Device Tap, NEMA4X Female/ Male Termination Network DataSticks with MODBUS RTU Interface

  17. Layout of a PROFIBUS DP Network Offer to the customer:

  18. Layout of a PROFIBUS DP Network Offer to the customer:

  19. Layout of a PROFIBUS Installation • Example: • Waste Water Plant with 1x influent (pH/ CD), 3x aeration basins (6x RDO) 1x Nitrification basin (1x RDO/ ORP) • 1x effluent (pH/ CD/ RDO) • Host connection via PROFIBUS DP • What should we offer?

  20. Layout of a PROFIBUS Installation Example: Primary Treatment Influent Grit Channel Effluent Aeration basin Clarifier Nitrification Basin

  21. Layout of a PROFIBUS Installation Example:

  22. Layout of a PROFIBUS Installation Example:

  23. Cable length for AQS Installations

  24. Cable length General Guide for Comms Adapter Cable Length MODBUS RTU via RS485

  25. Cable Length Examples Example: MODBUS RTU RS485 Trunk Length Max. 1000 m Drop Length Max. 20 m – Cumulative 40 m

  26. Cable Length Examples Example: MODBUS RTU RS485 Trunk Length Max. 1000 m Junction box with terminal block and termination resistor Drop Length Max. 20 m – Cumulative 40 m

  27. Cable Length Examples Example: EtherNet/ IP PC PC PoE Switch Cable length max. 100 m

  28. Cable Length Examples Example: EtherNet/ IP AV38 with Ethernet- connection PC/ PLC PoE Switch PC Cable length max. 100 m