Robustness assessment for multiple column loss scenarios

Robustness assessment for multiple column loss scenarios. M. Pereira and B. A. Izzuddin Department of Civil and Environmental Engineering. Robustness assessment framework. Robustness Assessment. Damage Scenarios. Single Damage Scenario. Multiple Damage Scenarios.

long
Download Presentation

Robustness assessment for multiple column loss scenarios

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Robustness assessment for multiple column loss scenarios M. Pereira and B. A. Izzuddin Department of Civil and Environmental Engineering

  2. Robustness assessment framework Robustness Assessment Damage Scenarios Single Damage Scenario Multiple Damage Scenarios Sudden single column loss Sudden single column loss Sudden two adjacent column loss

  3. Column loss scenario – Main Stages • Nonlinear static response of the damaged structure under gravity loading • Simplified dynamic assessment to establish the maximum dynamic response under column loss scenarios • Ductility assessment of the connections/structure

  4. Dynamic response of a SDOF system – Point Load - =

  5. Dynamic response of a SDOF system – UDL - =

  6. Dynamic response of a MDOF system – UDL - =

  7. Pseudo-static response of a MDOF system

  8. Simplified Dynamic Assessment – Case Study Floor system Service Load Edge: 406UB38 (Floor), 305UB28 (Roof) Internal: 305UB25 (Floor), 152UB16 (Roof) Transverse: 356UC153 (Floor), 254UC107 (Roof) Floor Dead Load: 4.2 kN/m2 (factored 1) Floor Live Load: 5.0 kN/m2 (factored 0.25) Edge Floor (Facade) Dead Load: 8.3 kN/m Roof Loads : ½ of Floor Loads

  9. Individual beam level – Longitudinal edge beam Rigid Column Flexible Column

  10. Longitudinal edge beam - Rigid Column 2 Point Load Uniformly Distributed Load • Accurate approximation of the dynamic response for both loading cases • Slight overestimation as expected in the static analysis more visible for 2 point load (concentrated masses) • High frequencies excitation for uniformly distributed mass case

  11. Longitudinal edge beam - Flexible Column Uniformly Distributed Load • Good approximation of the dynamic response for a case with variable deformation mode during loading • Slight overestimation in the static analysis • High frequencies excitation

  12. Individual floor level Detailed Floor Grillage Model Simplified Floor Grillage Model Compatibility between members assuming a governing mode and

  13. Individual floor (Pseudo) Static vs. Dynamic Detailed Model (Pseudo) Static Detailed vs. Simplified Models • Vertical displacement point of zero system acceleration (maximum static displacement) corresponds to point of exact vertical reaction prediction as expected • Under/overestimation of vertical support reaction is observed for total down/upwards acceleration • Accurate approximation of the dynamic response • Dominant trapezoidal mode of deformation for floor system • Additional rotational restraint given by transverse beams torsional stiffness • Better approximation of structural response from assembling individual beams with rigid columns, rather than flexible columns • Use of longitudinal edge beam for governing member and imposed compatibility in remaining floor members • Good approximation of floor vertical support reaction from individual beams (rigid columns) vertical reaction profiles

  14. Conclusions • Successful extension of the multi-level simplified dynamic assessment to structures subjected to two adjacent columns loss • Dominant trapezoidal mode observed even for asymmetric load/structural configuration • Consideration of reaction transmitted to surrounding structure for alternate load path assessment (including column resistance / connection shear failure) • Further studies on effect of high frequency excitation in instantaneous system failure

  15. Conclusions • Comparing the dynamic and pseudo-static responses: • Validity of the assumption of zero kinetic energy at maximum dynamic displacement for MDOF system; • Conservative assumption of the inertial forces distribution for determination of dynamic vertical support reaction. • Comparing detailed and simplified assembly models responses: • Simplified models are feasible for structures exhibiting constant deformation mode during loading.

  16. Multiple floors level Detailed Multiple Floors Model Simplified Multiple Floor Model Compatibility between members assuming a governing mode and

  17. Multiple floors (Pseudo) Static vs. Dynamic Detailed Model (Pseudo) Static Detailed vs. Simplified Models • Accurate approximation of the dynamic response • Dominant trapezoidal mode of deformation for multiple floor system • Vertical displacement point of zero system acceleration (maximum static displacement) corresponds to point of exact vertical reaction prediction as expected • Under/overestimation of vertical support reaction is observed for total down/upwards acceleration • Good approximation of structural response either using detailed floors assembly or starting from individual beams assembly. • Equally satisfactory approximation using either 1st Floor or Roof longitudinal edge beams as governing members • Satisfactory approximation of floor vertical support reaction from individual beams (rigid columns) vertical reaction profiles taking into account moderate load redistribution between floors