Legislation Electricity Act 1992 plus amendments Electricity Regulations 2003 • AS/NZS 3000 wiring rules • AS/NZS 3760: 2003 Inservice Safety Insp. & test. • AS/ NZS 3012:2003 Con. & Demo sites.
ElectricityRegulations Reg. 76(B) – AS/NZS 3760:2003 Inservice Safety Inspection & testing Electrical Equipment Reg. 69(B)(d) – AS/NZS 3012:2003 Electrical installations – Construction & demolition sites.
Standard AS/NZS 3012:2003 Applies to all construction & demolition sites.
Key points - AS/NZS 3012:2003 • Support of cables entering switchboards –’flexible’. • All final sub-circuits protected by 30mA RCD’s. • Construction wiring must be separate to perm wiring. • Minimum flexible cord size 1.00mm2 • Leads – Protect from mechanical damage. • – Supported off the floor.
Lighting Festoon lamps • Lampholder permanently moulded to cable. • Non-conductive, mechanical guard. • Supported at least 2.5m from the floor.
Lighting - portable Portable lamps Must have a rating of IP2X or higher.
Inspections • Prior to initial service • Where new, supplier to test & tag. • Before return to service after servicing or repair. • Can use an individual tag or register. • Competent person can carry out testing & tagging. • Only a registered person with a current practicing license can carry out electrical repairs. Testing & Tagging
Testing & Tagging Table 2 • 3 Monthly – Portable equipment. • RCD’s – trip test daily before use. (portable gear) – monthly (fixed). • RCD’s testing every: – 3 months portable. – 12 months fixed.
Testing & Tagging Sheds & switchboards. Require Certificate of compliance on completion of installation.
Testing & Tagging - continued • Testing & tagging – visual inspections. • All electrical devices made to AS/NZS 3105 do not comply with AS/NZS 3012:2003.
Testing & Tagging - continued Compliance Plug boxes • Jackson(comply) • PDL(comply) • Others do not currently comply with AS/NZS 2012. (domestic plug boxes)