Harmonic Distortion on the CHESF Transmission Grid Caused by: TV Receivers)

The World Cup Soccer and Harmonic Distortion Paulo F Ribeiro. Measurement Point. Harmonic Distortion on the CHESF Transmission Grid Caused by: TV Receivers).

Download Presentation

Harmonic Distortion on the CHESF Transmission Grid Caused by: TV Receivers)

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. The World Cup Soccer and Harmonic DistortionPaulo F Ribeiro Measurement Point • Harmonic Distortion on the CHESF Transmission Grid • Caused by: • TV Receivers) Harmonic Distortion Measurements - 230kV Substation - During World Cup Soccer Game Fortaleza, Brazil, June 12, 1986Brazil 3 X 0 Ireland

  2. Summary of the Measurements5th Harmonic Voltage – 230kV Bus Match Time

  3. Voltage at the 230kV - Detail of 13.2kV Residential Feeder Disconnection (before the beginning of the match) 7th Harmonic Led to Flexibility and Higher Tolerance Clearly indicates the origin the harmonic source / contribution to the 5th harmonic distortion on the 230kV bus.