1 / 11

C300 - Pressure Regulating

C300 - Pressure Regulating. C300 Options Available. Regulating Deluge Regulating Sprinkler Pump control-Regulating Pressure Control Valve. Types. Materials. C300 Regulating Valve - Common Components. C300 Pressure Sensing. Upstream. Downstream. pressure sensing:. pressure sensing:.

Download Presentation

C300 - Pressure Regulating

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. C300 - Pressure Regulating

  2. C300 Options Available Regulating Deluge Regulating Sprinkler Pump control-Regulating Pressure Control Valve Types Materials

  3. C300 Regulating Valve - Common Components

  4. C300 Pressure Sensing Upstream Downstream pressure sensing: pressure sensing: • Pressure relief • Deluge • Sprinkler • PVC • Pump control

  5. Deluge with Pressure Control C300 Control Water Discharge

  6. C300 Valve Deluge - Pressure Regulating Pilot regulator tocontrol pressure Multi-way actuator On/Off - To Open/Close Vent port Regulator controls flow in/out of cavity Outlet pressure sensing port Inlet sensing port In/Out port to cavity

  7. C300 Regulating Deluge Valve in Closed Position Air pressure ‘ON’ 3 - 12 bar Regulator ‘LOW’ position prevents water entering the valve cavity. Actuator in closed position diverts water to valve cavity Pilot water by-passes Pilot Regulator System Pipe Empty Water Supply Cavity pressure keeps sleeve closed

  8. C300 Regulating Deluge Valve - Opening Air Supply ‘OFF’ Control water to waste Actuator in operated mode switches ports Regulator ‘LOW’ position prevents water entering the valve cavity. Cavity Vents allowing the sleeve to lift from its seat. Water Enters System Pipe work Water Supply

  9. C300 Regulating Deluge Valve - Low system pressure Air Supply ‘OFF’ Control water to waste Cavity Vent remains open. Spring pressure greater than water pressure Regulator ‘LOW’ position prevents water entering the valve cavity. More water enters system pipe work Water Supply Pressure increases

  10. Regulating Deluge Valve - High System Pressure Air Supply ‘OFF’ Water Pressure greater than spring pressure Regulator in ‘High’ position allows water to enter cavity Vent port closes Water Pressurises Sleeve Flow reduces Pressure reduces

  11. C300 - Pressure Regulating

More Related