1 / 60

Humidity Control Concept

ENERCOV SYSTEMS By YF Yap Enercov Co. Humidity Control Concept. ENERCOV (SUZHOU) Co Ltd Block B, B6-7, Suhong Ind Square, #81 Suhong West Road, Suzhou Industrial Park, JiangSu, China 215021. 2. ENERCOV (THAILAND) Co Ltd 52/1 Moo 13 Krungthep-Kreeta Road, Sapansung, Bangkok 10250

niveditha
Download Presentation

Humidity Control Concept

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. ENERCOV SYSTEMS By YF Yap Enercov Co. Humidity Control Concept

  2. ENERCOV (SUZHOU) Co Ltd • Block B, B6-7, Suhong Ind Square, • #81 Suhong West Road, • Suzhou Industrial Park, • JiangSu, China 215021 2. ENERCOV (THAILAND) Co Ltd 52/1 Moo 13 Krungthep-Kreeta Road, Sapansung, Bangkok 10250 Thailand Humidity Control Concept 3. ENERCOV (SINGAPORE) Co Ltd 80 Genting Lane #06-02, Genting Block, Ruby Industrial Complex, Singapore 349565

  3. We are TEMPERATURE , HUMIDITY & CONTROLS SPECIALISTS Humidity Control Concept

  4. Presentation Details • Company Policies • Desiccant Application • Enercov Application • Enercov’s Control System • Enercov’s Components • Proposals to NTU • Job References • Conclusion • Questions & Answers Humidity Control Concept

  5. Company Policy • Assist our customers to reach the best • solution for your needs. • Design your unit. • Use Good Quality Components. • Assemble and Start Up. • Provide Good After Sales Service. • Customer Satisfaction. Humidity Control Concept

  6. Desiccant Application Humidity Control Concept

  7. Desiccant Wheel Humidified Exhaust Air Humidity Control Concept Outside Air -------------------------------------------------- Dehumidified Air into CleanRoom Humidified Room Air

  8. Desiccant • Advantages • It can be used for very low • Room Dew Point Temp < 4 deg C • It can be used to achieve RH < 10% • Disadvantages • High Power Consumption due to Heating • Element. • Steps control and not analog. • High Maintenance Cost. Need to change • filter and Desiccant. • Loose Desiccant can contaminate the supply air . • 5. Need big floor space. Humidity Control Concept

  9. ANNUAL SAVINGS Humidity Control Concept

  10. ENERCOV means ENERGY RECOVERY Humidity Control Concept

  11. DX Coil Evaporator Coil Humidity Control Concept

  12. ENERCOV SYSTEM Evaporator Coil Condenser Coil Chilled Water Coil Humidity Control Concept Semi Hermetic Compressor

  13. Refrigeration Cycle Diagram Humidity Control Concept

  14. Psychometric Explaination Outdoor Condition Cooling Humidity Control Concept Heating Room Condition

  15. DX Coils • Advantages • Uses Energy Recovery. Very little energy wasted. • VSD control. Analog Control. • Most cost effective to control RH above 30%. • Low Maintenance Cost. Wash the coil with water. • No contamination to supply air due to no direct • contact media. • 6. DX coils is build into the AHU. Need less space. • Disadvantages • Limitations to control RH below 30% RH due to • minimum suction gas temp of 3 deg C. Humidity Control Concept

  16. ITS SOUND SIMPLE BUT ALL THIS THINGS IS NOT COMPLETE WITHOUT TOTAL CONTROL Humidity Control Concept

  17. Conventional Air Conditioner & Desiccant Control • Room RH Sensor Activate when RH above 55%. • Signal send to DDC. • Activate to ON the Desiccant Unit. 3 stages heater • in Desiccant Unit fully ON. • RH of Room Drops to 50%. Then , 1 stage heater OFF. • Once RH drops below 45% , 3 stages heater OFF. • Once RH above 55% , 3 stages heater ON again. • This system uses STEP CONTROL and NOT • ANALOG CONTROL. • MOST IMPORTANTLY Control DEHUMI- • DIFICATION & COOLING SEPARATELY. Humidity Control Concept

  18. Conventional Air Conditioner Humidity Control Concept Biosafety Laboratory Concept

  19. RESULTS WITH ENERCOV SYSTEM Humidity Control Concept Humidity Control Concept

  20. RESULTS WITH ENERCOV SYSTEM Humidity Control Concept

  21. Before we can start to CONTROL We must know What are the CONTROL MODE Humidity Control Concept

  22. Process of the Air Humidity Control Concept Humidification Cooling Heating Dehumidification

  23. ENERCOV SYSTEM CONTROL Dehumidification, Cooling, Heating & Humidification to keep Temperature and Relative Humidity of the ROOM as CONSTANT as POSSIBLE. Humidity Control Concept

