YS100 Series A Complete Process Control Solution!

YS170 Dual Loop Programmable Controller. YS100 Series A Complete Process Control Solution!. YS100 Control Room Instruments. YS150 Pre-configured single loop YS170 Programmable dual loop (plus YS150) YS110 Standby manual station YS131 Dual input indicator with alarms

maitland
Download Presentation

YS100 Series A Complete Process Control Solution!

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. YS170 Dual Loop Programmable Controller YS100 Series A Complete Process Control Solution!

  2. YS100 Control Room Instruments • YS150 Pre-configured single loop • YS170 Programmable dual loop (plus YS150) • YS110 Standby manual station • YS131 Dual input indicator with alarms • YS135 Auto/Manual Station SV Loader • YS136 Auto/Manual Station MV Loader • YSS20 Programming Software

  3. YS100 Hardware Platform • Surface mount technology: reliable & low power • Non-volatile memory (EEPROM) • Up to 400 lines of programming (YS170) • Modular construction with separate boards for: • Power supply (auto sensing AC or DC voltage) • Communications (RS485, DCS, Peer-to-Peer) • Signal conditioning input • Independent CPU’s for control and display • 24VDCPower for two-wire transmitters • Integral HARD MANUAL backup

  4. YS150 Pre-Configured • No programming • Setup without PC • 3 ready to go strategies • Single PID • Cascade PID • Hi/Lo Auto Select

  5. YS150 Single Loop Strategy

  6. YS170 Programmable Dual Loop • All the YS150 functions • 2 Independent PID loops • 400 lines of custom code

  7. YS150/170 Model Description

  8. YS150/170 Inputs/Outputs • Controller Inputs/Outputs YS150 YS170 • Analog inputs 4 5 • 4-20mADC analog output 1 1 • 1-5VDC analog output 2 1 • Selectable 4-20mA/1-5V 0 1 • Discrete inputs 1 fixed function 6 DI/DO • Discrete outputs 5 fixed function (Software Selectable) • Independent PID loops 1 2

  9. YS131 Dual Input Indicator Tag Name FI-1076 FAIL FAIL & ALM Lamps ALM LOOP 1 GPM 300.0 PV: Process Variable 146.9 Set Point CHANGE Key (Press to Observe HH/LL Alarm Value) CHG 0.0 PAGE key SHIFT YOKOGAWA

  10. Tag Name HIC-1076 FAIL FAIL & ALM Lamps ALM LOOP 1 C GPM CASCADE (Remote SV) 300.0 Process Variable PV: 146.9 Set Point SV: M Set Point MANUAL Mode Override Remote SV 150.0 /\ & \/ Local Set Point 0.0 PAGE key SHIFT  YOKOGAWA YS135 SV Auto/Manual Station

  11. HIC-1076 Tag Name FAIL FAIL & ALM Lamps ALM LOOP 1 C GPM CASCADE (Remote MV) Control Input from External Device 300.0 Process Variable PV: 146.9 Set Point M Manipulated Variable (Control Output) MANUAL Mode (Override Remote MV) MV: 77.7 0.0 PAGE key C O /\ or \/ Output SHIFT  YOKOGAWA YS136 MV Auto/Manual Station

  12. INPUT 100 BAT CHK • Powered by three • Can be inserted into 9VDC batteries controller case 50 • Provides 4-20mA • Powered by 110VAC 0 OFF SET output to control while installed in OUTPUT CONT 100 element enclosure 50 INC MAN DEC 0  YOKOGAWA YS110 Remote Standby Station

  13. YS100 Signal Conditioning • One signal conditioning card per instrument • mV (/A01) • Universal thermocouple (/A02) • RTD (/A03) • Potentiometer (/A04) • Input isolator (/A05) • 2 wire transmitter input with isolation (/A06) • Frequency (/A08)

  14. YS100 Security Features • Password protection • Prevents unauthorized changes • Allows all parameters to be viewed but not changed • Built-in HARD MANUAL backup station • Used if controller fails • Controls Y1 analog output ONLY (LOOP 1) • Standard feature (specify it!)

