Transformer -2. (d) Tapped -windings. ( a) Iron-cored Transformer. F. B. E. D. A. C. (b) Ferrite –cored Transformer. (e) Auto-Transformer. C. B. A. (c) Multiple-windings. H. G. B. F. E. A. D. C. Types of transformer. Construction of transformer.

Download Presentation

Transformer -2

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Transformer -2

  2. (d) Tapped -windings (a) Iron-cored Transformer F B E D A C (b) Ferrite –cored Transformer (e) Auto-Transformer C B A (c) Multiple-windings H G B F E A D C Types of transformer

  3. Construction of transformer Laminated steel-core transformer

  4. 6000/230 V I1 R1 Xe R2 I2 10  23  0.016  V1 V1’ V2’ V2 30 kVA Example 5 Primary windings of a 30 kVA, 6000 V/230 V transformer has a resistance of 10 , the secondary windings has a resistance of 0.016 . The total reactance of the transformer referred to primary is 23 . Calculate the voltage regulation of the transformer when it supplies a the full-load current at power factor of 0.8 lagging

  5. I1 Re Xe 6000/230 V I2 V1 V1’ V2’ V2 30 kVA Equivalent resistance of primary and secondary referred to primary is Full-load current at primary

  6. Efficiency • Losses in transformer on load categorized into two • I2R losses in primary and secondary windings, namely I12R1+I22R2. • Core losses due to hysteresis and eddy currents Usually variation between no-load and full-load can be negligible thus, the total core loss, PC , is assumed to be constant all the time. Therefore total loss or R1e=equivalent resistance of primary and secondary referred to primary R2e=equivalent resistance of primary and secondary referred to secondary

  7. Note: p.f= power factor The wire losses can be expressed as Divided by I2

  8. It is also possible to express Or

  9. Example 6 The primary and secondary windings of a 500 kVA transformer have a resistances of 0.42  and 0.0011  respectively. The primary and secondary voltages are 6600 V and 400 V respectively and the core loss is 2.9 kW , assuming the power factor of the load to be 0.8. Calculate the efficiency on (a) full-load and (b) half-load. (c) assuming the power factor 0.8, find output which the efficiency of the transformer is maximum. (a) Primary current on full-load Secondary current on full-load Coil Wire loss at primary PW1=I12R1=75.82 x 0.42=2415W Coil Wire loss at secondary PW2=I22R2=12502 x 0.0011=1720W

  10. PW = PW1 + PW2 = 2415 + 1720 = 4.135kW Total loss PL= PW + PC = 4.135 + 2.9 = 7.035kW Output power on full load Pout = 500 x 0.8 = 400 kW Therefore Pin = Pout + PL = 400+7.035 = 407.035 kW

  11. (b) Since the wire loss varies as square of the current , thus Losses on half-load PW/2=4.135/22=4.135/4=1.034kW Total Loss on half-load PL= PC+PW/2=2.9+1.034=3.934kW Output power on half-load Pout/2= 400/2 = 200kW Input power on half-load Pin/2= Pout/2+PL=200+3.934 = 203.934kW

  12. (c) Full-load I2R loss is PW = 4.135kW Let n= fraction of full-load appearance power at which it is maximum efficiency Total I2R loss is = n2 x 4.135 kW=2.9 Therefore n=0.837 Output at maximum efficiency is= 0.837 x 500= 418.5kWA Output power at power factor 0.8= 418.5 x 0.8 = 334.8 kWA Since the core and I2R are equaled, then total loss is PL= 2 x 2.9 = 5.8 kW