220 likes | 311 Views
345kV Lines. C ompetitive R enewable E nergy Z ones. Protection & Control Issues -. NERC Press Release on April 24, 2009.
E N D
345kV Lines Competitive Renewable Energy Zones Protection & Control Issues -
NERC Press Release on April 24, 2009 “ Misoperations of system protection and control systems have been a leading cause of bulk power system disturbance in North America for a number of years, causing nearly 45% of category two and higher disturbances in 2007 ” -NERC
NERC Standards, Papers, Reports etc. • PRC-001-01: System Protection Coordination • PRC-004-01: Analysis and Mitigation of T and G Protection System • Reliability Paper: Protection System Reliability - Redundancy • Special Report: Accommodating High Levels of Variable Generation • And more …..
Can backup protection trip within 18 cycles ? Can breaker failure prot. trip within 9 cycles ? Wind farm LVRT curve from FERC 661A and PRC-024-1 0.65pu 18 cycles 0.45pu 9 cycles
Which should be used for CREZ lines ? Transmission Line High-Speed Protection High-Speed Line Protection: Communication-based protection scheme that can cover 100% line and trip in 1-2 cycles • Power line carrier-based schemes - DCB or POTT • Optical fiber-based current differential scheme (87L)
Z1 Z2/3 Z2/3 Z1 Power Line Carrier (PLC) - Based Schemes • Utilizing power line for communication. Consist of wave traps, coupling capacitors, line tuners, transmitters, receivers, etc. • Two prevailing PLC-based schemes: • Directional Comparison Blocking Scheme (DCB) • Permissive Overreach Transfer Trip (POTT) • Dependent upon distance (21)and directional (67) elements 21 21 PLC Channel
I_Local I_Remote Line Differential Protection (87L) • Based on digital communication channels such as optical fibers, SONET network, etc. • Compare current flow in & out line terminals • Easy to discriminate internal & external faults • High dependability – instantaneous trip for all internal faults • High security – no operation for external faults 87L 87L
PLC Schemes vs. 87L : Mutually Coupled Lines • Many CREZ 345kV lines are double circuits in long distance • Zero sequence mutual coupling effects 21G / 67G • 21G may overreach or underreach • Wrong direction from 67G due to zero seq. voltage reversal • Mis-operations occur often from DCB or POTT due to communication errors • 87L is not affected by mutual coupling
PLC Schemes vs. 87L: Current Reversal • Cause: one end tripped prior to the other end • 21 / 67 may give wrong directions • DCB or POTT may trip the healthy line due to scheme error • 87L is not affected by current reversal
PLC Schemes vs. 87L: Power Swings • Power system dynamic balance is disturbed after loss of critical generators or transmission lines • Swings could be damped by automatic & manual system controls, or aggravated towards out-of-step and blackout • 21P is susceptible to power swings • 87L is not affected by power swings
PLC Schemes vs. 87L: CCVT Transients • 21 and 67 protection are relying on voltage signals • CCVT transients may cause overreach, underreach, delayed trip or wrong direction • DCB or POTT may mis-operate for wrong direction • 87L is not affected by CCVT transients at all
RF ZSC&MOV ZAPPARENT PLC Schemes vs. 87L: Series-compensated Line • Protection Issues brought by series-compensation (SC) • Uncertainties caused by SC, MOV and bypass switch • Voltage inversion and current inversion effect 21/67 • 21 over-reach or under-reach • Sub-synchronous resonance effects phasor measurement • Other interactions with system components • DCB or POTT schemes have high probability of mis-operation for SC line and the adjacent linesas well • 87L is immune to all above issues except current inversion, that can be overcome by proper 87L settings K*Z0L (1-K)*Z0L remote bus X I0 Z0S2 Z0S1 V0 R A zero seq. network example
PLC Schemes vs. 87L: Weak Feed Applications • Wind farm is regarded as weak source or no source • 21/67 at weak terminal may not see the fault • DCB and POTT need special logics to handle weak feed applications, at a price of increasing the complexity of coordination and increasing possibility of mis-operation • Weak feed has no impact on 87L
PLC Schemes vs. 87L: High Impedance Faults • 21G cannot detect ground faults with high impedance • 67G has to compromisebetween the sensitivity and security against system unbalance under heavy load • 87L is sensitive to internal high impedance faults and not affected by load
PLC Schemes vs. 87L:Cross Country Faults, Evolving Faults • Cross Country Faults: two faults at the same time but different locations, one internal and one external • Evolving Faults: 1LG fault evolves to 2LG or 3LG fault • 21 or 67 could be confused, DCB or POTT may mis-trip for external fault or no-trip for internal fault • 87L can discriminate if there is internal fault, and not confused by evolving faults
Proposed 345kV Line Protection Schemes for CREZ Redundant protection system including: • Dual high speed primary protections • Redundant communication channels using optical fibers fibers fibers Self-healing SONET MUX MUX 87L 87L Direct fibers 87L 87L • Primary A: Line differential protection (87L) over direct fibers • Primary B: 87L over self-healing SONET network
OPGW for Every New CREZ 345kV Line • Optical Fiber Composite Overhead Ground Wire (OPGW) • Lower cost for new line construction • Expensive to put in afterwards (factor of 5-7) • Other benefits of optical fiber network utilizing OPGW • Wide Area Control • Synchronous phasor data stream • SCADA network communication • Disturbance monitoring system • Video surveillance system • Smart grid, voice communicationetc.
Breaker Failure Protection • Since over 20% generation may be from wind / sun, system stability has high requirements on backup protection • Wind farm LVRT curve implies fault clearance within 9 cycles even if breaker fails BF trip 86 trip DTT trip Fault cleared Fault Inception Breaker clearing Fault detector Local & remote Safety Margin Relay time breakers clearing time time drop out time t (cycles) General Total 13-14 2 3 1-2 2 5 Better breakers 1 2 < 1 2 3 Total 8-9 & better schemes
Summary • Redundancy is necessary for CREZ 345kV lines • 87L is superior to carrier-based schemes • Communication channels using optical fibers and self-healing SONET network • OPGW for every new CREZ 345kV line • Breaker failure and backup timing • Joint Development of CREZ Common approach / design specification on system protection and control
Discussion Questions? Comments?