170 likes | 385 Views
Computer Based Systems R&D-ES, NPCIL. About R&D-ES, NPCIL Established in 2001 Computer Based System Software & Hardware Development Systems Developed for TAPS - 3&4 (2001-2004) Test & Monitoring System (TMS-II) ECCS Test Facility (ETF) Instrumented Channel Monitoring System (ICMS)
E N D
About R&D-ES, NPCIL • Established in 2001 • Computer Based System Software & Hardware Development • Systems Developed for TAPS -3&4 (2001-2004) Test & Monitoring System (TMS-II) ECCS Test Facility (ETF) Instrumented Channel Monitoring System (ICMS) Reactor Power Display System (RPDS) Computerized Operator Information System Gateway (COIS - GW) Neutronic Trip Unit (NTU)
Systems developed at R&D-ES, NPCIL Kaiga -3&4 and RAPP-5&6 (2004-2008) Computer Channel Temperature Monitoring System (CCTMS) Radiation Data Acquisition System (RADAS) Digital Recording System (DRS) Programmable Digital Comparator System – Process Control System (PDCS-PCS) Programmable Digital Comparator System – Primary Shutdown system (PDCS-PSS) Dual Computer Hot Standby - Process Control System (DCHS-PCS) Dual Computer Hot Standby - Reactor regulating system (DCHS-RRS) Computerized Operator Information System - Gateway (COIS-GW) Reactor Power Display System (RPDS) Rod Monitoring Unit (RMU) RAPP-5&6 Electrical Supervisory Control and Data Acquisition System (ESCADA)
Electrical Supervisory Control and Data Acquisition System ( ESCADA ) • Monitoring of Electrical Parameters • Status of Electrical Equipments • Event Recording • Supervisory Control on Electrical Systems
Display LAN-1 Display LAN-2 SERVER-2 SERVER-1 I/O LAN-1 I/O LAN-2 CER RTU-5 TB RTU-5 CER RTU-6 TB RTU-6 220KV SY RTU 440KV SY RTU RAPP 5&6 ESCADA ARCHITECTURE MMI in Master Control Room-5 MMI in SwitchYard Control Room MMI in Master Control Room-6 Program Station Printer
Features of ESCADA – RTU • Dual Redundant CPU boards based on 32 bits 68020 microprocessor • Separate CPU for ESR for scanning @2 ms. • Analog I/P – 576, Digital I/P – 4096, Digital O/P – 496 • Main CPU scans Analog I/Ps @ 1s & Digital I/P @ 10ms • Communication with Servers on Dual Redundant LAN I/O LAN. • Time synchronization. • Self Diagnostics. • RTU identification. • Relay Actuation.
Features of ESCADA – Servers • Dual Redundant Servers • Server- Dual Xeon 3.6 G Hz based Computer • Dual Hard Disk (RAID) • Acquires data from all RTU over dual redundant I/O LAN • Processes data and stores it for archival • Communicates with Display station Over Dual Redundant Display LAN • Alarm generation and transmission • Validation of device operation commands • Provides password protected supervisory control • Also works as Display Station
Features of ESCADA - Display Stations • P 4 based Computers for Operator Interface • Communicated over Dual Redundant Display LAN with Servers • Provides various functionality Mimic display and equipment operation. Display of online data in various formats. Display of history data and analysis. Display of Alarms and other messages. Diagnostic display. System configuration using mimic editor, database editor, report generator and other display Transfer of data to CD, DVD and Pen-Drive