  15. YS100 Display • Display Technology • Backlit high resolution LCD • Blue background or white background • Display Screens • LOOP (1&2) • TREND (1&2) • ALARM • DUAL (1&2) (YS150 & YS170 only) • TUNING (PID values, alarm set points, etc.) • ENGINEERING(Eng. units, tag name, etc.)

  16. +24VDC Terminal 13 + Two-Wire YS150/170 Controller Transmitter - 4-20mADC Xn + Input Analog Input Terminal # EJA YEWFLOW 250 ohms X1 Positive 1 X1 Negative 2 X2 Positive 3 X2 Negative 4 X3 Positive 5 X3 Negative 6 X4 Positive 7 X4 Negative 8 X5 Positive 9 X5 Negative 10 EXA pH200 Precision + Xn - Input Resistor Two-Wire Transmitter - 4-20mADC Xn + Input 250 ohms Two transmitters can be powered... Xn - Input Precision Resistor Direct Input Option: Reduces available power to ONE transmitter!! Wiring of 24VDC Loop Supply

  17. FIC-1076 FAIL ALM LOOP 1 TMP 122.5 C GPM 300.0 PV: A 146.9 Set Point SV: M 150.0 MV: 77.7 ALARM-1 PF PF OFF 0.0 C O SHIFT  YOKOGAWA YS170/YS150 LOOP Display • Tag Number or • Descriptor FAIL & ALM Lamps • Remote Set Point (CSV) • Local Set Point (SV) & Automatic • Manual Operation of Output (MV) DATA WINDOW • Process Variable • Set Point Value • Control Output • Increase Set Point (SV) • Decrease Set Point (SV) • Programmable Function Key • PAGE Key ALARM Indication • Manual Output • Keys (< & >) • SHIFT to observe • TUNING & ENG

  18. FIC-1076 FAIL ALM TREND 1 PV1: SV1: MV: 146.9 150.0 77.7 C GPM 300.0 A • Time base selectable • by configuration (CONFIG 2) • 90 seconds to 45 hours • 90 samples displayed • Always active • All keys operational as LOOP • display M PF PF OFF 1M O.O C O SHIFT YOKOGAWA YS170/YS150 TREND Display

  19. Process Alarms • High, low, deviation, velocity • System Alarms • Open input, output, defective A/D, • RAM, CPU • STC Alarms (Self Tuning Control) • Time out, high/low PB, TI, TD • High lighted = active/unacknowledged • alarm FIC-1076 FAIL ALM ALARM PROCESS SYSTEM C X1 PL1 PH2 A X1 M STC PF CLR C O SHIFT YOKOGAWA YS170/YS150 ALARM Display

  20. Tag Number or • Descriptor of LOOP 1 • PV1 & SV1 • highlighted • LOOP 1 operational • LOOP 2 can be only • viewed from DUAL 1 • display FIC-1076 FAIL • FAIL & ALM Lamps DUAL 1 ALM PV: 146.9 PV: 97.4 SV: 175.0 SV: 100.0 C DEG GPM • Remote Set Point (CSV) • Local Set Point (SV) & Automatic • Manual Operation of Output (MV) 2 1 300.0 200.0 A Set Point M • Increase Set Point (SV) • Decrease Set Point (SV) • Programmable Function Key • PAGE Key • Manual Output Keys • (< & >) • SHIFT + PAGE to • observe TUNING • & ENG Menus PF PF OFF 0.0 0.0 MV: 77.7 C O SHIFT  YOKOGAWA Dual Loop Display

  21. FIC-1076 FIC-1076 FAIL ALM FAIL ALM TUNING MENU ENG.MENU 1 C C PID 1 CONFIG 1 A A PID 2 CONFIG 2 M M STC 1 SMPL&BATCH STC 2 SC MAINT P&T REG PASSWORD I/O DATA FX TABLE PF PF SHIFT SHIFT YOKOGAWA YOKOGAWA Tuning/Engineering Group Menus

