1 / 25

GE Power Management

g. GE Power Management. MMII Intelligent MCC Controller. g. GE Power Management. MMII Intelligent MCC Controller. A concept that will offer reduced overall installed cost and production efficiency through information availability to operators and maintenance. g. GE Power Management.

ike
Download Presentation

GE Power Management

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. g GE Power Management MMII Intelligent MCC Controller

  2. g GE Power Management MMII Intelligent MCC Controller A concept that will offer reduced overall installed cost and production efficiency through information availability to operators and maintenance.

  3. g GE Power Management MMII Intelligent MCC Controller Presentation Overview • Applications • User Interface • Protection and • Control • Communications • Inputs • Typical Wiring • Metering and • Monitoring • Ordering

  4. g GE Power Management MMII Intelligent MCC Controller Applications In one package the Motor Manager II (MMII) combines control functions and comprehensive motor protection, providing sophisticated control and protective relaying. • Low voltage motor control centers • Integrated process and electrical control MAIN

  5. g 52 480 VOLTS BUS FUSE CONTACTOR A (FORWARD/WYE) CONTACTOR CONTACTOR B (REVERSE/DELTA) AUX 1 RELAY 59 27 PHASE PT AUX 2 RELAY 51 49 37 46 PHASE CT 51G CONTROL INPUTS GROUND CT PROCESS PLC OR TRANSDUCER MOTOR MANAGER II WINDING 4 - 20mA INPUT 49 THERMISTOR THERMISTOR LOAD MOTOR RS485 REMOTE COMMUNICATION 1200-19K2 BAUD GE Power Management Application SINGLE LINE DIAGRAM Legend MAIN

  6. g GE Power Management Application DEVICE PROTECTION 49/51 overload 46 phase unbalance (single phase) welded/open contactor 50G/51G ground fault 48 locked rotor/stalled rotor 49 hot winding (thermistor) 37 undercurrent/under power 27 undervoltage 59 overvoltage STANDARD PROTECTION OPTION 2 ENHANCEMENT MAIN

  7. g GE Power Management MMII Intelligent MCC Controller Protection • Overload • Phase unbalance • Contactor failure • Locked/stalled rotor • Ground fault • Hot winding thermistor • Undercurrent/underpower MAIN

  8. g GE Power Management Protection 100000 10000 4 NEMA compatible time/current overload curves 1000 TIME IN SECONDS 100 CURVE # CLASS 30 CLASS 20 10 CLASS 15 CLASS 10 MAIN 1 0.1 0.5 1 2 3 4 5 6 7 8 9 10 20 50 100 MULTIPLE OF PICKUP CURRENT (PER UNIT)

  9. g GE Power Management MMII Intelligent MCC Controller Control • Undervoltage auto restart • Outputs (assignable to any one of 31 functions) • 2 contactor (A and B) • 2 programmable • Inputs: 6 fixed, 10 programmable • 1 analog input MAIN

  10. g • Switched Inputs • up to 6 fixed control inputs used for start A and B, • stop, local isolator, and contactor A and B status. • Switched Inputs • scaleable to user defined values • high and low alarm and trip setpoints recorded with • time delays GE Power Management MMII Intelligent MCC Controller Inputs MAIN

  11. g GE Power Management MMII Intelligent MCC Controller Metering • The MMII meters and displays: • RMS current of each phase • ground fault leakage current • motor load as a % of full load current • thermal capacity used (%) according to I2t • history and chosen overload curve; hot/cold • ratio is used to model heating when running • below full motor current • % unbalance • power (kW) • energy (kWh) • voltage • analog input MAIN

  12. g GE Power Management MMII Intelligent MCC Controller Monitoring • Trip Record • when a trip command is issued, a trip record is generated, • including the cause of trip and pre-trip actual values • Statistics and Maintenance • user enabled to set the interval at which a number of • routine maintenance tasks should be performed. When • these times are exceeded an alarm is generated, including: • motor greasing interval • contactor inspection • maximum motor stopped time MAIN

  13. g GE Power Management MMII Intelligent MCC Controller User Interface • RS485 ModBus®, 1200 - 19,200 bps • Display model for local interface • Up to 11 status LEDs • MMII PC Software

  14. g GE Power Management MMII Intelligent MCC Controller User Interface The Chassis Mount Model • mounted inside the motor • control center (MCC) • comes with all standard • features • setpoints are loaded through • the RS485 communications • port from a personal computer • running the MMII program. MAIN

  15. g GE Power Management User Interface MMIIPC Software • Windows based software • Windows 95 or Windows NT • Features: • program or modify setpoints • load or save setpoints from or to a disk • read actual values from the MMII • monitor status • read pre-trip data and trip record • display dynamic trending of actual values • get help on any topic • print the instruction manual from disk MAIN

