The Vanjen Group, LLC

The Vanjen Group offers docking stations for temporary power connections to generators, load banks, and chillers. Our docking stations provide quick, safe, and legal connection and disconnection for temporary power needs in the power generation and oil & gas industries. Learn more at www.vanjen.net.

mccrays
Download Presentation

The Vanjen Group, LLC

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. • Manufacture's Representative – Power Generation/Oil & Gas• Covering TX, OK, LA, AK, in some cases NM and MS• Extensive Power Gen Experience• Extensive Docking Station Experience – Design, installation, operation The Vanjen Group, LLC

  2. Electrical

  3. www.vanjen.net Brochures, Guides Specs, Data Sheets, Our Blog, Contact Info, Links to our manufacturers websites, & Presentations

  4. Trystar Docking Stations • What is a Docking Station? • Termination station • Quickly, Safely and Legally connect/disconnect • Temporary Generators • Temporary Load Banks • Temporary Chillers • Temporary Power

  5. Why Do I Need a Docking Station? • How does a temporary genset get connected to a building in an emergency? • How do generator service companies connect their load bank when performing their annual testing?

  6. Typical Temporary Genset Hook-Up How do cables get connected? A. Knock a hole into existing switchgear B. Run cable through the building

  7. Typical Temporary Loadbank Hook-Up How do cables get connected? Most Common – Disconnect the permanent conductors from the output side of genset circuit breaker – tie in load bank cables

  8. Typical Temporary Connection • The problem for owners: • Temp Genset • DOWNTIME • Damage to gear • Unsecured building • Outage to connect & disconnect • Electrician required • Load Bank • Customer is exposed to an outage • During connection, testing, and disconnection • Cable terminations exposed during operation • Excessive wear to breaker lugs – not torqued-stripped

  9. Typical Temporary Loadbank Hook-Up

  10. NEC 700.3 2017 Code Change • If the emergency system relies on a single alternate source of power, which will be disabled for maintenance or repair, the emergency system shall include permanent switching means to connect a portable or temporary alternate source of power, which shall be available for the duration of the maintenance or repair. The permanent switching means to connect a portable or temporary alternate source of power shall comply with the following: • 1. Connection to the portable or temporary alternate source of power shall not require modification of the permanent system wiring. • 2 . Transfer of power between the normal and the emergency source shall be in accordance with 700.12. • 3 The connection point for the portable or alternate source shall be marked with the phase rotation and system bonding requirements. • 4. Mechanical or electrical interlocking shall prevent inadvertent interconnection of power sources. • 5 . The Switching means shall include a contact point that shall annunciate the location remote from the generator or at another facility monitoring system to indicate that the permanent emergency source is disconnected from the emergency system. It shall be permissible to utilize manual switching to switch from the permanent source of power to the portable or temporary alternate source of power and to utilize the switching means for connection of a load bank. • Informational Note: There are many possible methods to achieve the requirements of 700.3(F).

  11. Go from this To this

  12. Trystar Docking Stations • What is a Docking Station? • Termination station • Quickly, Safely and Legally connect/disconnect • Temporary Generators • Temporary Load Banks • Temporary Chillers • Temporary Power

  13. Standard Construction • Available from 100A to 5000A • UL 50 powder coated aluminum or stainless steel enclosure • Lockable rake system reduces cable theft & cable disconnection • Cam lock style inputs and/or outputs, mechanical lugs, or pin and sleeve • Phase rotation meter

  14. Standard Docking Station Simple Camlock or Mechanical Lug connection box. Provides no isolation between sources Temporary generator Temporary load bank Temporary chiller Company switch Can be factory mounted to 3rd Party MTS and shipped pre-packaged together

  15. Pair With Transfer Switch • Includes 2 wire auto start terminal and phase rotation monitor. • Available with battery charger and water heater outlets • Available as dual purpose for load banking permanent gen

  16. Docking Station With Kirk Key Kirk Key Provides isolation between sources Temporary generator Temporary load bank Temporary chiller Company switch Many variations can be achieved through multiple kirk key Interlocks

  17. How does a Kirk Key System work? Key is Captive and cannot be removed while Breaker is “On Docking station door cannot be unlocked without key

  18. How does a Kirk Key System work? Once breaker is in ”Off” position captive key can be removed Key can then be used to unlock docking station door

  19. Breakered Docking Stations Service Entrance Rated Distributions & Feeder Breakers Temporary Generator Breaker Temporary generator Temporary chiller Company switch Distribution breakers allow for maximum flexibility

  20. Dual Purpose Docking Stations Used in conjunction with a permanent installed generator Provides temporary generator connection & temporary load bank connection Offer load dump circuitry Offers remote start capability

  21. How does the Remote Start circuit work? Circuit wired in parallel with automatic transfer switch

  22. How does the Load Dump circuit work? Circuit wired in parallel with automatic transfer switch position contacts

  23. Rotary Docking Stations Integrated Manual Transfer Switch and Docking Station Three Position Utility-Off-Generator, Up to 1200A Option for Service Entrance Rating

  24. Output Docking Stations Temporary Chiller Used to quickly connect temporary chillers Healthcare & Data Centers Company Switches Convention Center, Stadiums & Arenas

  25. Accessories Gland Plates Inlet Panels Designed to be mounted on single and double throw type disconnect switches. • Mount to temporary gensets, ATS, or Switchgear

  26. Why Trystar Market Leader in Docking Stations Superior Product Construction, Design & Engineering Invented the Dual Purpose Docking Station 100% Rated Full Buss used in Construction No cabling between sections Full ETL 1008 Listing (ATS Listing) Not UL 508A like most/others Enclosures, engineering, bussing, testing, UL certifications all done in house

  27. Recap Construction: • Up to 5,000A • Nema 3R and 4X Used for connections: • Temporary generators • Load banks • Chillers • Output power (Company switches) Models: • Generator Docking Station – with and without Kirk Key • Breakered Docking Station • Dual Purpose Docking Stations • Rotary Docking Stations Options include: • Kirk key interlocks • Service entrance breakers • Distribution breakers • Remote start terminals • Load dump terminals

  28. www.vanjen.net