Design of Power Capacitor For Power Factor Improvement In A Power Distribution System

Design of Power Capacitor For Power Factor Improvement In A Power Distribution System. High Voltage Laboratory. Power Capacitor. Team and Responsibilities. Team Leader Parson L.B – Coil and discharge resistor Members Page J.C – Bushing and withstand/impulse test

hoshi
Download Presentation

Design of Power Capacitor For Power Factor Improvement In A Power Distribution System

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Design of Power Capacitor For Power Factor Improvement In A Power Distribution System High Voltage Laboratory Power Capacitor

  2. Team and Responsibilities • Team Leader • Parson L.B – Coil and discharge resistor • Members • Page J.C – Bushing and withstand/impulse test • Watson K.M – Coil and discharge resistor • Wong C.S – Bushing and withstand /impulse test • Advisor • Dr. Stanislaw Grzybowski High Voltage Laboratory Power Capacitor

  3. Abstract Design power capacitors to maximize a distribution system’s overall performance High Voltage Laboratory Power Capacitor

  4. Problem 1. Voltage drop 2. Energy losses 3. Decreased system capacity Low power factor High Voltage Laboratory Power Capacitor

  5. Why correct power factor ? Efficiency of Power Distribution System $$$ Deregulation of Power Distribution System Energy Losses Power Quality High Voltage Laboratory Power Capacitor

  6. Design Requirements 1. The voltage rating across the capacitor will be 8.66kV 2. Provide a total reactive power of 2 MVAr 3. Reduce voltage drop by 5% 4. Reduce energy loss by 30% 5. Achieve an optimum power factor of at least 90% 6. Reduce current in power lines by 15% 7. Increase system capacity by 20% 8. Discharge to under 50V in less than 5 minutes 9. Low dielectric losses (tan ) (< 0.1W per kVAr) High Voltage Laboratory Power Capacitor

  7. Design Implementation High Voltage Laboratory Power Capacitor

  8. Design Implementation High Voltage Laboratory Power Capacitor

  9. Design Implementation High Voltage Laboratory Power Capacitor

  10. Capacitor Construction Individual coil Cutaway view of capacitor High Voltage Laboratory Power Capacitor

  11. Capacitor Components Aluminum Foil 1. Lightweight 2. Good conductor 3. Less expensive than other available conductors Polypropylene dielectric 1. Yields high dielectric constant 2. High voltage stress rating 3. Low dielectric losses Use of oil to impregnate dielectric 1. Better cooling properties 2. Increases maximum electrical stress High Voltage Laboratory Power Capacitor

  12. Design Process 1. Total reactive power of 2MVAR in 15kV substation 2. Each capacitor will supply 50kVAR 3. The capacitance for each capacitor is 1.901F 4. Each capacitor will have 6 coils in series and 2 in parallel High Voltage Laboratory Power Capacitor

  13. Design Process 5. The capacitance for each coil is 5.73F 6. The thickness of dielectric 0.02mm 7. The area of foil and dielectric is 2.942m2 8. The length of foil and dielectric is 23.165m with 5in. (12.7cm) polypropylene 9. The discharge resistor will be 15M High Voltage Laboratory Power Capacitor

  14. Simulation Results Reduce voltage drop by 5% Reduce energy loss by 30% Achieve an optimum power factor of at least 90% Reduce current in power lines by 15% Increase system capacity by 20% Discharge Capacitor in less than 5 minutes Load voltage increased (13.8kV to 14.44kV): 4.6% improvement Energy loss decreased (76.7kW to 44.7kW): 41.7% reduction Power factor increased (0.7 to 0.956) Current decreased (141.77A to 108.49A): 23.5% reduction System capacity increased: 40.4% improvement Discharged from 15kV to <50V: 3 minutes High Voltage Laboratory Power Capacitor

  15. Tests • 1. Test capacitance • 2. Measure dielectric losses (tan ) • Transformer Arm Ratio Bridge • 3. Withstand Voltage Test • Energize with DC between terminals • Vsource = 4 x Vrated for 10 seconds (IEEE Standard 18-1992) • Energize with AC between terminals and ground • Vsource = 40kV for 10 seconds (IEEE Standard 18-1992) • 4. Lightning Impulse Test (1.2/50s) (IEEE Standard 18-1992) • 5. Discharge Test High Voltage Laboratory Power Capacitor

  16. Tests Lightning Impulse Test (wet condition) High Voltage Laboratory Power Capacitor

  17. Tests Results • 1. Test capacitance (1.989F) • 2. Measure dielectric losses (tan  < 0.07w per kVAr or 3.5w) • Transformer Arm Ratio Bridge • 3. Withstand Voltage Test • Energize with DC between terminals • Successfully maintain voltage for 10 seconds • Energize with AC between terminals and ground • Successfully maintain voltage for 10 seconds • 4. Lightning Impulse Test • No dielectric breakdown observed • 5. Discharge Test (Vcap < 50V in <5min.) High Voltage Laboratory Power Capacitor

  18. Future Works Research dielectrics to provide better insulation properties New lighter materials to reduce overall weight Design a control system to automatically regulate the power factor High Voltage Laboratory Power Capacitor

  19. DEMO DEMO High Voltage Laboratory Power Capacitor

  20. References High Voltage Laboratory Power Capacitor