1 / 13

TT300 Centrifugal Compressor APPLICATIONS www.turbocor.com

TT300 Centrifugal Compressor APPLICATIONS www.turbocor.com. ARI 550/590 - 1998. IPLV (COP) = 0.01* A + 0.42* B + 0.45* C + 0.12* D A: EER or COP at 100% capacity B: EER or COP at 75% capacity C: EER or COP at 50% capacity D: EER or COP at 25% capacity

swain
Download Presentation

TT300 Centrifugal Compressor APPLICATIONS www.turbocor.com

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. TT300 Centrifugal Compressor APPLICATIONS www.turbocor.com

  2. ARI 550/590 - 1998 IPLV (COP) = 0.01*A + 0.42*B + 0.45*C + 0.12*D A: EER or COP at 100% capacity B: EER or COP at 75% capacity C: EER or COP at 50% capacity D: EER or COP at 25% capacity IPLV (kW/Ton) = (0.01/A + 0.42/B + 0.45/C + 0.12/D) A: kW/Ton at 100% capacity B: kW/Ton at 75% capacity C: kW/Ton at 50% capacity D: kW/Ton at 25% capacity 1

  3. Integrated Part Load Value Weighted average values % load 100 75 50 25 1992 standard 17% 39% 33% 11% 1998 standard 1% 42% 45% 12% ARI Standard 550/590-98

  4. Flooded Type Evaporator and Water Cooled Condenser (L. App) R134a Conclusion: On IPLV basis, the TT300 is 45% more efficient than the leading screw compressor.

  5. Turbocor vs. Screw Flooded Evaporator and W/C Condenser

  6. DX Type Evaporator and Water Cooled Condenser R-134a Conclusion: On IPLV basis, the TT300 is 32% more efficient than the leading screw compressor.

  7. Turbocor vs. Screw D-X Evaporator and W/C Condenser

  8. DX Evaporator and Air Cooled Condenser R134a Conclusion: On IPLV basis, the TT300 is 29% more efficient than the leading screw compressor.

  9. Turbocor vs. ScrewD-X Evaporator and A/C Condenser

  10. Notes • Further 3 to 5% efficiency increase when dual compressors used on common circuit HXs.

  11. Percent Oil Efficiency Loss Percent Oil

  12. The energy revolution in air-conditioning and refrigeration compressors…

  13. The energy revolution in air-conditioning and refrigeration compressors…

More Related