NS 300/500 - Parameter Read Sequence. Set MOD=1. Set Command Code [08h] C_STRT=1. Command Code = Command Code_R Parameter # =Parameter #_R C_STRT_R=1. Set Parameter # [0800h]. MOD_R=1. Read Response Data (Value In Hex). MOD_R=0. Command Code <> Command Code_R
E N D
NS 300/500 - Parameter Read Sequence Set MOD=1 Set Command Code [08h] C_STRT=1 Command Code = Command Code_R Parameter # =Parameter #_R C_STRT_R=1 Set Parameter # [0800h] MOD_R=1 Read Response Data (Value In Hex) MOD_R=0 Command Code <> Command Code_R Parameter # <> Parameter #_R C_STRT_R=0 Set C_STRT=0 Note: Example uses Pn800 for parameter # C_STRT_R=0 C_STRT_R=1 Important: Reset to zero or populate the command code and Parameter # Area to the appropriate data value before setting MOD=0; otherwise, command bits conflict may result in A.95 alarm.
NS 300/500 - Parameter Write Sequence Command Code = Command Code_R Parameter # =Parameter #_R Parameter Value = Parameter Value R C_STRT_R=1 Set Command Code [09h] C_STRT=1 Set MOD=1 Set Parameter # [0800h] Parameter Value [3] MOD_R=1 Parameter is set MOD_R=0 Command Code <> Command Code_R Parameter # <> Parameter #_R Parameter Value <> Parameter Value R C_STRT_R=0 Set C_STRT=0 Note: Example uses Pn800 for parameter # C_STRT_R=0 C_STRT_R=1 Note: After last parameter is set a “Reset Module” [Command Code = 1110] is required to commit the changes.