IEEE RURAL ELECTRIC POWER CONFERENCE FT. COLLINS, COLORADO APRIL 28, 2009

IEEE RURAL ELECTRIC POWER CONFERENCE FT. COLLINS, COLORADO APRIL 28, 2009. Application of Series Air-Core Inductors to Distribution Capacitor Banks Improves Reliability

jalen
Download Presentation

IEEE RURAL ELECTRIC POWER CONFERENCE FT. COLLINS, COLORADO APRIL 28, 2009

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. IEEE RURAL ELECTRIC POWER CONFERENCE FT. COLLINS, COLORADOAPRIL 28, 2009 Application of Series Air-Core Inductors to Distribution CapacitorBanks Improves Reliability Alan Hannah –AEP SWEPCO

  2. BACKGROUND • Standard Distribution Banks ,When Switched , Can Cause Ringing On Distribution Network • Back –To-Back Capacitor Switching Can Cause Circuit To Resonate in The 400 Hz Range -Theoretical Over Voltages Up To 2.0 P.U. • Engineer at Sister OPCO- Insert Permanent Small Inductance On Capacitor Bank-To Shift Ring Frequency • Inductors Are Fabricated in Utility Transformer Repair Shop

  3. CIRCUIT THEORY C =kvar x1000 2∏ f(kv)2 where C = 20.4 microfarads FOR 1200 KVAR -7.2 KV UNIT

  4. THE AIR CORE INDUCTOR

  5. THE AIR CORE INDUCTOR • CALCULATED VALUE = 72.78 MICROHENRIES VS. • MEASURED VALUE = 69.7 MICROHENRIES

  6. f o = ? KHz for 1 Capacitor without Choke Coil * f o = 4.2 KHz for 1 Capacitor with Choke Coil fo= 3.0 KHz for 2 CAPACITORS with Choke Coil * Neglecting Source Inductance

  7. WHY ADD INDUCTORS TO SHUNT CAPACITORS? • ENHANCED POWER QUALITY DURING CAPACITOR SWITCHING • ABILITY TO PLACE SWITCHED CAPACITORS CLOSE TO ONE ANOTHER IN TIGHT DISTRIBUTION CORRIDORS • LIMITS CAPACITOR CHARGING CURRENT & IMPROVES SAFETY

  8. SWEPCO CAPACITORS • Approx. 300 Capacitors in 2 Divisions • 90 % Are 7.2/12.47 KV, 1200KVAR Units • Other 10 % Are 13.2 KV & 34.5 KV W/ Some 600KVAR Units • 99% of Capacitors are Gr. Wye • 85 % Of Capacitors Are Switched • 70 % Of Banks Are On Shielded Circuits • All New Banks Fitted With Choke Coils

  9. BACK-TO-BACKSWITCHING EXAMPLE#1 SOUTH FAYETTEVILLE SUBSTATION

  10. EXAMPLE-S.E. FAY CKT 965640 • HEAVY INDUSTRIAL CORRIDOR • MW OF PEAK LOAD • TOTAL OF 4800 KVAR OF SWITCHED CAPACITORS • SUSTATION PEAK SHORT CIRCUIT- AMPS • 1033 AL. SHIELDED WIRE • 2-1200KVAR BANKS ON WEST LATERAL- 1 SPAN APART

  11. BACK-TO-BACKSWITCHING EXAMPLE# 2 FAYETTEVILLE SUB

  12. ENGINEERING CONSIDERATIONS • REACTIVE POWER CONSUMPTION= 81 VAR • REAL POWER CONSUMPTION = 37 WATTS • DIELECTRIC STRESSES = 3.8 VOLTS

  13. ACCOUNTING TREATMENT • CHOKE COILS ARE TREATED AS O&M • REDUCES BLOWN FUSES-O&M • AVOIDS BLOWN CAPACITOR CELLS –CAPITAL REPLACEMENT

  14. OTHER PHYSICAL CONSIDERATIONS • WEIGHT OF CHOKE COIL-9 LBS • ARRESTER LOCATION • RELOCATE TO SWITCH ARM • ICE LOADING

  15. QUESTIONS?