An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. The School of Forest Resources BuildingAquaculture Lab Lighting Layouts Chris Hoyman Dr. Mistrick, Faculty Advisor February 3, 2006

  2. Overview • The first space chosen for redesign was the Aquaculture Lab located in the basement. An analysis of the general room lighting was performed. Lights in the individual tanks are controlled centrally from a dimming panel with a day/night cycle setting.

  3. Overview • The original design, pictured here, used suspended linear fluorescent downlight fixtures, with no drop ceiling. For the redesign, I applied two new systems along with a drop ceiling.

  4. Overview • In applying the drop ceiling, I hope to create a brighter, more uniform looking space. Hiding the currently exposed piping will give the room a cleaner look as well. With the increased reflectance off the drop ceiling tiles it may be possible to reduce the overall number of fixtures in the room (saving on fixture and energy costs).

  5. Original Design • Original design featured 18 suspended fluorescent fixtures • Two 32W T8 bulbs each • 59W Input for two lamp ballast, 18 total • 1062W total over an are of 760 sq. ft. • Power Density = 1.4 sq. ft.

  6. Original Design

  7. Original Design

  8. Original Design

  9. Original Design

  10. Original Design

  11. New Design- Suspended • New design features 15 suspended fluorescent fixtures with a drop ceiling • Two 28W T5 bulbs each • 63W Input for two lamp ballast, 15 total • 945W total over an are of 760 sq. ft. • Power Density = 1.24 sq. ft.

  12. New Design- Suspended

  13. New Design- Suspended

  14. New Design- Suspended

  15. New Design- Suspended

  16. New Design- Suspended

  17. New Design- Suspended

  18. New Design- Suspended

  19. New Design- Suspended

  20. New Design- Suspended

  21. New Design- Suspended • New design useless less energy, fewer fixtures, has lower Avg./Min. and Max./Min. ratios, and creates a more comfortable space.

  22. New Design- Recessed • New design features 15 recessed fluorescent fixtures with a drop ceiling • One 54W T5 bulb each • 62W Input for one lamp ballast, 15 total • 930W total over an are of 760 sq. ft. • Power Density = 1.22 sq. ft.

  23. New Design- Recessed

  24. New Design- Recessed

  25. New Design- Recessed

  26. New Design- Recessed

  27. New Design- Recessed

  28. New Design- Recessed

  29. New Design- Recessed

  30. New Design- Recessed

  31. New Design- Recessed • New design useless less energy, fewer fixtures, has lower Avg./Min. and Max./Min. ratios, and creates a more comfortable space.

  32. New Design • Both new designs performed better than the existing, however the suspended system yields higher illumination and better uniformity for only a small increase in power density. • The suspended system with the drop ceiling was chosen for the final design.

  33. Light Loss Factors • LDD- suspended- Category II, very clean environment, 12 month cycle, LDD=0.97 • LDD- recessed- Category IV, very clean environment, 12 month cycle, LDD=0.94 • LLD- suspended- 2697/2900=0.93 • LLD- recessed- 4650/5000=0.93

  34. Light Loss Factors • RSDD-suspended- 7% expected dirt depreciation, Direct/Indirect, RCR= 3.1 (H=8’), RSDD= 0.94 from table • RSDD-recessed- 7% expected dirt depreciation, Direct, RCR= 3.9 (H=10’), RSDD= 0.97 from table

  35. Suspended System- Circuits • 63W/ fixture * 15 fixtures= 945 W • Power factor = 0.99 • 945W / 0.99 pf = 955 VA • 955 VA / 277V = 3.45 A • 16A limit, only one circuit needed

  36. Suspended System- Switching • General lighting in the room is for the occupants only, during observation and experiments. Dimming on this lighting is not required. For some flexibility of light levels, and potential energy savings, each row of lights (in the longer direction) will be switched together. In this manner the two outer rows could be on leaving the middle row off if desired (see next slide).

  37. Suspended System-Switching

  38. Notes • This space is not going to be one of the photo quality rendering spaces I complete for the final submission • All AGI files, cutsheets, and assorted information are available on my P Drive, under thesis/aquaculture.