LCLS Intermediate Power Supplies Paul Bellomo, Antonio de Lira, Dave Mac Nair. LCLS Intermediate (LGPS but rack-mounted) Power Supplies MCOR Bulk Power Supplies Injector Bend, Solenoid, and QB Power Supplies Power Supply Controllers and Transductors. 2.5 kW to 22.5 kW
E N D
LCLS Intermediate Power Supplies Paul Bellomo, Antonio de Lira, Dave Mac Nair
LCLS Intermediate (LGPS but rack-mounted) Power Supplies • MCOR Bulk Power Supplies • Injector Bend, Solenoid, and QB Power Supplies • Power Supply Controllers and Transductors
2.5 kW to 22.5 kW • 208 V / 480 V input • Series and parallelable • 27cm H*48cm W*61cm D What is the desired LCLS color scheme for power supplies and racks, etc?
Hazard Analysis • Bleeder resistors Across LF/HF filter capacitors • PPS interface External, upstream redundant AC contactors • Flammable liquids Trace amounts in electrolytic filters • Hazard signs Labels on PS for voltage and heat hazards • MPS interface In Ethernet chassis, open contact removes ON • Protective CB Lockable and covered line-load terminals • Soft-start Prevent input current surge • Totally enclosed AC plug, cover over DC terminals • Other components Non-flammable or fire retardant • Other Use listed components wherever possible and SLAC EEIP inspection prior to or after shipping
8 (1 contingency) Ethernet power supply controllers - $2,000 * 8 = $16,000
GMW Associates955 Industrial RoadSan Carlos, CA 94070650-802-8292 ian@gmw.com 7 systems * 2 /system *$660ea = $9,240 Mounting plates 2 plates * $250 each = $500