Control of maldistribution of flow in parallell heat exchangers Magnus G. Jacobsen, Sigurd Skogestad Nordic Process Controi workshop, Porsgrunn 29.-30. jan 2009
Outline • Motivation • Problem description • Model description • Simulations • Analysis • Conclusions and future work Nordic Process Controi workshop, Porsgrunn 29.-30. jan 2009
Motivation • The problem is observed in the LNG plant at Melkøya and is probably one of the reasons for suboptimal operation • At the same time, it is an interesting control challenge; • Can we control the system so we have equal flows in the two branches, using only one input? • Obviously, we can achieve this for flows outside the instability area, but by design, we are close to or inside this area. Nordic Process Controi workshop, Porsgrunn 29.-30. jan 2009
Problem description • When having a vaporizing fluid distributed between two or more parallels, we can have different flow rates in each parallell • This leads to temperature gradients inside the exchanger. This causes increased wear on heat exchanger material, and disturbance on operation of surrounding units. • We may also get liquid in one of the exit streams, this may damage compressors Nordic Process Controi workshop, Porsgrunn 29.-30. jan 2009
Simple model • Heat is transferred from a source of constant temperature and aritmethic mean ΔT is used • Gas phase is assumed ideal and heat capacities are assumed constant • Hydrostatic contribution to pressure drop is neglected • Flow = √(ρΔP/k) where k is a constant • Data used are for water Nordic Process Controi workshop, Porsgrunn 29.-30. jan 2009
Simulations • With one parallell, to establish how overall pressure drop, temperature and density change with increasing flow. • Model is run to steady state for different values of inflow • Next plots show: • Pressure drop as function of molar inflow • Outlet temperature as function of molar inflow • Outlet density as function of molar inflow Nordic Process Controi workshop, Porsgrunn 29.-30. jan 2009
Dynamic simulation with two parallell tanks • Individual flows may vary, but total is constant • Total flow divided by 2 lies inside instable region • Inlet pressures are equal • Adds inlet pressure as algebraic variable (DAE system) • Plots show: • Inflows • Outlet vapour fractions • Temperatures • Inlet pressure (common for both tanks) Nordic Process Controi workshop, Porsgrunn 29.-30. jan 2009
Linear analysis • Linearization (using Simulink) of the model after 30 seconds shows that the initial operating conditions are unstable • Linearization after 300 seconds shows that the final operating conditions are stable • This indicates that if the hot side temperature is not changing, the system will stabilize at the operating point where maldistribution is present Nordic Process Controi workshop, Porsgrunn 29.-30. jan 2009
Controllability • We have considered the following measured variables: Overall pressure drop (dP), difference in internal pressure (ΔP) , difference in outlet temperature (ΔT ) • Total feed rate nin is the manipulated variable • At the instable operating point, dP is the only measurement out of those considered which changes with total flow (the others are zero) Nordic Process Controi workshop, Porsgrunn 29.-30. jan 2009
At both operating points, the linearized system is state controllable, that is, the controllability matrix has full rank • However, because of the fast transition from the unstable to the stable region, control might be difficult • For example, the transfer function from total flow to overall pressure drop has a duplicate real RHP zero at almost the same location as its RHP pole. • At the instable solution, this is the variable that is simplest to measure. Nordic Process Controi workshop, Porsgrunn 29.-30. jan 2009
Control alternatives • Control inside the instable area is difficult anyway • Multivariable control – will it be fast enough? • Split-range SISO control? • Inside instable area, use feedback to control pressure difference • When ΔT is nonzero, reduce total flowrate temporarily • But can we then go back to nominal operating conditions without going unstable? Nordic Process Controi workshop, Porsgrunn 29.-30. jan 2009
Remember: Nordic Process Controi workshop, Porsgrunn 29.-30. jan 2009
Conclusions and further work • Control inside the unstable area is difficult (but probably possible) • For the LNG plant it may be easier because of slower dynamics • Next step will be trying out different control strategies Nordic Process Controi workshop, Porsgrunn 29.-30. jan 2009