Backflow Prevention devices for carbonators and industrial chillers

Backflow Prevention devices for carbonators and industrial chillers. June M. Weintraub, ScD, REHS Environmental Health Branch May 2019. http://www.jpchemtech.in/Boiler-Chemicals.php. Carbonator + Copper Pipe = Health Hazard.

raphaelr
Download Presentation

Backflow Prevention devices for carbonators and industrial chillers

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Backflow Prevention devices for carbonators and industrial chillers June M. Weintraub, ScD, REHS Environmental Health Branch May 2019 http://www.jpchemtech.in/Boiler-Chemicals.php

  2. Carbonator + Copper Pipe = Health Hazard • When CO₂ is mixed with water, carbonic acid (a weak acid) is formed. CO2+ H2O  →  H2CO3 • Many water supply lines are made from copper.If CO₂ backs up into a copper water linecarbonic acid will dissolve some of the copper.  Cu(OH)2 + H2CO3 → 2 H2O + CuCO3 • Copper Carbonate can cause illness – vomiting, nausea, easily mistaken for food poisoning

  3. Industrial Chillers Usually Use Chemicals • Industrial chiller and boiler chemicals are widely used to ensure proper functioning and equipment life • Backpressure or backsiphonage conditions can occur, introducing hazardous chemicals into the potable water supply and risk of illness for those who might consume contaminated water • Plumbing Code allows a DC device if a chiller or boiler is not planning to use chemicals • This rarely happens -- even if an installation “thinks” they won’t be using chemicals in their boiler/chiller, there is always the possibility that chemicals will be used at some later point • Therefore it is good practice to protect as though all industrial chillers and boilers are planning to use chemicals and require an RP or air gap

  4. Uniform Plumbing Code / CPC Requirements in Table 603.2

  5. ASSE 1022 Backflow Preventer Image credit: https://www.andersonbrass.com/back-flow-products