Humidifiers for Every Application. Pressure Steam Humidifiers Designed to deliver Reliable humidity from facility steam boilers. What is LiveSteam?. LiveSteam humidifiers utilizes existing facility boiler steam for humidification in one of two ways:
E N D
Pressure Steam Humidifiers Designed to deliver Reliable humidity from facility steam boilers
What is LiveSteam? • LiveSteam humidifiers utilizes existing facility boiler steam for humidification in one of two ways: • Directly introduce boiler steam into the duct work for humidification • Utilize boiler steam as the energy source to generate clean steam for humidification
Why Use LiveSteam? • A source of central steam is • available • Inexpensive • Energy efficient
LiveSteam Product Family SAM-e LS Tubes Steam Exchange
LS Components Manual Shut-Off Valve Strainer Actuator Distributor Tube Steam Valve Steam Main Steam Separator Interconnecting Piping F&T Steam Trap Manual Shut-Off Valve Pressurized Condensate Return *All Red Components By Nortec
LS Components Strainer
LS Components Strainer Clean yearly! Screen Cap
LS Components Distributor Tube
LS Components Distributor Tube Tube Adaptor Duct Plate Support Support Bracket Length, L Stainless Steel Sheath Fiberglass Insulation Distributor Cross Section Duct Plate Support 2 Piece Adjustable Insulated Distributor (Optional) Cross Section
LS Components Distributor Tube Adaptor Nut O-ring Threaded on to Valve or Header Nipple
LS Components Distributor Tube - Installation Steam Airflow Steam Airflow
LS Components Distributor Tube - Installation
LS Components Interconnecting Piping
LS Components Steam Separator
LS Components Steam Separator Spec Label Outlet Inlet ¾” NPT
LS Components Steam Valve
LS Components Steam Valve • Maximum pressure 50 psig • ½” to 2” (CV 0.10 to 40.0) • Bronze body with stainless steel components OR • Stainless steel body with stainless steel components
LS Components Actuator
LS Components Actuator Installation Most problems caused by incorrect installation!
LS Components Actuator Installation
LS Components Steam Trap
LS Components Steam Trap – Maintenance and Repair
Principle of Operation Single Tube Distributor Tube Section View
Principle of Operation Multiple Tube Distributor NOTE: DISTRUBUTORS MUST BE SUPPORTED BY STEAM PIPING AND DUCT SUPPORT BRACKET.
Multiple Tube Distributor Header Sizing Header
Electric Controls Temperature Switch
Pneumatic Controls Temperature Switch
Distributor Discharging Water? • Ensure “T” is from top of main • Verify steam trap operation • Ensure steam trap orifice is not clogged • Ensure proper amount of steam traps • Ensure pipe and traps are sized correctly
Water Leaks from Tube Adapters? • O-ring damaged or missing • Connection not tight • Distributor not supported properly at other end resulting in stress on the tube adapter and o-ring
Over Humidifying? • Incorrect valve size • Steam pressure too high • Exceeded max close off pressure of the actuator • Controls not calibrated or malfunctioning • Steam valve stuck open • Damaged seat in the valve • Spring tension on actuator too light or loose
Under Humidifying? • Incorrect valve size • Insufficient amount of steam (undersized boiler) • Controls out of calibration • Header size too small • Steam pressure too low or fluctuating
Humidity Swings? • Doors/Windows etc. opening and closing • Location of controls (ie. High limit too close to distribution) • Fluctuating steam supply pressure to the unit
Spitting During Start-Up? • Temperature switch not installed or not functioning • Incorrect valve size • Boiler carrying too much condensate
Condensate in Duct? • Duct too cold • Distributors too close to duct wall • Higher air velocity required (300 ft/min minimum) • Absorption distance calculations are incorrect • Incorrect valve size • Malfunctioning or lack of safety high limit humidistat
SAM-e Components Mounting Frame Steam Tubes Header Inlet Adapter Condensate Drain
SAM-e Header • Fits ducts 18” – 144” wide • 3”, 6”, 9” or 12” spacing • Atmospheric or pressure steam 9.0” 8.7” Spacing Width
SAM-e Header 801 – 1200 lbs/hr • Atmospheric steam • 3”, 6”, 9” or 12” spacing • Fits ducts 42” – 144” 9.0” 8.7” Spacing Width
SAM-e Steam Tubes • Lengths from 6” to 132” • 4 Types: • Type A: 15 lbs/hr (20 Tubelets) • Type B: 36 lbs/hr (48 Tubelets) • Type B+: 55 lbs/hr (74 Tubelets) • Type C: 75 lbs/hr (102 Tubelets) Length
How does the SAM-e Work? Steam Tube Cross Section Airflow Tube wall Hot Steam Nozzles Condensate
Atmospheric Installation Atmospheric Steam Trap and Funnel
Pressurized Installation With External Steam Separator Strainer Valve and Actuator Steam Main Separator F&T Steam Trap F&T Steam Trap Pressurized Condensate Return Main Return to Non-Pressurized Condensate Return Main or Drain
Pressurized Installation Without External Steam Separator
Pressurized Installation SAM-e Internal Baffle Internal Baffle Plate