230 likes | 447 Views
PROTECT 3.M 15 – 120kVA. PROTECT 3.M the new generation of uninterruptible power supplies (UPS) with 3-phase Mains input and 3-phase Mains output. PROTECT 3.M General data. PROTECT 3.M will be offered in two cubicle variances. Variance 1:
E N D
PROTECT 3.M the new generation of uninterruptible power supplies (UPS) with 3-phase Mains input and 3-phase Mains output
PROTECT 3.M General data PROTECT 3.M will be offered in two cubicle variances. Variance 1: Cubicle dimensions: (W x H x D) 600mm x 1600mm x 1000mm Maximum 6 modules each 15kVA = 90kVA per cubicle Variance 2: Cubicle dimensions: (W x H x D) 600mm x 2000mm x 1000mm Maximum 8 modules each 15kVA = 120kVA per cubicle • 15kVA per Modul (hot-swappable) • Degree of redundancy selectable via Display • Each Modul is independent , Controllcard/Display are just for Communication and Indication. • Integrated Distribution with up to 36 breakers as an option • LCD Display • Communication via RS232, RS485, SNMP & AS400
PROTECT 3.M General data 1.6 m cubicleMB at the bottom 2.0 m cubicleMB at the top
PROTECT 3.M • High MTBF ability Each UPS module in the Protect 3.M is the full function UPS. There is no additional controlling module to the parallel application and load sharing. Regarding to the serious calculation on the system MTBF, if you have two more UPS modules for parallel redundancy, the system ability is above 99.999% and the MTBF will be close to 15 Million Hours. • MTTR Once the system has one more UPS module for parallel redundancy, the system will still keepworking if one of the UPS modules fails. If the failed modules exceed the parallel redundancy modules, the module replacement procedure only need 5 minutes for system recover.
PROTECT 3.M Battery Battery +/- 240Volt DC (20 bloc for each string)Integrated batteriecharger in each Module (2700W / 4.5A) Battery Management in two stepsStep 1) up to 90% battery capacity constant currentStep 2) above 90% capacity constant voltage
PROTECT 3.M · Applications • Single- and multi-user systems (Workstations, FileServer, Application Server, ... ) • Network protection (client / server architecture) e.g. intranet / internet application • EDP - equipment (CAD-systems, ...) • Communication equipment (IT-sector) • Component protection of telecommunication • Cash systems (trade) • Other user-critical applicationen (process systems (stored-program contoller, ... ))
PROTECT 3.M · conceptual highlights • Modularity with UPS plug-in modulesin VFI (double-conversion) technology • n+x technology free choice of redundancy level • scalable design for flexible power-/autonomy time requirements • central simplified management more efficient service • independent UPS-modules (without any central control logic)
PROTECT 1.M · UPS classes Voltage Phenomenon Time e.g. IEC UPS solution 62040-3 > 10 ms continuous continuous sporadic < 4 ms sporadic periodic continuous 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. Outage - blackouts Sags / brownouts Dynamicovervoltage Undervoltage Overvoltage Lightning Transients (Surge) Frequency variations Voltage distortion (Burst) Voltage harmonics VFD Voltage + Frequency Dependent VI Voltage Independent VFI Voltage + Frequency Independent Classification 3 Offline Classification 2 LineInteractive Classification 1 (true) Online real Double- Conversion Publication by ZVEI: UPS Guide ........... by additional lightning arrestors
Protect 3.M System architecture Integrated Distribution with up to 36 breakers as an option Communication module incl. communication port LCD-Display UPS-modules each 15kVA
Mainsfilter Electronicstatic bypass Load PFC ~ Mains Filter ~ Inverter Rectifier DC/DC Booster ~ DSP / CanBuscontrol logic unit RS232 Battery charger SNMP Battery system PROTECT 3.M · UPS module design Diagram of an UPS PROTECT module : • High power reserves as a result of a max. 24 kVAtotal output • High safety reserves asa result of n+x technology • Independent UPS modules (no central control) slide-in types; suitable for rackmount
PROTECT 3.M · n + x technology · redundancy level n + x technologyadvantage • Higher reliability • Easy to increase overall capacity • Modules hot - swapable (without any interruption)
Protect 3.M Usage >> Delivery Cubicle packing Module packing
Protect 3.M - Mains connection Mains Battery Load
PROTECT 3.M – LCD display Appear „green light“ Appear „yellow light“ Appear „yellow light“ Appear „red light“ and warning alarm
- Expansible • AS/400 card with potential-free contacts • SNMP / SNMP PRO card • (with connector for additional temperature measurements) PROTECT 3.M Communication interface • “Dual monitoring“ interface • from left to the right: • - RS485 • RS485 • RS232 • - RS485
PROTECT 3.M SNMP-Adapter • Features: • Agent for RFC1628 MIB UPS standard MIB • Embedded Web-Server • Monitoring via Web • Configuration via Web • Embedded Event Manager • Start of different Jobs • Net Broadcast • E-Mail • Monitoring of environmental conditions • Temperature, Humidity, GenSet, Fire, Air condition, Smoke shutter... • Support Software products • Network Management Software „NMS“ • NMS special for Power Supply Systems • Shutdown Software “CompuWatch” • Direct multi-server shutdown of different OS with communication modules • SNMP Slot-Adapter for UPS SNMP Adapter Pro: 6000001271 SNMP Adapter: 6000004036
PROTECT 3.M AS/400 slotcard Pin 1: UPS Fault Battery below cutoff voltage Pin 2: Summary Alarm: UPS failure, Utility power failure, Battery low Pin 3 and 4: Short from Pin 3 to 4 generates an UPS shutdown, e.g. by installing an external switch for EPO. Pin 5: Common ground for relays (pins 1, 2, 6, 7, 8 und 9) Pin 6: Bypass active; mains operationPin 7: Battery low Battery voltage is below the predetermined level Pin 8: UPS on; normal operation (relay closed during normal operation) Pin 9: Utility Failure; battery operation Attention ! Contact load rating: AC / DC 24 V / 0,5 A
UPS system: PROTECT 3.M • Graphical front-end of CompuWatch Normal operation