John Hill. Technical Training. john.hill@goodmanmfg.com 713-861-2500 Ext.907. TECHNICAL SUPPORT. 888-593-9988. NAECA. National Appliance Energy Conservation Act January 23, 2006 Minimum SEER – 13 Previously – 10 Minimum HSPF 7.7 Previously – 6.8. Montreal Protocol.

quito
Download Presentation

John Hill

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. John Hill Technical Training john.hill@goodmanmfg.com 713-861-2500 Ext.907

  2. TECHNICAL SUPPORT 888-593-9988

  3. NAECA • National Appliance Energy Conservation Act • January 23, 2006 • Minimum SEER – 13 • Previously – 10 • Minimum HSPF 7.7 • Previously – 6.8

  4. Montreal Protocol • Montreal Protocol on Substances that Deplete the Ozone Layer • No Production of R-22 Equipment in 2010

  5. Montreal Protocol • CFC Phase Out (R-12) • 1991 – 100% • 1996 – 0% • HCFC Phase Out (R-22) • 1995 – 100% • 2020 – 0%

  6. Service Valves • Service valves located at 90o angle. • Unobstructed access to gauge ports. • More room to maneuver tools.

  7. Access to the Control/Electrical Panel • Two screws to remove the outside cover • Removable Panel • Contactor with lug connectors • Ground with lug connector • Room for field installed accessories

  8. Super-heat and Sub-cooling charts • The super-heat and sub-cooling charts will be posted on the back side of the control door.

  9. Access to the Condenser Coil • The 2006 units will come with 4 independent louver panels. They are easy to remove for quick accessibility to the condenser coil.

  10. 2006 Product Line

  11. 2006 Product Line

  12. 2006 Product Line

  13. INSTALLATION TIPS • NO CAPILLARY TUBE EVAPORATORS • LINE SETS WITH ¼ LIQUID 5/8 SUCTION MUST BE LESS THAN 25 FT. IN LENGTH • EVAPORATORS WITH FLOWRATORS CHANGED TO THE PISTON SUPPLIED WITH NEW CONDENSORS • WHEN CHARGING SYSTEM USE SUPERHEAT OR SUBCOOLING METHOD • HEAD PRESSURE WILL BE LOWER THAN 10 SEER SYSTEM • HEAT PUMPS REQUIRE COMPLETE SYSTEM CHANGE OUT

  14. INSTALLATION TIPS USING A 13 SEER CONDENSER WITH A 10 SEER OR LESS EVAPORATOR MAY DEGRADE CAPACITY BY 6% TO 10%. IN APPLICATIONS WHERE CAPACITY IS MARGINAL, IT MAY BE NECESSARY TO INCREASE THE CAPACITY OF THE CONDENSOR BY ½ TON. IT IS IMPORTANT THAT WHEN DOING THIS , THAT THE ELECTRICAL SERVICE IS ADEQUATE FOR THE LARGER CONDENSOR. IT MAY ALSO BE NECESSARY TO INCREASE THE SIZE OF THE REFRIGERATION LINE SET.

  15. R-22 Phase-Out Timeline % $20/lb 100 R-22 Cost Montreal Protocol/US Phase-Out 65% % 1996 CAP $10/lb 50 35% EU Phase-Out 10% $2/lb 0 1999 2004 2010 2015 2020 No New Equip. US No New Equip. EU

  16. Why R-410a? • R-22 Alternatives • R-134a • R-407c • R-410a • R-417b • Propane • Carbon Dioxide

  17. US New Refrigerant Transitions R-134A Screw Chillers60- 500 Ton R-22 R-410A R-407C Commercial5 to 100 Ton R-22 R-410A R-410A Residential1.5 to 5 Ton R-22 1990 1995 2000 2005 2010

  18. Back Seat Service Valves • All “R” series models equipped with back seating service valves • RVP February 2003

  19. R-410 Facts • Ozone friendly- No Chlorine • Replacement for R-22, NOT a drop in! • Higher Pressure Range-50 to 75% higher than R-22 • Requires Special Lubricants

  20. Components that needed Redesigned for R410A • Compressor • Condenser coil • Filter Drier • Expansion device • Evaporator • Pressure switches

  21. Compressors • Copeland ZRS and ZPS Compressors • We will get further into these later in the program

  22. Pressure Switches • Pressure Switches have to be at higher settings • Low Pressure R410a=50psi • High Pressure R410a=610psi

  23. Line Sets Line Sets New Line Sets are always recommended, but required if: • The previous system had a compressor burn out. • The existing line set has oil return traps. • The existing line set has been open to the atmosphere for an extended time. • The existing line set is larger than or smaller than the recommended line size for the Amana R-410a system. • The existing line set is damaged, corroded, or shows signs of abrasion/fatigue.

  24. Special Tools Required • Differences in Saturation Pressures between R22 and R410a affects many of the tools the Technician must use when Charging and Servicing an R410A system. • Some of the tools used on R22 systems may be unacceptable for use on R410a systems.