  24. ENERCOV Humidity Total Control Concept DX COILS Hot Gas Reheat, Hot Gas Bypass, VSD & DDC Controls System Humidity Control Concept

  25. High Quality Components Used • Air Handling Unit – Carrier, Robatherm, etc • Humidity Control Unit • Carlyle Compressor • CAREL Controller, Panel & Sensors • CAREL Steam Humidifier • Others Humidity Control Concept

  26. CARRIER AHU Humidity Control Concept

  27. HUMIDITY CONTROL UNIT Humidity Control Concept

  28. CAREL CONTROLLER, PANEL & SENSORS DDC PROGRAMMABLE 4 x 20 LCD Display Humidity Control Concept Temperature & Humidity Sensor Pco1 Controller

  29. CAREL STEAM HUMIDIFIER Humidity Control Concept

  30. We would like to Proposed to the TOP MANAGEMENT of NANYANG TECHNOLOGICAL UNIVERSITY ( NTU ) Humidity Control Concept

  31. PROPOSE ENERCOV SYSTEM Enercov Unit AHU AND

  32. ENERCOV’S CONTROL CONTROLLER, PANEL & SENSORS DDC PROGRAMMABLE 4 x 20 LCD Display Humidity Control Concept Temperature & Humidity Sensor Pco1 Controller

  33. SCHEMATIC DIAGRAM Humidity Control Concept

  34. ENERCOV CONTROL ITEMS • Two sets of Sensors Temperature & Humidity • One at Supply Air and One in the Room. • Solenoid Valve to Control The Reheat Coil. • Control Valve to Control Chilled Water Coil. • Solenoid Valve to Control the HotGassBypass. • Temp Sensor for Air Off Chilled Water Coil. • Temp Sensor for Air Off DX Cooling Coil. • Others Humidity Control Concept

  35. Control Points Schedule Humidity Control Concept

  36. Psychometric Process ENERCOV DX Cooling Coil ( 20kW Only ) Humidity Control Concept MUNTER’S Dehumid ( 98 kW) ENERCOV DX Heating Coil

  37. ENERCOV FLEXIBILITY DX Cooling Coil Total Cooling 31.58 kW Sensible Heat Rat 0.51 Sensible Heat 16.1 kW Latent Heat 15.5 kW Chilled Water Coil 48.4 kW 0.94 45.5kW 2.9kW Humidity Control Concept Range for Sensible Heat 9.1 kW to 61.6 kW Range for Latent Heat 0.58 kW to 18.4 kW

  38. ENERCOV SYSTEM CONTROL Dehumidification, Cooling, & Heating to keep Temperature and Relative Humidity of the ROOM as CONSTANT as POSSIBLE. Humidity Control Concept

  39. RESULTS WITH ENERCOV SYSTEM Humidity Control Concept Humidity Control Concept

  40. TOTAL CONTROL TEMPERATURE 22 +/-1 deg Celcius andRELATIVE HUMIDITY 40%-50% RH Humidity Control Concept

  41. JOB REFERENCES Humidity Control Concept

  42. JOB REFERENCES • Takeda Lace Co Ltd Bangkok. • Biological Safety Lab Level 3 in Ministry of • Health Thailand. • NSM Factory Co Ltd. • UL & CE Standard Testing Room Bangkok. • Ministry of Medicine Thailand Vaccine • Production Class 10000. Humidity Control Concept

  43. Takeda Lace Co Ltd • Temperature 24 deg C +/- 1 deg C • Relative Humidity 65% +/- 2% RH • DDC micro processor based control system • Steam Humidifier capacity control • Cooling / Heating / Dehumidification / • Hum are controlled in proportional linearity. Humidity Control Concept

  44. Takeda Lace Co Ltd Humidity Control Concept

  45. 2. Biological Lab Safety 3 • Ministry of Health Thailand • Temperature 23 deg C +/- 1 deg C • Relative Humidity 50% +/- 5% RH • Room Pressure Clean Room - 20 Pa • Room Pressure Clean Room + 20 Pa • 100% Outdoor Air Intake • DDC micro processor based control system • Hot gas bypass system Humidity Control Concept

  46. Biological Lab Safety 3 Ministry of Health Thailand Humidity Control Concept

  47. Biological Lab Safety 3 Ministry of Health Thailand Humidity Control Concept

  48. 3. NSM Factory Co Ltd • Temperature 27 deg C +/- 1 deg C • Relative Humidity < 40% RH • Double series evaporator coils system • Hot gas by pass system • DDC micro processor based control system Humidity Control Concept