EVALUATION OF ISLANDED GRID OPERATION TESTS AND DYNAMIC MODELLING. Dr. Robert Schmaranz – Austria – Session 3 – Paper 0570. CONTENT. Grid Topology and Islanded Operation Dynamic Simulation Model Evaluation Minimal Machine Configuration Conclusion.

newman
Download Presentation

Dr. Robert Schmaranz – Austria – Session 3 – Paper 0570

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. EVALUATION OF ISLANDED GRID OPERATION TESTS AND DYNAMIC MODELLING Dr. Robert Schmaranz – Austria – Session 3 – Paper 0570

  2. CONTENT • Grid Topology and Islanded Operation • Dynamic Simulation Model • Evaluation • Minimal Machine Configuration • Conclusion Dr. Robert Schmaranz – Austria – Session 3 – Paper 0570

  3. Grid Topology in Carinthia Malta-Oberstufe Rennweg Zirknitz Innerfragant Außerfragant St. Leonhard Malta-Hauptstufe Treibach Gurk Reißeck Wolfsberg Lieserbrücke Wölla Radenthein Malta-Unterstufe Wietersdorf Kleinkirchheim Lienz Steinfeld St. Andrä Spittal/Drau St. Veit Brückl Windischbach Oberdrauburg Feldkirchen Kamering Obersielach Ettendorf Würmlach Landskron Klagenfurt Lassendorf Schwabeck Tröpolach Nord Ost Gummern Hermagor Forstsee Koralpe Völkermarkt Seebach Lavamünd Vorderberg Warmbad West Süd Edling Bleiburg Gailitz Siemens Rosegg Freibach Annabrücke Fürnitz St.Martin St.Margarethen Feistritz Ferlach 110-kV 220/380-kV Dr. Robert Schmaranz – Austria – Session 3 – Paper 0570

  4. Islanded Operation Malta-Oberstufe Rennweg Zirknitz Innerfragant Außerfragant St. Leonhard Malta-Hauptstufe Treibach Gurk Reißeck Wolfsberg Lieserbrücke Wölla Radenthein Malta-Unterstufe Wietersdorf Kleinkirchheim Lienz Steinfeld St. Andrä Spittal/Drau St. Veit Brückl Windischbach Oberdrauburg Feldkirchen Kamering Obersielach Ettendorf Würmlach Landskron Klagenfurt Lassendorf Schwabeck Tröpolach Nord Ost Gummern Hermagor Forstsee Koralpe Völkermarkt Seebach Lavamünd Vorderberg Warmbad West Süd Edling Bleiburg Gailitz Siemens Rosegg Freibach Annabrücke Fürnitz St.Martin St.Margarethen Feistritz Ferlach 110-kV 220/380-kV 110-kV islanded grid (length: 180 km) participating power plants Dr. Robert Schmaranz – Austria – Session 3 – Paper 0570

  5. real devices simulation model Dynamic Simulation Model Matlab - Simulink • Generators • Hydro governor • Excitation systems • Grid elements • Loads Dr. Robert Schmaranz – Austria – Session 3 – Paper 0570

  6. Evaluation • Measured vs. simulated • time courses • Optimization of the • simulation model • Implementation of • nonlinear behavior • Sufficient Accuracy Dr. Robert Schmaranz – Austria – Session 3 – Paper 0570

  7. Minimal Machine Configuration • Number of additional machines • Varying operating modes versus • Number of machines in frequency control mode Dr. Robert Schmaranz – Austria – Session 3 – Paper 0570

  8. CONCLUSION • Accurate representation of real conditions • Main stability parameters for grid restoration • Detecting source of low-frequency oscillations • Minimal machine configuration - two machines in frequency control mode necessary - maintenance planning • Optimization of the grid restoration plan Dr. Robert Schmaranz – Austria – Session 3 – Paper 0570

  9. Dr. Robert Schmaranz – Austria – Session 3 – Paper 0570