SEPAM Communications Troubleshooting. Power. Communications module not powered. Power. Communications module not powered. Terminating Jumper. Protocol. Modbus Wiring . 2-Wire RS-485 + connects to + and – connects to - 4-Wire RS-485 +’s and –’s are swapped TX+ > RX+, TX- > RX-, etc.
E N D
Power • Communications module not powered
Power • Communications module not powered
Modbus Wiring • 2-Wire RS-485 • + connects to + and – connects to - • 4-Wire RS-485 • +’s and –’s are swapped • TX+ > RX+, TX- > RX-, etc.
Modbus Configuration • Modbus Address, Parity, Baud Rate
Incorrect Sepam Port selection • Sepam 80 has dual comm and remote module ports
ION Master Connections • To communicate to an ION meter there are two communication port settings that need to be made. • Comm port on the meter needs to be set to Modbus Master • Modbus Master Options Module must have the comm port assigned to ModbusGate Connection
Common Wrench Errors • Wrench 1 (most common) • Typically CCA63x (CT module) is absent • I/O module is absent • Wrench 2 • Typically caused by faulty wiring between remote module connection. • Wrench 3 • MET148-2 (Temp Module) module is not available • Wrench 4 • MSA141 (Analog Module) is not available • DSM303 (Remote Display) is not available • Wrench 5 • MCS025 (Sync-Check) is not available • Wrench 10 • CPU overload (Sepam 80 only) typically caused by excessively large Logipam program
Wrench 1 • Normally caused by: • CT module not attached to relay • I/O card is configured in the software but is not attached to relay • If you are unable to connect with SFT2841 it could indicate a major fault with the base unit • On Sepam 80 it could indicate a faulty memory cartridge
Verifying Cause of Error • IF you are able to connect with the software…