1 / 40

YUKON OPEN LOOP GEOEXCHANGE CASE STUDY Na-Cho Nyak Dun First Nation Government House

YUKON OPEN LOOP GEOEXCHANGE CASE STUDY Na-Cho Nyak Dun First Nation Government House. Presented by: Katherine Johnston, EIT EBA Engineering Consultants Ltd. What is Geoexchange?. What is Geoexchange?.

Download Presentation

YUKON OPEN LOOP GEOEXCHANGE CASE STUDY Na-Cho Nyak Dun First Nation Government House

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. YUKON OPEN LOOP GEOEXCHANGECASE STUDYNa-Cho Nyak Dun First Nation Government House Presented by: Katherine Johnston, EIT EBA Engineering Consultants Ltd.

  2. What is Geoexchange?

  3. What is Geoexchange? Geoexchange is the coupling of low-grade heat from earth sources (soil, rock, groundwater, surface water, ocean, waste heat) which is transformed using heat pump technology to higher-grade heat for building conditioning, domestic hot water or process purposes.

  4. Ground coupling side Building side Supply line Loop within Earth Energy Source Heat Pump and/or Heat Exchanger Heating/ Cooling Load Return line building How Does it Work?

  5. Ground coupling side Building side Supply line Loop within Earth Energy Source Heat Pump and/or Heat Exchanger Heating/ Cooling Load Return line building How Does it Work? Our domain

  6. Two Types of Ground Heat Exchanger Vertical Borehole System (Closed Loop) Well Water System (Open Loop)

  7. Open Loop Well Water System (Open Loop)

  8. Location Map – Village of Mayo

  9. Village of Mayo “Heart of the Yukon” • 407 km north of Whitehorse • Population 450 • Centre for mineral exploration in the central/ north Yukon • Annual “Midnight Marathon” held on the summer solstice

  10. Geologic Setting

  11. Village of Mayo Wells- History

  12. Village of Mayo – Geoexchange History • 1987-1988 GSHP commissioned to heat central building group using the existing water distribution system installed in the Village • System failure after approximately 1 yr because….

  13. Village of Mayo – Geoexchange History • Heat pump incompatibility with existing space heating systems • Power availability issues related to the Keno Hill Mine (operation until 1989) • Failure to account for groundwater quality resulted in severe encrustation/ bio-fouling of the system

  14. Village of Mayo – Key Lessons Learned • Water quality consideration in system design 2) Need for ongoing monitoring and maintenance

  15. Pre-Feasibility Study Results • Potential for existence of shallow “perched” aquifer (water supply potential) • Potential for existence of deeper “warm” aquifer • Need for potable water system regardless • Decision to proceed with combined drinking water/ geoexchange supply drilling program

  16. NNDFN Building – Expected Drilling Conditions

  17. Village of Mayo – Well Drilling

  18. Village of Mayo – Well Drilling

  19. Village of Mayo – Well Drilling

  20. Actual Drilling Conditions

  21. Open Loop - Well Screen Design

  22. Open Loop – Well Screen Installation

  23. Village of Mayo – Well Development

  24. Well Chemical Treatment and Testing

  25. Well Chemical Treatment and Testing

  26. Hydraulic Testing Results – Constant Rate Test

  27. Open Loop – Water Quality Analysis

  28. Water Quality Analysis Con’t

  29. Key Design Recommendations: • Continuous operation of the system • Implementation of a regular monitoring and maintenance schedule • Use of a single, central heat exchanger • Batch chemical injection system upstream of the injection well (CO2 and Sodium Hypochlorite) to inhibit biological activity and maintain a neutral pH

  30. Where are we now? • Yukon water license requirements for groundwater extractions above 100 m3/day (20 USgpm) • First time the Yukon water board is addressing both extraction and re-injection • Injection well construction and commissioning will follow water board approval

  31. Other Yukon Geoexchange Applications

  32. Acknowledgements: • Diana M. Allen • Broadway Architects • DEC Design • Quest Engineering Group • Na-Cho Nyak Dun First Nation

  33. Thank You! Questions? ksjohnston@eba.ca EBA Kelowna 1-250-862-4832