70 likes | 207 Views
EL SCADA Components Rad Tests. EL SCADA components Radiation R esistance Tests Typical US/RE system components. EL SCADA Components Rad Tests. Typical US/RE installation: RTU: CLP500E EFACEC Advantech Diskless board Power Supply module, 48VDC Supply DAU, 48VDC Supply
E N D
EL SCADA Components Rad Tests EL SCADA components Radiation Resistance Tests Typical US/RE system components
EL SCADA Components Rad Tests • Typical US/RE installation: • RTU: CLP500E EFACEC • Advantech Diskless board • Power Supply module, 48VDC Supply • DAU, 48VDC Supply • CPU/Communication: MAP3200 Prometheus • Input MAP3020, Output MAP3050 • Analogues MAP3080 • IED,DIRIS Ap, 48VDC Supply (Low Voltage Switchboards) • Adapters, 24VDC Supply • ADAM 4520: RS232/RS485 • Switch MOXA EDS308 • ELECDAN Power Converter 48/24VDC • ELECDAN Pt100/10V Converter • ELECDAN Counter/10V Converter (Ackerman Battery Measurement) • Acquisition of Voltage Relay
EL SCADA Components Rad Tests • Monitoring: • Remote Desktop Connection to connect to RTU • CLP500 Version 5.1.0 managing the system • Daily Control execution in List Mode • Automatism (Fung function) • Return on Input board makes events & Alarm • Reaction in case of failure (SEE) • Remote Reboot • RTU level (if RDC & ping failure) • DAU level (if IEC-Down & Win 3200 failure) • 24VDC convertor (Switch, ADAM4520, ELECDAN convertors) • DIRIS module (if Communication or measurements lost)
Ethernet GPN Remote Desktop Connexion RR RTU CLP500E RR RR Switch SPHINX EDS308 Win3200/RS232 ADAM 4520 RS232/RS485 ELECDAN Converter 48/24VDC RR 870-5-104/TCP/IP Remote Reboot Jbus/RS485 DAU MAP3200 MAP3020/50/80 24VDC ELECDAN Counters RT ELECDAN Pt100 Power Supply 230/48VDC 6Amp 48VDC DIRIS Ap 230VAC
Ethernet GPN Remote Desktop Connexion RTU CLP500E RTU CLP500E RTU CLP500E Remote Reboot RR RR RR RR RR RR RR RR RR Converter 48/24VDC Converter 48/24VDC Converter 48/24VDC ADAM 4520 ADAM 4520 ADAM 4520 RR RR RR 870-5-104/TCP/IP 870-5-104/TCP/IP 870-5-104/TCP/IP Switch SPHINX EDS308 Switch SPHINX EDS308 Switch SPHINX EDS308 Win3200/RS232 Win3200/RS232 Win3200/RS232 DAU MAP3200 MAP3020/50/80 DAU MAP3200 MAP3020/50/80 DAU MAP3200 MAP3020/50/80 Jbus/RS485 Jbus/RS485 Jbus/RS485 RT RT RT ADAM4080 & Pt100 ADAM4080 & Pt100 ADAM4080 & Pt100 ELECDAN Counters ELECDAN Counters ELECDAN Counters DIRIS Ap DIRIS Ap DIRIS Ap 48VDC Power Supply 230/48VDC 6Amp 230VAC
EL SCADA Components Rad Tests • Mechanical design • No extra shielding,Light rack mounting • Statistics • 3 systems in // • Permanent monitoring • Human daily check • Costs • Components: 20kCHF • Work: 10kCHF • Conditions • Activated material • Not repairable • Not re-usable • Schedule • CNGS TSG46 • Time slot to be defined Rack Front view Rack Back view