Tool Development for Peak Electrical Demand Limiting Using Building Thermal Mass January 2004 Jim Braun and Kyoung-Ho Lee Purdue University Ray W. Herrick Laboratories Purdue University
Project Objectives • Further develop and validate inverse building modeling tool • a tool for developing site-specific strategies and evaluating field site savings • Evaluate potential for demand reduction in a small commercial building structure
Project Approach • Develop calibrated forward simulation model for the Iowa Energy Center (IEC) • Use forward simulation to evaluate model structure and data training requirements for an inverse building model • Train inverse building model using available data from the IEC • Study impact of precooling duration and on-peak period on peak cooling demand for the IEC
Iowa Energy Center(Energy Resource Station) • Well-instrumented test rooms that are representative of a small commercial building (east, south, west, and internal zones) • No “internal” thermal mass (only floor and exterior walls) • Data collected in summer of 2001 for both night setup and a precooling strategy
Facility Layout EA, EB - EAST TEST ROOMS SA, SB - SOUTH TEST ROOMS WA,WB - WEST TEST ROOMS IA, IB - INTERIOR TEST ROOMS
Strategies for 2001 Tests • Night Setup Control: Phase I Testing • 74 F occupied setpoint (7 am – 6 pm) • 90 F unoccupied setpoint (6 pm – 7 am) • Precooling Control Strategy: Phase II Testing • 68 F setpoint for midnight – 6 am • 74 F setpoint 6 am – 6 pm • 90 F setpoint for 6 pm – midnight
Phase I, Interior A: August 10 - 11 4000 Phase II, Interior A: August 19-20, 2001 3500 3000 2500 Sensible Cooling Load (Btu/hr) 2000 1500 1000 500 0 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 45 47 Hour Test Results - Interior Test Rooms
70000 Phase I, All Rooms: August 10 - 11 Phase II, All Rooms: August 19-20, 2001 60000 50000 40000 Sensible Cooling Load (Btu/hr) 30000 20000 10000 0 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 45 47 Hour Test Results – All Test Rooms
Inverse Model Structure Ta Qsol,r Ta Qsol,e Tzo Qg,rad,i Qg,conv Tz Ta Qg,rad,e Qg,rad,f Qsol,f Resistance Capacitance Tg
Model Training Inputs • Measurements • ambient/zone temperature • solar radiation • internal gains Training Global Search (Systematic Search) Estimated R & C Building Model Building Model Local Search (Non-Linear Regression) Testing Best R & C • cooling loads • zone temperatures Prediction of Loads (Building Simulation) Outputs
Effect of Training Length (simulated data, precooling strategy for training and testing)
Effect of Control Strategy (simulated data, night setup for training and precooling for testing)
Demand-Limiting Control Evaluation Basic Demand-Limiting Strategy • Unoccupied Period: precool at 67 F • Occupied, Off-Peak Period: maintain zone at 69 F • Occupied, Demand-Limiting Period: maintain zone at 69 F until load exceeds target, then operate at maximum target capacity and allow temperature to float Parametric Studies • Considered individual days (steady-periodic condition) • Determined target that allowed temperature to float between 69 and 76 F within occupied period • Varied start times for precooling and demand-limiting periods
Precooling with Afternoon Demand Limiting(South, East, West, and Interior Zones Combined) 30% Afternoon Peak-Load Reduction with No Precooling 69 F – 76 F Over Last 6 Hours of Occupancy
No Precooling with Afternoon Demand Limiting(South, East, West, and Interior Zones Combined) 27% Afternoon Peak-Load Reduction with No Precooling 69 F – 76 F Over Last 6 Hours of Occupancy
Precooling with All-Day Demand Limiting(South, East, West, and Interior Zones Combined) 23% Daytime Peak-Load Reduction with Precooling 69 F – 76 F Over 8 Hours of Occupancy
Peak Load Reduction Potential(South, East, West, and Interior Zones Combined) Precooling Start-Time 20-40% Peak-Load Reduction with Precooling
West Zone Demand-Limiting Results(No Precooling, Afternoon Demand Limiting) 35% Peak-Load Reduction at End of Day 69 F – 76 F Over Last 3 Hours of Occupancy
Conclusions Afternoon Demand-Limiting • 30-40% Peak Load Reduction with zone temperature adjustments from 69 - 76 F • Precooling has small effect on afternoon peak • Potential for large morning peak with no precooling All-Day Demand-Limiting • ~20% Peak Load Reduction with zone temperature adjustments from 69 - 76 F • Precooling has significant effect
Control of Building Mass inSmall Commercial Buildings ??? • Peak load and load shifting potential is very significant • Major portion of the total building stock cooling requirements • Implementation requires automation • Packaged equipment with on/off control and individual thermostats (no EMCS) • Very small ratio of human-to-equipment supervision • Potential for automation is high • System simplicity is an asset (1 thermostat per unit) • Thermostat call for cooling is a load measurement • Modern thermostats can be connected to a network and obtain utility and weather information