SCED Penalty Factor Resmi Surendran
Current Values • Maximum Shadow Price for Transmission Constraints • Base Case: $5,000/MW • Generic constraints : $5,000/MW • Post Contingency • 345 kV: $4,500/MW • 138 kV: $3,500/MW • 69 kV: $2,800/MW
Power Balance Penalty Curve • equivalent to having extra capacity for meeting power balance violation at • (+/-) 3001 $/MWh for violated MW from 0MW to 9999.999MW, and • (+/-) 5000$/MWh for violated MW from 10000MW to 99999.999MW
Constraints 1-May - 28-May • 9 violated constraints - 616 intervals • 15 binding constraints - 415 intervals
Violated Constraint 1 Contingency SSNDAUS5 overloading 345kV line 440_A @SNDSW 5/5/2010 5:15:28 PM High prices due to scarcity
Violated Constraint 2 Contingency DGBY_GS8overloading 138kV GT_MID90@MID 5/26 3:45 pm High prices due to not having enough energy offer curves
Violated Constraint 3 Contingency DGRSBNB5 overloading 1800@LENSW : 5/27 8:00 am
LFC Test • Time period of full nodal control 11:55 – 12:25 • Two constraints binding/violated during test • DGBY_GS8 - Garrott-Midtown 138 kV, • X_BI58T2 - Bellaire 345/138kV Xfrmr
SPP during LFC Test on May 20th • System was under full nodal control from 11:55 A.M. to 12:25 P.M. • Two constraints were binding/violated during test • Contingency loss of double circuit line from Green Bayou to Gable street and Hardy to Crocket overloading Garrott to Midtown 138 kV line • Contingency loss of one Bellaire 345/138kV Transformer overloading other Bellaire 345/138kV Transformer • Constraints were in Houston area causing price separation in Houston. • Negative prices were in non load buses causing the Houston Load Zone price to be nearly $40 higher than the Houston Hub price • For example for 5/20/2010 12:15 interval • Price ranged from $ 310.87 ( Resource Nodes @ WAP) to $ -104.18 (Resource Node @ BVE_CC1) • Houston Hub price was $-3.44 • Houston Load Zone price was $36.21
Need for Realistic Data • Not enough energy offer curve • Suspect or inconsistent telemetry Action plan • Submit EOC based on Zonal bids during the week of LFC testing. • Possible focused testing once a week.
West to North • Max SF = 0.14523 => Lambda – 4.61 • Min SF = -0.8077 => Lambda + 25.63
West to North For settlement interval 5/24/2010 20:15 to 5/24/2010 20:30
North to Houston • Max SF = 0.86985 => Lambda – 2.57 • Min SF = -0.08326 => Lambda – 0.25 • Only time period with only N-to-H • When also W-to-N, shadow prices are similar to W-to-N
North to Houston For settlement interval 5/21/2010 10:15 to 5/21/2010 10:30