Managing Harmonics –A case studyJim BridgemanPFC Engineering
Introduction • Basics of harmonic resonance • Effects of harmonic resonance • Typical solutions applied to resonant Power Systems • Harmonic magnification case study
Effects of Harmonic Resonance • Increased voltage distortion, possibly resulting in equipment malfunction • Loss of transformer output due to increased heating • Interference with communication systems • Premature failure of motors • Premature failure of power factor correction capacitors
Typical Solutions Applied to Resonant Power Systems • Detuning reactors • Partial harmonic filtration • Full harmonic filtration
Typical Solutions Applied to Resonant Power Systems – Detuning Reactors
Typical Solutions Applied to Resonant Power Systems – Partial Filtration
Typical Solutions Applied to Resonant Power Systems – Full Filtration
Case Study – Harmonic Magnification at a Car Battery Factory • Large 5th harmonic magnification excited by 600 kVAr of capacitors • Costly installation of detuning reactors appeared to be the only solution • A more cost effective solution involving reconfiguration of the existing plant was found
Case Study – Initial System Configuration (Transformer T1) • Plain capacitors • All non-linear loading • No load damping
Case Study – Initial System Configuration (Transformer T2) • Nearly all linear loading • Significant load damping
Case Study – Reasons for severity of 5th harmonic voltage magnification • High base level of harmonics due to all non-linear load being connected to this supply • Connection of plain capacitor banks • Total lack of harmonic damping from linear loading
Case Study – Proposed Solution to Problem of Harmonic Magnification
Case Study – Improvement in Harmonic Performance with Re-configured Load
Conclusions • Harmonic resonance can be caused by connection of Power Factor Correction equipment • Various methods of avoiding this scenario involving blocking / filtration systems are available • Careful examination of the problem and more appropriate load configuration can provide more cost effective solution to the problem Questions?