  25. Manifold Gauge Set • Standard Gauges and hoses cannot be used safely with R410a. • The High Side gauge should have a range of zero to 800psi. • The Low Side gauge should have a range from 30 inches vacuum to 250psi. • The Low Side gauge should also have a 500psi retardation feature. This slows the movement of the gauge needle at higher pressures.

  26. Manifold Gauge Set

  27. Refrigerant Hoses • The 600psi rating of standard hoses is NOT adequate for R410a. • Hoses need to be rated for a 800psi working pressure, with a 4000psi bursting rating. • 5 to 1 safety margin is necessary to prevent dangerous hose ruptures.

  28. Vacuum Pumps • Pumps used with CFC and HCFC charged systems may also be used on R410a systems as long as the pump is capable of attaining a vacuum of level of at least 250 Microns.

  29. Leak Detectors • Leak detectors should be checked to see that they are designed to properly detect R410a. • The detector should have adjustable sensitivity to allow leaks to be pinpointed in areas where background vapor might cause false readings.

  30. Two Stage Compressor • Features: • High Efficiency • Quiet Operation • Scroll Technology • No Shut-Down to Shift Capacity

  31. Copeland Scroll™ UltraTech Two-Stage Modulation Scheme Bypass Ports Closed Bypass Ports Open 100% Capacity 67% Capacity

  32. R-410a • It’s a Blended Refrigerant. • 50% R-32 and 50% R-125. • This blend is a near-azeotrope, not a true azeotrope like R-502. • A true azeotrope is a mixture that maintains its composition through both the liquid and vapor phase.

  33. R-410a • For a near-azeotrope, the individual refrigerants evaporate or condense at different temperatures. • The differences between these boiling points with mixed refrigerants is called “ TEMPERATURE GLIDE”

  34. R-410a • When temperature glide is high the refrigerants can separate during evaporation or condensation. • This changes the composition of the resulting vapor and liquid. • This separation is called: “FRACTIONATION”

  35. R-410a • Fractionation is very low. • R410a does not significantly separate in the system and the composition of the refrigerant has very minor changes if a leak occurs. • But the fact that some fractionation occurs, means that charging techniques must be adjusted. • The temperature glide of R410a is very low, thus it acts very much like a single refrigerant.

  36. R-410a • Another significant difference between R410a and R22 is its saturation pressure range. • R410a has a higher pressure range curve than R22. • Remember, R410a is a near azeotrope that is subject to some fractionation. At any specific temperature it has a higher vapor pressure when saturated.

  37. Cylinders • Most R410a cylinders have an internal dip tube which allows the feeding of liquid when the cylinder is in an upright position. They must be inverted for for vapor flow. • Color is rose(pink). • The cylinder has to have minimum cylinder pressure requirement of 400 psig rating (DOT 4B400 or DOT 4BW400)

  38. Lubrication • The chemistry of R410a makes it incompatible with mineral based lubricants. • Mineral oils typically used with R22 has relativity low Miscibility with with R410a. • Miscibility is the ability of an oil to dissolve uniformly in refrigerant in either the liquid or vapor state.

  39. Lubrication • The preferred lubricants are the Polyolester or ester based oils. • Commonly known as POE oils. • POE oils are miscible with with any mineral oil traces that might be in the system. • While miscible, it is very important to remove as much mineral oil, particulates, and moisture from existing line sets as possible.

  40. Lubrication • The POE oils are more Hygroscopic than mineral oils. • This means that they absorb moisture very rapidly. • Exposure to the atmosphere must be limited. • The oil will break down into acid and alcohol • Keep the system closed

  41. Lubrication • Any moisture absorbed by into POE oils cannot be removed with a vacuum pump-Only a new drier will work! • Break a recovery vacuum with Nitrogen! • Keep all systems closed until any component replacements are ready for installation.

  42. Brazing • Should be using at least 2% silver alloy • Always wear glasses and gloves. • Always purge with nitrogen when brazing. • Protect the service valves with wet rags or heat sink material. • Scale will get you with POE oils.

  43. Evacuation

  44. Evacuation

  45. Recovery • Yes, you still have to recover the refrigerant. • R410a does not readily biodegrade, care should be taken to avoid any releases to the environment. • The recovery machines used for R410a must be designed to prevent cross contamination between oils and refrigerants.. • Use machines certified for use with R410a.

  46. Recovery • Preferred type is an oil-less compressor model with a pump down feature for removal of all refrigerant from the machine after each use. • If an oil bearing compressor is used, the machine should be restricted to R410a refrigerant. The machine must use ester based oil.

  47. Charging • Charge through the suction side of the system. • Use a commercial-type metering device in manifold hose to allow liquid to vaporize. • Follow your typical sub-cooling and superheat procedures to arrive at the correct charge.

  48. Charging Single Stage