An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Advanced Heat Load Estimating In Class Exercise – Week 2

  2. Ductwork Heat Gains: Example: A duct that is 2500mm x 650mm runs through a plant room for 25m before entering a conditioned space. The plant room temperature can be taken as 35°C and the supply air temperature is 12.5°C. The air velocity is 6m/s. Find the heat gain to the conditioned air, • No Insulation. 22,326W • 25mm Insulation 3,898W • 50mm Insulation 2,126W

  3. Ductwork Heat Gains: Example: A Return Air riser that is 1500mm x 1300mm runs vertically up a building to the mid rise plantroom (35m). Two sides of the riser joins a conditioned space while two sides join a fire stair and a toilet area. The return air temperature is 24°C. The air velocity is 6m/s. Find the heat gain to the conditioned air, • 90mm Common Brick i. How much air is flowing in the Return Air riser? ii. Find the heat gain to the riser.

  4. Zoning: Case Study: • AQIS – Constant volume, variable temperature system. Chilled water central plant, hot water reheat. Perimeter Zone/s & Centre Zone/s • Gateway Building Level 47 – Variable volume, constant temperature Chilled water central plant, hot water reheat. Perimeter Zone/s & Centre Zone/s How deep are the perimeter zones?