  22. FIC-1076 PID1 FIC-1076 200.0 PB1 FAIL ALM TUNING MENU STC OFF PV1 146.9 C PID 1 SV1 150.0 MV 77.7% DV1 3.1 A PID 2 PB1 200.0% M STC 1 TI1 10S SAV TD1 0S SFA1 0.0 STC 2 SFB1 0.0 GW1 1.0% GG1 1.000 P&T REG PH1 300.0 PL1 0.0 DL1 100.0 I/O DATA VL1 100.0 PF VT1 1S MH1 100.0% ML1 0.0% MR1 0.0% CHG RB1 0.0% PMV1 0.0% SHIFT C O YOKOGAWA Tuning Menu - PID 1

  23. FIC-1076 CONFIG 1 PANEL from ENG MENU 1 CONFIG 1 FIC-1076 PROG CTL FAIL ALM ENG.MENU 1 SET ENBL C CONFIG 1 CTL PROG START TIM1 COMM - COMWR ENBL ADRS 1 STBIT 1 PAR NO BPS 1200 ATSEL LOW LOOP1 1 LOOP2 1 TRND1 1 TRND2 1 ALARM 1 DUAL1 1 DUAL2 1 DISP1 - NAME1 PRM DISP2 - NAME2 PRM PROG DEFAULT REV 400.2 Press A button to SET... PRESS /\ key to allow ENABLE Press A to high light CTL... Press & hold /\ button to change CTL strategy: SELECT CASCADE SINGLE PROG A CONFIG 2 M SMPL&BATCH SC MAINT PASSWORD FX TABLE PF SHIFT SHIFT YOKOGAWA ENG MENU - CONFIG 1

  24. FIC-1076 CONFIG 2 FIC-1076 SCH1 3 FAIL ALM ENG.MENU 1 SET ENBL C CONFIG 1 PROG CMOD1 - BMOD BUM CNT1 PID ALG1 I-PD ACT1 RVS VDIR1 C-O SCH1 000 SCL1 0 SCDP1 3 SCDV1 1 UNIT1 GPM TRDT1 1M TAG1 FIC-1076 CMOD2 - BMOD2 BUM CNT2 PID ALG2 I-PD ACT2 RVS VDIR2 C-O SCH2 1000 SCL2 0 SCDP2 3 SCDV2 1 UNIT2 % TRDT2 1M TAG2 -YS170- A CONFIG 2 3 M SMPL&BATCH SC MAINT PASSWORD FX TABLE PF SHIFT YOKOGAWA ENG MENU - CONFIG 2

  25. FIC-1076 I/O DATA FIC-1076 FAIL ALM TUNING MENU X1 48.9 X2 0.0 X3 0.0 X4 0.0 X5 0.0 Y1 77.7% Y2 -6.3% Y3 0.0% DI1 0 DI2 0 DI3 0 DI4 0 DO2 0 DO1 1 C PID 1 A PID 2 M STC 1 STC 2 P&T REG I/O DATA PF SHIFT YOKOGAWA Tuning Menu - I/O DATA Shows analog inputs X1 - X5 Analog outputs Y1 - Y3 Discrete inputs/outputs DI or DO 0 = low 1 = high

  26. FIC-1076 CONFIG 1 PANEL from ENG MENU 1 CONFIG 1 FIC-1076 SINGLE CTL FAIL ALM ENG.MENU 1 SET ENB C CONFIG 1 CTL SINGLE START TIM1 COMM - COMWR ENBL ADRS 1 STBIT 1 PAR NO BPS 1200 ATSEL LOW LOOP1 1 LOOP2 1 TRND1 1 TRND2 1 ALARM 1 DUAL1 1 DUAL2 1 DISP1 - NAME1 PRM DISP2 - NAME2 PRM PROG DEFAULT REV 4.1 Press A button to SET... PRESS /\ key to allow ENABLE Press A to high light CTL... Press & hold /\ button to change CTL strategy: SINGLE A CONFIG 2 M SMPL&BATCH SC MAINT PASSWORD FX TABLE PF SHIFT SHIFT YOKOGAWA Pre-configured SINGLE Mode

