Flight Testing of the FAA OBIGGS On the NASA 747 SCA. William Cavage AAR-440 Fire Safety Branch Wm. J. Hughes Technical Center Federal Aviation Administration. International Systems Fire Protection Working Group Place de Ville Tower C Ottawa, Canada February 14-15, 2005 . Outline.
E N D
Flight Testing of the FAA OBIGGS On the NASA 747 SCA William CavageAAR-440 Fire Safety BranchWm. J. Hughes Technical CenterFederal Aviation Administration International Systems Fire Protection Working Group Place de Ville Tower C Ottawa, Canada February 14-15, 2005
Outline • Background • Goals and Objectives • System Architecture • OBIGGs Installation • Instrumentation and Summary of Testing • Results • OBIGGS Performance • Fuel Tank Inerting • Summary AAR-440 Fire Safety R&D
Testing Goals and Objectives • Study the FAA dual flow methodology as well as a variable flow system methodology and expand upon existing system performance data • Develop/validate system sizing data • Validate previous in flight inert gas distribution modeling done by FAA • Additionally study CWT flammability in flight (not discussed in this presentation) AAR-440 Fire Safety R&D
OBIGGS - System Architecture • Uses Air Separation Modules based on HFM technology • Accepts hot air from aircraft bleed system • Cools, filters, and conditions air using heat exchanger air from external scoop • Air is separated by ASMs and NEA is plumbed to output valves to control flow • OEA is dumped overboard with H/X cooling air through dedicated scoop under aircraft on pack bay panel • System configured to operate in a dual flow methodology for some tests and a variable flow methodology for others • Prototype OBIGGS components wired to a system control box by a single cable AAR-440 Fire Safety R&D
OBIGGS - System Installation • System installed in empty pack bay area by FAA as designed by Shaw Aero Devices with the System Interfacing • Mounted with 6 brackets to the fairing super structure • Gets bleed air from small T put in 8” main bleed duct • NEA deposited in bay 6 of the compartmentalized (6 bays) CWT with no cross-venting in tank (vent system half blocked) • Two exterior panels replaced with FAA test article panels which have the H/X scoops installed • System controlled by box in cabin • Manually controlled ASM air temperature AAR-440 Fire Safety R&D
FAA OBIGGS Installation Drawing in 747 Pack Bay AAR-440 Fire Safety R&D
Photos of FAA OBIGGS Installation on 747 SCA AAR-440 Fire Safety R&D
Instrumentation and DAS • OBIGGS system pressures and temperatures same as in previous testing • Eight sample locations within the CWT in six different bays • FAA (OBOAS) utilized • Aircraft altitude measured by pressure transducer • Measured flammability of CWT and #2 wing tank • Laboratory DAS utilized • Simple out-of-the-box solution AAR-440 Fire Safety R&D
Instrumentation Racks Mounted in NASA 747 SCA Existing Power Distribution Rack OBOAS DAS Rack NDIR Analyzer FAS Rack AAR-440 Fire Safety R&D
Flight Test Plan • Operated system in dual flow configuration for first test and in variable flow configuration for remainder of testing • Did a series of 7 flight tests ranging from 2 to 5 hours totaling approximately 30 hours of flight time • Validated the two-flow mode methodology and studied maximizing system flow during top of descent • Studied effect of CWT fuel on inerting and demonstrated the ability of a system to reduce the flammability exposure of an aircraft • Examined the effects of long cruise times on system performance • Examined existing fleet flammability with baseline flammability testing AAR-440 Fire Safety R&D
747 SCA Results - System Performance • System performed as expected with predictable ASM dynamic characteristics • Less bleed air pressure in cruise and greater deviations • The data does not indicate deviations decreases the system efficiency AAR-440 Fire Safety R&D
747 SCA Results - System Performance • Correlation of pressure and flow for low flow mode as expected with test 1 data slope deviating from test 2 and 4 slope somewhat • Probably an indication of system being operated (warmed up) before start of flight test • As fiber gets warmer it becomes more permeable but more selective AAR-440 Fire Safety R&D
