Exercise Ducting Design. Determine type and number of resisters Decide on the air distribution Decide on velocity and noise criteria Find worst case scenario Duct Sizing method selected: equal Friction. Data. 10m. 7m. Airflow = 3214 m³/h = 896 l/s. H = 3,5 m. Trox Air Distribution.
E N D
Exercise Ducting Design • Determine type and number of resisters • Decide on the air distribution • Decide on velocity and noise criteria • Find worst case scenario • Duct Sizing method selected: equal Friction Daikin Europe, Consulting Sales Section
Data 10m 7m Airflow = 3214 m³/h = 896 l/s H = 3,5 m Daikin Europe, Consulting Sales Section
Trox Air Distribution Daikin Europe, Consulting Sales Section
Trox Air Distribution Daikin Europe, Consulting Sales Section
Trox Quick Selection Daikin Europe, Consulting Sales Section
Position and type of resisters 10m How many resisters? L < 1,5 * W 10 < (1,5 * 7 = 10,5) L < 3 * H 10 < 3 * 3,5 = 10,5 in theory, 1 resister could do but the airflow = 896 l/s is TOO BIG for 1 resister 7m For a better air distribution, to avoid draft and noise, we select 8 diffusers H = 3,5 m Airflow= 896l/s Daikin Europe, Consulting Sales Section
A C B C Air Distribution 10m 8-off TDF500’s For 112l/s 7m Airflow= 896l/s Daikin Europe, Consulting Sales Section
Duct Layout Daikin Europe, Consulting Sales Section
Duct Layout Daikin Europe, Consulting Sales Section
Duct Layout - results Daikin Europe, Consulting Sales Section