  16. g GE Power Management Front View DISPLAY: 2 line, 40 character illuminated display communicates all messages in simple English for easy interpretation by users unfamiliar with unit RELAY INDICATORS: RELAY A: Contactor A energized RELAY B: Contactor B energized AUX 1: User programmable relay 1 energized AUX 2: User programmable relay 2 energized PROGRAM KEYS: ACTUAL VALUES: Press to enter actual values mode to display actual motor values such as current, ground leakage, thermal capacity. SETPOINTS: Press to enter setpoint mode to alter or examine setpoints. STORE: Save a newly entered setpoint. RESET: Reset the MMII after a trip. MESSAGE: Move to the desired setpoint or actual value message. VALUE: Increment or decrement currently displayed setpoint value. MAIN

  17. g GE Power Management Front View CONTROL KEYS: AUTO: Selects operation of start via communication port. MANUAL: Selects manual operation of motor using start key. START A: Energize contactor A. START B: Energize contactor B. STOP: De-energize contactors. STATUS INDICATORS: RUNNING: Contactor is energized and motor is running. STOPPED: Contactor is not energized and motor is not running. TRIPPED: Contactor is not energized. Motor is not running. The MMII has tripped the motor due to a fault. Normally a cause of trip message will be displayed. ALARM: One or more alarm conditions are present. Normally a cause of alarm message will be displayed. FAULT: An internal fault or abnormal condition has been detected. The MMII may need to be replaced or serviced. MAIN

  18. g GE Power Management Rear View COMMUNICATIONS RS485 2 wire serial communication port operates at 1200 - 19,200 bps for remote commands, monitoring and setpoint store. ModBus® RTU protocol. SWITCH INPUTS Opto-isolated 120 VAC live inputs for various interlock functions. The interlock inputs are fully programmable and can be assigned to such functions as setpoint access, plant interlock, test, and various others. CONTROL POWER 120/240 VAC supply voltage selector switch and fuse access door • 4 RELAYS • Contactor A: direct on • line / forward / wye • Contactor B: reverse / delta • User programmable relay • (AUX 1) • User Programmable relay • (AUX 2) SUPPLY VOLTAGE required to power the MMII MAIN

  19. g GE Power Management Rear View Ground safety and surge ANALOG INPUT 4 - 20mA input for process control monitoring / alarming / tripping. VOLTAGE INPUT Phase A voltage input for voltage and power monitoring. THERMISTOR NTC or PTC thermistor input for hot winding detection. GROUND CT INPUT 5 amp or 50:0.025 ground fault input for residually connected phase CTs or separate core balance (zero sequence) CT. PHASE CT INPUTS 3 isolated phase CT inputs that accept 1 amp or 5 amp CT. MAIN

  20. g GE Power Management MMII Intelligent MCC Controller Communication • ModBus® RTU RS485 connection • Up to 32 MMIIs can be daisy chained • together on a single communication • channel. • supports operation at 1200 to 19,200 bps MAIN

  21. g GE Power Management MMII Intelligent MCC Controller Typical Wiring Residual Ground Connection Two Phase CT Connection Direct Connection CT PHASE A CT PHASE A CT PHASE C CT PHASE C CT PHASE B PART 2 OF DIAGRAM MAIN

  22. Core Balance (Zero Sequence) Isolater Switch CT Phase A CT Ground Contactor CT Phase B CT Phase C L1 L1 L2 L2 MOTOR L3 L3 4-20mA Analog Input RS485 Programmable Switch Inputs Stator Thermistor Stop MOTOR MANAGER II = Option 1: Process control Start Fixed Switch Inputs = Option 2: Enhanced protection A MCC Ground Bus Contactor A L AC Control Voltage 120 / 240 VAC MAIN N

  23. MMII Basic Unit PD Panel Mount With Display * C Chassis Mount (Black Box) 1Option 1 Process control, process input, undervoltage auto restart, diagnostics 2Option 2 Enhanced protection, power (kW), thermistor, 2nd contactor control 120 Control voltage 120 VAC 240 Control voltage 240 VAC g GE Power Management MMII Intelligent MCC Controller Ordering MAIN

  24. g GE Power Management Ordering Accessories: MMIIPC software package supplied free RS232 TO RS485 CONVERTER box designed for harsh industrial environments 5A PHASE CT: 50, 75, 100, 150, 200, 250, 300, 350, 400, 500, 600, 750, 1000 1A PHASE CT: 50, 75, 100, 150, 200, 250, 300, 350, 400, 500, 600, 750, 1000 50:0.025 GROUND CT for sensitive ground detection on high resistance grounded systems COLLAR for reduced depth mounting Modifications: MOD601: 240 VAC switch inputs - allows the use of external 240 VAC supply to power switch inputs MOD602: 24 - 48 VDC switch inputs - allows the use of external 24 - 48 VDC supply to power switch inputs MOD603: ESD relay - converts AUX 2 relay into an emergency shutdown relay MOD605: Removable rear terminals - allows terminals 13 - 58 to be unplugged from the MMII MOD610: Conformal coating MOD613: 240 VAC VT input MOD616: MMII with remote display MAIN

  25. g GE Power Management MMII Intelligent MCC Controller

More Related