An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Energy Analysis Topics • Base Case Supermarkets • Base Case Assumptions • Simulation Methods • Energy Efficiency Measures 1

  2. Supermarket Base Case • Three sizes • Small supermarket: 10,000 SF • Non 24-hour operation • Large supermarket: 61,000 SF • 24-hour operation • Average of last 50 Savings By Design stores • Big box food store: 150,000 SF • Non 24-hour operation • Includes large point-of-sale boxes 2

  3. Supermarket Base Case • Three condenser types • Air-cooled • Evap-cooled • Evap-cooled fluid cooler with water-cooled condensers • Two refrigeration system types • Central rack systems • Multiple distributed systems 3

  4. Base Case – Envelop, Lighting • Title-24 compliant building • Roof and wall insulation • Code required lighting power density • Minimum skylights and light level control • Not on small supermarket based on ceiling height • Schedules • Operating hours, occupancy, lighting 4

  5. Base Case – HVAC • System type: • Central air handler(s) on large supermarket • Packaged rooftop units on small, big box • Gas heat, no heat recovery 5

  6. Base Case – Display Fixtures • Line-ups taken from Savings By Design • Fixture assumptions *: • T8 lighting; certain lighted shelves • EC (DC) fan motors • No (or small) liquid-suction heat exchangers • Low-watt glass door heater option * Assumed features that would likely be used to meet the Federal appliance standards (kWh daily energy consumption) for DX remote display cases 6

  7. Base Case – Walk-ins • Federal WI Standard/Title 20 compliant • Insulation levels • Glass door heater wattage • EC fan motors on unit coolers • Loads based on widely used look-up tables • Unit coolers sized at typical 10 F approach 7

  8. Base CaseRefrigeration Assumptions • Partial floating head pressure control • 80°F SCT fixed setpoint (SBD basis) • Fan cycling (air) or two-speed (evap) • Fixed suction pressure control • No mechanical subcooling • 404A/507 refrigerant • Typical uneven parallel or multiple stages • Condenser specific efficiency (SBD basis) 8

  9. Analysis Methods • Primary Base Case models (preceding) • Other “Baseline” reference models for comparative and incremental analysis, or to compare alternative packages • Example: heat recovery incrementally evaluated vs. system combination with floating head pressure • Example: efficient DX combination vs. efficient secondary (glycol) combination 9

  10. Modeling Tool • Whole building hourly simulation • DOE 2.2R • Fixtures loads disaggregated, balance space interactions (fixture, HVAC, building, etc.) • Mass-flow/component based refrigeration system modeling, explicit control strategies • DOE2 modeling of building envelope, HVAC, lighting, skylights, etc. • Energy Plus • For aggregation of final results combinations 10

  11. Adjustments and Calibration • Fixture load breakdowns are estimated • Allowance for pressure drops & heat gains • De-rate condensers and evaporators • Actual applied performance vs. catalog • Effect of non steady-state operation • Results compared with actual operation(?) • Some field study and remote data collection • Need more, especially newer systems 11

  12. Questions? Base Case Assumptions Modeling 12

  13. Refrigeration Efficiency Measures Current High Priority Measures • Floating head pressure • Condenser variable speed control • Condenser specific efficiency • Floating suction pressure • Mechanical subcooling • Evaporator coil specific efficiency • Evaporator coil variable speed control • Display case LED lights • Liquid-suction heat exchangers • Night covers 13

  14. Refrigeration Efficiency Measures Other Medium or Lower Priority Measures • Condenser sizing (approach) • Evaporator sizing (approach) • Compressor staging/capacity control • Electronic expansion valves • Demand defrost • Piping insulation • DHW heat recovery • Glass doors on certain medium temperature fixtures Also see to “supermarket efficiency measure matrix.xls” 14

  15. Floating Head Pressure • Float to 70°F condensing temperature • Variable speed fan control • Or low power condenser, to be evaluated • Variable setpoint logic (ambient-following) • Details: • Design to avoid excessive ambient subcooling • All fans in unison (on air-cooled) 15

  16. Condenser Specific Efficiency • Set minimum specific efficiency values • Very large range of existing efficiencies • Savings By Design base case: • Air-cooled: 53 Btu/W at 10 F TD • Evap-cooled: 140 Btu/W at 100 SCT/70 WBT • Appears easy to justify removing least efficient models 16

  17. Condenser Specific Efficiency • However: • Condensers not rated to standards or certified • Current ratings make big assumptions: • Perfect UATD over full range of TDs and SCT • Power not published and not necessarily measured • Standards and certification: • High cost to industry and time required • Allows accurate comparison and competition • SBD experience indicates we can “start” 17

  18. Floating Suction Pressure • Require control logic to float suction • Adjust setpoint based on case or walk-in temperature requirements • Part of most SBD incentives for five years • Simple but requires labor to optimize • Integration: more complex with electronic circuit controls and/or variable speed evaporator fan control 18

  19. Mechanical Subcooling • Require mechanical subcooling • Require only on low temperature systems • Methods: • From medium temperature suction group • Using economized compressors (scroll, screw) • Cost neutral in most cases • At least with 404A/507 19

  20. Evaporator Coil Specific Efficiency • Set minimum specific efficiency levels (Evaporators, “coils”, unit coolers – same thing) • Very wide range of existing efficiencies • Applications and sizes: • Cooler, freezer • Low profile, medium profile • Indirect (glycol)?, often much higher power 20

  21. Evaporator Coil Specific Efficiency • However: • Coils not rated to standards or certified • Current ratings: • Probably significantly commercialized • Rating standards not adequate if they were used • Standards and certification: • High cost to industry and time required • Allows accurate comparison and competition • Appears feasible to start with basic rqmts 21

  22. Display Case LED Lights • Require LED lights in reach-ins and open display cases • Used in majority of recent SBD incentives for low temp reach-in cases • Economics and availability on open cases (canopy and shelf lights) to be determined 22

  23. Display Case Liquid-Suction HX • Require high performance liquid-suction heat exchangers on display cases • More than traditional small LSHX or soldering two pipes together • Choice of one HX per line-up (better performance) or one per display case (easier) • Large savings on LT • Benefits on MT close-approach and refrigerants with glide • Zero cost measure including capacity gain 23

  24. Walk-in Variable Speed Fan Control • Require variable speed fan control • Primary (first) temperature control • Integrate with other temperature control methods (electronic suction regulator, liquid solenoid, suction stop) and floating suction • Inherent variable speed with EC motors • Third power fan savings (~50% power at 75% airflow) • Lack of testing on commercial (DX) coils 24

  25. Walk-in Liquid-Suction HX • Require high performance liquid-suction heat exchangers on walk-ins • Same benefits as display cases • Benefits on refrigerants with glide • Better evaporator and cycle performance • Zero cost measure including capacity gain • Applies to DX systems, not indirect 25

  26. Investigate: Defrost Methods • Compare electric vs. hot gas defrost • Best practice electric defrost • Trunk piping, demand defrost (frost sensor) • Gas defrost • Some penalty on head pressure • Some advantage with higher SSTs • Provide energy analysis for evaluation with reduced leakage with electric defrost 26

  27. Investigate: Heat Recovery • Space heat recovery • Display cases remove heat, high annual heating requirement = big savings vs. past designs’ increased refrigerant charge and charge volatility • Many options and designs; not suitable for mandatory design requirements • Consider a small mandatory % of heat recovery with wide application flexibility • OSA/make-up; stock room; main AHU; etc. • Limit of ~15% additional charge 27

  28. Questions and Discussion Are measures missing? Should priorities change? Are there unidentified technical challenges? 28