50% Fill is Full!

50% Fill is Full!. NEC 50% FILL is FULL! Lets Do the Math EXAMPLE: 2x6 (54-150) Cablofil = 12 sq in of area Per NEC 50% rule 12/2 = 6 sq in space for cables. Cat 5e cable = .21 in (DIA) = 3.14(.21) 2 /4= .04 sq in 6 sq in / .04 sq in = 150 cables

owen
Download Presentation

50% Fill is Full!

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. 50% Fill is Full! • NEC 50% FILL is FULL! • Lets Do the Math • EXAMPLE: • 2x6 (54-150) Cablofil = 12 sq in of area • Per NEC 50% rule 12/2 = 6 sq in space for cables. • Cat 5e cable = .21 in (DIA) = 3.14(.21)2/4= .04 sq in • 6 sq in / .04 sq in = 150 cables • So what does 150 cat 5e cables look like in a 2x 6 (54-150) wire mesh tray?

  2. BICSI 2006 • 50% Fill is FULL -3 bundles of QTY 50 cat 5e cables (tightly bundled)