30 likes | 173 Views
Drummy Spalled Spalled & drummy Crack Cold Joint Panel Joint. SR3 Cooler, Pier No 2 Photos. Papworth’s Pty Ltd Narngulu Synthetic Rutile Plant January 2004 Inspection By F.Papworth Lyall Murphy. N. Pier 1. Pier 2. Figure 41. Photo “Cooler P2-11”. Photo “Cooler P2-08”.
E N D
Drummy Spalled Spalled & drummy Crack Cold Joint Panel Joint SR3 Cooler, Pier No 2 Photos Papworth’s Pty Ltd Narngulu Synthetic Rutile Plant January 2004 Inspection By F.Papworth Lyall Murphy N Pier 1 Pier 2 Figure 41 Photo “Cooler P2-11” Photo “Cooler P2-08” Photo “Cooler P2-01” Photo “Cooler P2-10” Photo “Cooler P2-02” Photo “Cooler P2-09” Photo “Cooler P2-07” Photo “Cooler P2-13” Photo “Cooler P2-12” Photo “Cooler P2-03” Photo “Cooler P2-06” Photo “Cooler P2-04” Photo “Cooler P2-05”
E N F Q G H I J K L M N O P A B C D ALF/S3 ALF/S2 x x x x x x x x x x x x x Acid Leach Foundation Detail 1 in Area A Cover & Samples Cover in mm, as measured with cover meter 75mm diameter grinding core cut Resistance for 4 probe Wenner method with probes at 50mm centres Papworth’s Pty Ltd Narngulu Synthetic Rutile Plant January 2004 Inspection By F.Papworth Lyall Murphy …. Figure 5 630mm 590mm Detail 1 = = = 41mm 41mm 41mm 42mm ALF/S4 200mm 1.29m 170mm 41mm 40mm 40mm 40mm Detail 1 40mm …. 41mm 40mm 39mm 160mm R=2520ohms Vertical 25mm Ø bar cover = 40mm Horizontal 12-15mm bar cover = 67mm Depth of Carbonation = 0mm