  27. FIC-1076 FIC-1076 PID1 20.0 FAIL ALM PB1 TUNING MENU STC OFF C PID 1 PV1 146.9 SV1 150.0 MV 77.7% DV1 3.1 A M PB1 20.0% STC 1 TI1 10S SAV TD1 0S SFA1 0.0 SFB1 0.0 GW1 1.0% GG1 1.000 PARAMETER PH1 300.0 PL1 0.0 DL1 100.0 I/O DATA PF VL1 100.0 VT1 1S MH1 100.0% ML1 0.0% MR1 0.0% CHG RB1 0.0% PMV1 0.0% SHIFT C O YOKOGAWA PID Tuning Parameters PID 1 Display from TUNING Panel Press A button until PB1 is highlighted... Press \/ until PB1 is 20.0%. Change TI1 to 10 seconds. Press PAGE to return to TUNING menu. Select PARAMETER by pressing \/ button... Press A until PLG1 is highlighted... /\ until 1.0 is set...

  28. FIC-1077 FIC-1076 FAIL FAIL ALM ALM LOOP 1 LOOP 1 TMP 172.5 TMP C GPM GPM 5000.0 300.0 PV: A PV: 246.9 146.9 Set Point SV: M SV: 250.0 150.0 MV: MV: 77.7 77.7 PF PF PF OFF OFF 0.0 0.0 C O C SHIFT u YOKOGAWA u YOKOGAWA RS485 Communications Option (/A31) 122.5 C A M Up to 16 instruments/serial port PF Available on ALL YS100 Series Instruments O SHIFT

  29. MV1 SV1, Auto/Manual Status PV1 Up to 16 Instruments 4 transmitting 16 receiving YS-NET FIC-1076 FIC-1076 FIC-1076 FIC-1076 FAIL FAIL FAIL FAIL ALM LOOP 1 ALM ALM ALM LOOP 1 LOOP 1 LOOP 1 TMP 122.5 TMP 122.5 TMP 122.5 TMP 122.5 C C C C GPM GPM GPM GPM 300.0 300.0 300.0 300.0 PV: PV: PV: PV: A A A A 146.9 146.9 146.9 146.9 Set Point Set Point Set Point Set Point SV: M SV: SV: SV: M M M 150.0 150.0 150.0 150.0 MV: MV: MV: MV: 77.7 77.7 77.7 77.7 PF PF PF PF PF PF PF PF OFF OFF OFF OFF 0.0 0.0 0.0 0.0 C O C O C O C O SHIFT SHIFT SHIFT SHIFT u u u u YOKOGAWA YOKOGAWA YOKOGAWA YOKOGAWA Peer-to-Peer Communications (/A33)

  30. YSS20-210 Programming Software • Required to write a custom YS170 program • Latest edition is Version 1.04 • Required for peer-to-peer communications option (/A33 card) • Required for 400 steps of programming

  31. Write custom programs on PC Upload/download programs from PC to YS170 Data monitoring mode YSS20 Programming Software

  32. Fundamentals • Basic Features • Library of 36 function modules (PID, function generators, math, boolean logic, etc.) • 400 lines of program possible, with comments • Flexible use of software flag registers • Subroutines and conditional branching • Location of important reference material • YS170 Programming Manual is the best source • TI 1B7C2-03E • Control Functions Manual • TI 1B7C1-01E

  33. Programming Function Modules • PID Control (BSC, CSC & SSC) • Math Functions (+, -, *, /, SQT & ABS) • Program Constants (P, T & K) • Boolean Logic (AND, OR, NOT, EOR) • Alarms (HAL, LAL, DLM & VLM) • Discrete Inputs/Outputs (DI/DO) • Timers, Lead, Lag & Deadtime Functions (TIM, LED, LAG & DED) • Function Generators (FX & GX)

  34. Programmable Control Strategy Wiring Terminations

  35. Programming using the PC • File management • Program editing • Parameter editing • Communication • Documentation printing

  36. X1 + X2 = Y1 LD X1 LD X2 + ST Y1 I/O Registers X1 X2 Y1 X1 X2 X1+X2 X1+X2 Stack Registers A X1 A A B A B B C B C C D C C C Lost Stack Registers Operation