1 / 17

Simulation Method for Quantifying Induced Voltage & Current in AC Transmission Circuits

Explore safety concerns in de-energized circuit maintenance with induced voltage and current simulations. Learn about electrostatic and magnetostatic coupling principles. Study the impact of removing protective grounds and enhance work practices. Discover concepts for parallel and partially parallel lines. Evaluate a comprehensive case study, theoretical frameworks, and safety measures. Access valuable insights on minimizing hazards during line maintenance.

lorend
Download Presentation

Simulation Method for Quantifying Induced Voltage & Current in AC Transmission Circuits

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Novel Simulation Method to Quantify Induced Voltage & Current between Parallel or Partially Parallel Proximity AC Transmission Circuits Xuan Wu, David Meisner, Vinod Simha and Ronald Wellman • Videos • Electric Arc from an De-energized Line Induced by Proximity Energized Circuits 1 2 • Lineman Removing a Temporary Protective Ground

  2. Background & Purpose • Electrostatic and Magnetostatic coupling can cause personnel safety concerns • A de-energized power line in the vicinity of an energized line. • Temporary protective grounds (TPGs) typically used for de-energized transmission line maintenance Lineman Working Zone Substation B Substation A Circuit Breaker Circuit Breaker Hot-stick Temporary Protective Grounds • Installing/removing TPGs is a slow switching (manual) movement, which may produce an electric arc influenced by recovery voltage and interrupting current. • Meanwhile, removing the last TPG is always the worst-case scenario

  3. Concepts for Totally Parallel Lines

  4. Concepts for Partially Parallel Lines

  5. Concepts for Partially Parallel Lines

  6. Concepts for Partially Parallel Lines

  7. Concepts for Partially Parallel Lines

  8. Simulation & Comparison

  9. Simulation & Comparison

  10. AEP Case Study

  11. AEP Case Study (Results) Table 4 Induced Voltages of Selected De-energized Circuit Phase Conductors Table 5 Induced Current in De-energized Circuit with TPGs Installed in Shared Right-of-Way

  12. AEP Case Study (Discussions) • The induced voltage on phase b for the 345 kV double-circuit transmission network is always the smallest. This is because it is farthest from the energized conductors in the AEP circuit arrangement as shown in the right figure. • Furthermore, the next smallest phase voltage for 345 kV double-circuit lines will be based on the conductor’s location to the shield wire. The phase that is closest to the shield wire will be more coupled to ground potential and the resulting induced voltage will be lower. • The electrostatically induced charging current is typically smaller than the magnetostatically induced loop current. The electrical field induced current (charging current) is very sensitive to line separation and quickly diminishes as the distance between two unparalleled line sections is increased. • Two TPG removal scenarios are mentioned in the introduction. Based on simulation and field testing experience, the removal of the last and final TPG leads to the longest arc. Therefore, the induced voltage in Table 4 and the charging current in Table 5 are of specific interest when developing safe work practices for line maintenance work.

  13. Line Charging Ground Switches • Permanent ground switches eliminate the risk (electric arc hazards) caused by high induced voltage/current when installing or removing the Temporary Protective Ground (TPG). • Permanent ground switches are installed at both the 345 kV terminal stations when two 345 kV circuits share the same T-Line structures from station to station. Lineman Working Zone Substation B Substation A Circuit Breaker Hot-stick Circuit Breaker Permanent Ground Switch Permanent Ground Switch Temporary Protective Grounds

  14. Conclusions & Future Works • This paper presents the theory of electrostatic and magnetostatic coupling on adjacent transmission lines. Additionally, expanded concepts including more complex line configurations with both parallel and unparalleled line sections are examined. A computer simulation is presented using CDEGS software. Calculated induced voltages and currents were well matched when compared with the previous field measurements reported by Horton [2]. An AEP station case is presented to study coupling effects of a complex, five-circuit EHV line system. • Further work needs to be done concerning the arc behaviour when removing TPGs from a de-energized line. The safety criteria associated with arc length and incident thermal energy are needed to be researched. The authors intend to continue this future work for inclusion in other technical papers.

  15. Bibliography • Electric Power Generation, Transmission, and Distribution, OSHA 29 CFR 1910.269. • R. Horton, K. Wallace, “Induced voltage and current in parallel transmission lines: causes and concerns”, IEEE Transaction on Power Delivery, Vol. 23, No. 4, Oct. 2008. • R. Horton, K. Wallace, and M. Halpin, “Induced voltage in parallel transmission lines caused by electric field induction”, presented at the IEEE ESMO Conf., Albuquerque, NM, 2006. • A. Mousa, “New grounding procedures for work on de-energized lines eliminate the need for ground switches”, IEEE Transaction on Power Apparatus and Systems, Vol. PAS-101, No. 8, Aug. 1982. • “EPRI Transmission Line Reference Book 345 kV and Above”, EPRI, Palo Alto, CA, 1975, Elect. Power Res. Council. • H. Zhang, G.G. Karady, J. Hunt, “Effect of various parameters on the inductive induced voltage and current on pipelines”, IEEE Power and Energy Society General Meeting, 2011, 1-7. • Z. Wang, Q. Qiu, D. Ball, L.E. Anderson, “Case Study – Effects of Geomagnetically Induced Current (GIC) Neutral Blocking Device”, presented at 2014 CIGRE Grid of the Future Symposium, Houston, TX, October 19~21, 2014

  16. Questions ? Comments ?

  17. Thank You!

More Related