1 / 4

Sepam series 10

Sepam series 10. Proprietary current sensors CRa, CRb, CSa, CSB. Use of RM6/SFset proprietary sensors CRa, CRb, CSa CSb. RM6 and SFset use specific current sensors initially developed to be used with VIP range relays. CRa : 200A/1A rated for RM6 CRb : 1250A/1A rated for RM6

lopezt
Download Presentation

Sepam series 10

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Sepam series 10 Proprietary current sensors CRa, CRb, CSa, CSB

  2. Use of RM6/SFset proprietary sensors CRa, CRb, CSa CSb • RM6 and SFset use specific current sensors initially developed to be used with VIP range relays. • CRa : 200A/1A rated for RM6 • CRb : 1250A/1A rated for RM6 • CSa : 200A/1A rated for SFset • CSb : 1250A/1A rated for SFset • As they were developed for VIP range only, these sensors were not classified in accordance to the standards : they don't have any classification like 5P20 for IEC or C20/C50. • These sensors can be used with Sepam series 10 with some restrictions

  3. Measured Current Linear region ISC Use of RM6/SFset proprietary sensors CRa, CRb, CSa CSb • CT behavior • CT has a linear region where secondary current is the exact image of primary current • Above this region, CT will saturate and become non linear • CT must only be used in the linear region

  4. Use of RM6/SFset proprietary sensors CRa, CRb, CSa CSb • Condition of use with Sepam series 10 :