747 SCA Results - System Performance • Correlation of pressure and flow for high flow difficult to see because of constantly varying ASM pressure • Some data illustrates excellent correlation because of the stabilization of system temperature • Other data illustrates wide range of results probably due to constantly changing ASM conditions due to jockeying ASM pressure • Delays in [O2] Instru-mentation make this even more difficult AAR-440 Fire Safety R&D
747 SCA Results - Fuel Tank Inerting • Evolution of oxygen concentration from bay-to-bay typical of previous scale model and ground testing • Oxygen concentration spike in bay 1 greater than in modeling exercises (spiked to 19.5%) • Obtaining higher NEA flows with a wider orifice (variable flow valve) at the top of cruise more difficult than anticipated due to high back pressure on NEA output at times AAR-440 Fire Safety R&D
747 SCA Results - Fuel Tank Inerting • Average ullage oxygen concentration data illustrates system worked as expected for a approximately 42 minute descent • Resulting ullage oxygen concentration about 11% • Average spiked to 13.5% oxygen by volume • Descent had a 10 minute hold AAR-440 Fire Safety R&D
747 SCA Results - Fuel Tank Inerting • Comparison of average ullage oxygen concentration for 4 tests with different descent profiles that have similar features • Main parameters that effect the average ullage oxygen concentration are descent time and change in altitude AAR-440 Fire Safety R&D
747 SCA Results - Fuel Tank Inerting • Comparison of peak worst bay (bay 1) oxygen concentration for same 4 tests illustrates very similar relationships • Average peaks correlate directly with worst bay peaks in oxygen concentration • Worst bay peak tends to be sensitive to average peak oxygen concentration AAR-440 Fire Safety R&D
747 SCA Results - Fuel Tank Inerting • Comparison of oxygen concentration distribution for same 3 tests with similar descent profiles illustrates pattern • Have to extrapolate test 1 because does not have 42 min descent • Greater flow tended to allow better distribution but had little if any effect on the resulting oxygen concentration 46 Min Descent 42 Min Descent 42 Min Descent AAR-440 Fire Safety R&D
747 SCA Results - Fuel Tank Inerting • Tank oxygen concentration evolution after landing shows previously measured relationship • Worst bay [O2] goes from 13% to 12% in one hour • After 3 hours band of oxygen concentration is about 1% • Increase in average ullage [O2] probably not real Increase in average ullage [O2] AAR-440 Fire Safety R&D
747 SCA Results - Fuel Tank Inerting • Tank oxygen concentration change overnight illustrated expected results Line does not reflect Expected trend • Overall average ullage oxygen concentration rose about 1% • Bay oxygen concentrations completely equilibrated AAR-440 Fire Safety R&D
Summary • FAA dual flow OBIGGS concept validated and variable flow methodology studied • Lower ASM pressures will give less NEA production from OBIGGS but wide varying system aircraft parameters had no noticeable adverse effect on the resulting system performance • Increasing flow during the bottom of descent (variable flow valve) had little effect on the resulting oxygen concentration but did increase inert gas distribution in a compartmentalized tank AAR-440 Fire Safety R&D
Summary • Fuel tank inerting results illustrated expected relationships between system performance and ullage oxygen concentration • Dual flow methodology allows for relatively small OBIGGS, when sized correctly, to provided complete flight cycle protection for virtually all expected commercial transport airplane missions • Inert gas distribution accomplished easily in single bay tank while differences in multiple-bay tank [O2] tend to equilibrate readily • Fuel load effected ullage oxygen concentrations very little if at all • Proper sizing of inerting system will tend to minimize peak worst bay oxygen concentrations in multi-bay CWTs • Inert gas dispersion from CWT during long ground operations and overnight sits does not appear to be a problem AAR-440 Fire Safety R&D