An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Generation & Load Modeling Lecture #17 EEE 574 Dr. Dan Tylavsky

  2. P,Q P1,Q1 |V| P2,Q2 Lf - + Vref • Generator modeling can be very complex. • For power flow calculations, what we need is rather simple model. • Lets look at generator characteristics and develop a model from that.

  3. Under-Excitation Limit Highest permissible stator winding losses. M/c design gives max ohmic stator losses of: PSch Overexcitation limit - exciter current thermal limit. Qmax Qmin PGmin PG Under-Excitation (Small |V|). Recall Pe =EV sin /X; hence PeX/EV Small |V| large   small stability margin. QG • PGmin • Water Turbine - low output causes turburlet flow which can cause pitting type damage to blades. • Steam Turbine - don’t have enough steam to keep turbine running smoothly. PSch≡Scheduled Generation Qmax≡Q max limit @ PSch Qmin≡Q min Limit @ PSch

  4. PSch Qmax Qmin PG QG

  5. Model PL + jQL = Constant • Load Models: • Real-time load models are complex. • Voltage regulators. • Switched elements (capacitors). • FACTS (Flexible AC Transmission) devices. • Static load models have: • Voltage dependence. • Frequency dependence. • For power flow we use a simplified model:

  6. IEEE Format • Bus Data • Bus number- 4 digit right justified Cols. 1-4 • Bus Name Cols. 6-17 • Bus Area (Control Area) Cols. 19-20 • Bus Type Col. 26 • 0  Load Bus • 1  Synchronous Capactor: P=Const. & • QG=Const, Vmin<|V|<Vmax • Otherwise |V|=Vlim, Vlim=Vmin,or Vmax • 2  Generator Bus (P-V Bus) P=Const. & • V=Const, Qmin<Q<Qmax ) • Otherwise: QG=Qlim, Qlim=Qmin,or Qmax • 3  Swing Bus (V=Const., =Const.)

  7. IEEE Format • Bus Data • Final Voltage (F6.4) Cols. 28-33 • Final Angle (F7.2) Cols. 34-40 • Load PL (>0 for load) (F9.2) Cols. 41-49 • Load QL (>0 for inductive load) (F9.2) Cols. 50-58 • Load PG (>0 for P flow from generator) (F9.2) Cols. 59-67 • Load QG (>0 for Q flow from generator) (F8.2) Cols. 68-75 • Base kV - Optional (F6.2) Cols. 77-83 • Desired bus voltage (P.U.)(F6.4) Cols. 85-90 • Min. Voltage (PU) or VAR limit(MVAR) Cols. 91-98 • (F8.2 or F8.4, respectively) • Max. Voltage (PU) or VAR limit(MVAR) Cols. 99-106 • (F8.2 or F8.4 , respectively)

  8. IEEE Format • Bus Data • Shunt Conductance (PU) (F8.4) Cols. 107-114 • Shunt Susceptance (PU) (F8.4) Cols. 115-122 • Capacitors are entered a +|B| • Reactor entered as +|G|, -|B| • Remote Control Bus (I4) Cols. 124-127

  9. The End