1 / 23

Harmonics Problems in Distribution Systems Case Study AEP Texas Central Company

Harmonics Problems in Distribution Systems Case Study AEP Texas Central Company Scott Lee, Reliability Engineer. What’s wrong with my lights?!. SYMPTOMS OF A PROBLEM. Residential customer calls complaining of problems with electronics: TV, thermostat – AC, motors making strange noises

oistin
Download Presentation

Harmonics Problems in Distribution Systems Case Study AEP Texas Central Company

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Harmonics Problems in Distribution Systems Case Study AEPTexas Central Company Scott Lee, Reliability Engineer

  2. What’s wrong with my lights?!

  3. SYMPTOMS OF A PROBLEM Residential customer calls complaining of problems with electronics: TV, thermostat – AC, motors making strange noises Serviceman and Operations Tech troubleshoot and have transformer replaced because of unusual humming and arcing sounds from coil New transformer makes the same sound, customer still has problems – call the engineer Tech goes to new pipe plant down the road and finds 2000kVA pad transformer making same noise

  4. THE SOURCE • Houston based company built a pipe coating and storage plant in George West to better serve the Eagle Ford Shale area • Two 1000kW induction furnaces to heat and coat 2 inch to 24 inch diameter casing with fusion bonded epoxy • Two solid state 6-pulse rectifiers and step up transformers provide variable frequency 4kV power to induction coils For more info . . . see texisle.com and ajaxtocco.com

  5. INSTALLATION • Previously during the plant planning stages, AEP provided system, line, and transformer impedances to drive manufacturer for design. Distance and PQ were discussed. • 3 miles of distribution feeder was upgraded with 477MCM aluminum, with a total length of 6.4 miles • Drive manufacturer wanted two 1500kVA or one 3000kVA transformer, we supplied one 2000kVA. They were also very insistent on our transformer meeting their specs. Actual peak is 1380kW. • A 1000kVA pad was installed for other plant power that peaks at 600kW • AEP standard for three phase padmounts is wye-wye • IEEE-519 requirements were not discussed, customer did not tell us the inverter was a 6-pulse drive

  6. Plant * Residence  Feeder upgraded to 477, 6.4 circuits miles from sub to customer George West Sub 138/12kV 9.4 MVA

  7. AjaXtocco, pacer-2 drive • 1000kW • 500 Hz • Variable Frequency • 6-pulse rectifier • No filtering • Water cooled

  8. Induction heating line

  9. Fusion bonded Expoxy coating

  10. PMI recorders installed at plant transformer and at residential customer. Set to record harmonics and capture waveforms. Voltage THD at pipe plant on secodary, 14% Voltage THD at residential secondary, 5.1% MEASUREMENTS PMI stands for Power Monitors Incorporated, see www.powermonitors.com, iVs-3 and Eagle 440

  11. Unfiltered, running at 1550kVA 5th 2000 kVA Padmount 6-Pulse Drive 7th 12.4% THD-Voltage 11th 13th 3rd 5th 7th 23.4% THD-Amps 11th

  12. Unfiltered, 2000kVA Padmount, 6-Pulse Drive 12.4% THD-V 23.4% THD-A

  13. THE FIX Met with pipe company and drive manufacturer to request they install filtering and comply with IEEE-519 (5% THD limit on voltage) Move other distribution customers in area to another feeder Drive manufacturers said they would install passive filters (reactors and capacitors) but parts would have a 14 week lead time plus engineering and installation time I countered to pipe company that this was unacceptable, and offered three filter manufacturers with on the shelf parts that offered active filtering and engineering support. Recomended MTE Matrix Pure Sine active filters, Schaffner EMC ECOsine active filters, and TCI H5 active filters.

  14. There was a debate over passive versus active, but after some research, I pressed the customer to go with active filters because of the varying load and the possibility of hitting resonance with a passive unit, also recommend a 5% line reactor which is standard for 6 pulse drives The customer chose a vendor, and we had several phone conferences about what to install, and what would be acceptable with AEP The vendor chosen was Schaffner EMC and the ECOsine FN3420 filter with additional 5% reactors THE FIX cont. For more info . . . List location or contact for specification (or other related documents)

  15. Active filter • Schaffner EMC ECOsine filter injects up to 300 amps of current • Compensates for harmonic currents • Compensates for reactive current • Can choose percentage of overall current dedicated to each harmonic • Two installed with 5% reactor ahead of each drive

  16. Measurement after filter install • Before at 1850 amps of load: • Voltage THD 12.6% Current THD 23% • After at 2150 amps of load: • Voltage THD 5.5% Current THD 8.8% • After at 1320 amps of load: • Voltage THD 7% Current THD 5% • Adjacent Transformer Voltage THD 3.5%

  17. Total Load 1800 amps HarmonicAmpsAmps with Filter 5th 427 49 7th 225 60 11th 113 52 13th 60 59 THD-V from 12.2% to 8.1% Harmonic currents before/after

  18. Testing, filter on and off --------- Filter off 2300A rms 5.9% THD-V 9.6% THD-A 8.4% THD-V 24.2% THD-A Neutral volts and amps

  19. Waveforms showing commutation notching 6.9% THD-voltage 5% THD-current 1300 amps

  20. UG Residence, one mile from pipe plant, plant running at 7% THD-V 3.5% THD-V 3rd, 7th, and 5th V I

  21. Still progress to be made • Not below 5% THD on voltage at meter • Filtering has done all it can do • Work with drive manufacturer to control commutation notching using saturating reactors on SCRs to speed gate closing

  22. IN RETROSPECT • Should have required drive manufacturer to meet IEEE 519 standard • Get a written proposal from drive manufacturer on how they will meet the standard • Use delta primary transformer to trap Triplen harmonics, this is 2.7% of total • Recommend active filtering • Recommend 12 pulse drives or technology to reduce commutation notching

  23. Questions

More Related