1 / 14

Slobodan Lubura, Milomir Šoja, Srđan Lale, Marko Ikić

Experimental verification of single-phase PLL with novel two-phase generator for grid-connected converters. Slobodan Lubura, Milomir Šoja, Srđan Lale, Marko Ikić The Faculty of Electrical Engineering, University East Sarajevo, East Sarajevo, Bosnia and Herzegovina. Introduction.

phyre
Download Presentation

Slobodan Lubura, Milomir Šoja, Srđan Lale, Marko Ikić

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Experimental verification of single-phase PLL with novel two-phase generator for grid-connected converters Slobodan Lubura, Milomir Šoja, Srđan Lale, Marko Ikić The Faculty of Electrical Engineering, University East Sarajevo, East Sarajevo, Bosnia and Herzegovina

  2. Introduction The general structure of single-phase PLL based on SRF theory

  3. Novel two-phase generator with noise and DC offset rejection The new two-phase generator with DC offset rejection realized in Simulink environment

  4. Novel two-phase generator with noise and DC offset rejection • Proposed structure of novel two-phase generator can be presented with following transfer functions: • Both (1) and (2) represent transfer functions of band-pass filters.

  5. Experimental results of proposed PLL Block-diagram of proposed PLL topology realized in Simulink using Real Time Windows Target library

  6. Experimental results of proposed PLL – continuous model of PLL The response of two-phase generator on grid voltage with noise

  7. Experimental results of proposed PLL – continuous model of PLL a) b) • Input grid voltage with 30% DC offset and estimated grid amplitude, without control loop for DC offset rejection • Input grid voltage with 30% DC offset and estimated grid frequency, without control loop for DC offset rejection

  8. Experimental results of proposed PLL – continuous model of PLL a) b) • Input grid voltage with 30% DC offset and estimated grid amplitude, with control loop for DC offset rejection • Input grid voltage with 30% DC offset and estimated grid frequency, with control loop for DC offset rejection

  9. Experimental results of proposed PLL – continuous model of PLL Estimated grid frequency (top) and amplitude (bottom) forki = 10, 100 and 500 (robustness against step changes of grid frequency and amplitude)

  10. Experimental results of proposed PLL – continuous model of PLL Input grid voltage with 30% DC offset and generated reference voltage.

  11. Experimental results of proposed PLL – discrete model of PLL • Discretization of proposed PLL was performed in two ways: Tustin approximation Schneider approximation

  12. Experimental results of proposed PLL – discrete model of PLL Ts=50μs Estimated grid amplitude for two discrete models of PLL (step changes of grid parameters)

  13. Experimental results of proposed PLL – discrete model of PLL Ts=50μs Estimated grid frequency for two discrete models of PLL (step changes of grid parameters)

  14. Conclusion • The results show that proposed PLL (bothcontinual and discrete) can solveimportant issues of presence of DC offset and noise inmeasured values of grid voltage. • Proposed PLL can be used for both, grid-connected systems (e.g.Photovoltaic and Wind turbines) and power conditionequipment (uninterruptible power supply (UPS), activefilters) which rely on PLL based synchronization. • The further work should be implementation of proposed PLL topology on digital platform (using dsPIC).

More Related